Page 2 PB SERIES BOILER INSTALLATION AND OPERATING INSTRUCTIONS
CONTENTS
General ....................................................................... 2
Codes, Rules and Regulations ................................... 2
Boiler Location ............................................................ 3
Chimney and Breeching ............................................. 3
Combustion and Ventilation ........................................ 3
Inspection ................................................................... 4
Jacket Assembly ......................................................... 4
Cleanout Cover Plates ................................................ 4
Boiler Trim ......................................... (water)5, (Steam)11
Thermostat and Limit Controls .......... (water)5, (Steam)12
Piping Connections ............................ (water)6, (Steam)11
Circulators .................................................................. 8
Domestic Hot Water Heaters ............. (water)9, (Steam)15
Filling the System .............................. (water)8, (Steam)14
Boiler Maintenance ...................... (water)9-10, (steam)15
Special Boiler Cable Installation ............................... 16
Replacement Parts ................................................... 19
Start-Up Checklist .................................................... 21
Burner Specifications ............................................... 22
GENERAL
The PB boiler-burner unit is a wet-base, vertical flue,
low pressure, sectional, cast iron steam or hot water
heating boiler. It is rated for natural draft firing with
-0.02" W.C. over the fire draft.
The ports between sections are provided with a special
hydronic seal which is resistant to petroleum products.
The flue gas seal between sections is accomplished by
the use of fiberglass rope rated at 1000 ° R
Packaged units are hydrostatically tested for the maxi-
mum working pressures.
An insulated metal jacket is furnished to both enhance
the units looks and to minimize any heat loss. A
full access cleanout cover for cleaning vertical flue
passages is on the left hand side of the boiler and is
accessible by removing the left hand cleanout access
jacket panel.
The PB boiler is offered in 2 different configurations:
1 - Packaged boiler with "burner in the box" shipped
separately.
2 - Packaged boiler with burner mounted and wired.
CODES, RULES AND REGULATIONS
The installation of the boiler, the burner, wiring, controls
and fuel piping must be done in accordance with the
requirements of the local authorities having jurisdiction.
In the absence of local requirements, the following
codes apply:
ANSI/NFPA31 - "Installation of Oil Burning Equipment"
ANSI/NFPA70- "National Electrical Code"
In Canada the following codes apply:
CSA STD. B149 - Latest Edition.
"Installation Code For Oil Burning Equipment."
CSA STD. C22.2 No. 0 - Latest Edition.
"General Requirements - Canadian Electrical Code
Part I1."
All completed boilers shall satisfactorily pass the
hydrostatic tests as prescribed by A.S.M.E., Code
Section IV.
,
,
,
Steam Boilers - The assembled boiler shall be
subjected to a hydrostatic test of not less than 45
psig.
Water Boilers - The assembled boiler shall be
subjected to a hydrostatic test pressure of 60 psig.
The required test shall not exceed the test pressure
by more than 10 psig.