INSTALLATION GUIDE
hidglobal.com An ASSA ABLOY Group brand
GOVERNMENT SOLUTIONS for Physical Access
R10-H, RP10-H, R40-H, RP40-H, RK40-H,
RPK40-H, RKCL40-P, RPKCL40-P, RKCLB40-P
pivCLASS® Reader
Parts
1 - Reader and base plate assembly
1 - Installation guide
2 - Terminal connector - terminal readers only
RKCL40, RPKCL40 & RKCLB40
4 - M3.5 mm x 12 mm Phillips machine screw
4 - #6-32 x .375” Phillips self-tapping machine screw
4 - #6 x 1.5” Phillips sheet metal screw
3 - #6-32 x .4375” Spanner security screw, anti-tamper (black)
3 - #6-32 x .4375 Phillips security screw (black)
1 - Mounting gasket
Recommended
• Cable, 6 conductor, 22 or 24 AWG [65 mm or 51 mm] Twisted Pair, Over-All Shield (Belden 3108A or equivalent) - RS-485-FDX +
power
• Cable, 4 conductor, 22 or 24 AWG [65 mm or 51 mm] Twisted Pair, Over-All Shield and UL approved (Belden 3107A, or equivalent) -
RS-485-HDX + power
• Cable, 6 to 9 conductor, 22 or 24 AWG [65 mm or 51 mm] Over-All Shield, (Alpha 1296C or equivalent) - Wiegand + power
• DC power supply
• Metal or plastic double-gang junction box - RPKCL40 / RPKCL40 / RKCLB40
• Metal or plastic single-gang junction box - R10 / RP10 / R40 / RP40 / RK40 / RPK40
• Reader spacer when using metal junction boxes - see pivCLASS How to Order Guide
• Security tool (for spanner security screw, anti-tamper) HID 04-0001-03
Specifications
pivCLASS Protocol
PRODUCT BASE PART
NUMBER
INPUT VOLTAGE
(VDC)
CURRENT OPERATING
TEMPERATURE CABLE LENGTH UL REF
NUMBER
Standby
AVG1
Maximum
AVG2PEAK3
R10-H 900NHR
12VDC
60mA 100mA
200mA
-30° to 150° F
(-35° to 65° C) RS-485 = 500 ft - 22 AWG
(152 m)
300 ft - 24 AWG
(91 m)
R10Ex1x2x3
RP10-H 900PHR 75mA RP10Ex1x2x3
R40-H 920NHR 65mA 110mA R40Ex1x2x3
RP40-H 920PHR 85mA RP40Ex1x2x3
RK40-H 921NHR 85mA 125mA 220mA RK40Ex1x2x3
RPK40-H 921PHR 95mA RPK40Ex1x2x3
RKCL40-P 923NPR 150mA 185mA 250mA -4° to 122° F
(-20° to 50° C)
RKCL40Ex1x2x3
RPKCL40-P 923PPR RPKCL40Ex1x2x3
RKCLB40-P 924NPR 165mA 215mA 275mA 14° to 122° F
(-10° to 50° C) RKCLB40Ex1x2x3
R10, RP10, R40, RK40, RP40 & RPK40
2 - M3.5 mm x 12 mm Phillips machine screw
3 - #6-32 x .375” Phillips self-tapping machine screw
2 - #6 x 1.5” Phillips sheet metal screw
1 - #6-32 x .375” Spanner security screw, anti-tamper
1 - Mounting gasket (optional, recommended for outdoor
installation)
1 StandbyAVG-RMScurrentdrawwithoutacardintheRFeld.
2MaximumAVG-RMScurrentdrawduringcontinuousPIVcardreads.NotevaluatedbyUL.
3 Peak-highestinstantaneouscurrentdrawduringRFcommunication.
UL Reference Number Deciphering
x1Reader Colors: K = Black
x2 Wiring: N = Pigtail, T = Terminal
x3 Communications: N = No Module, R = RS-485
PLT-01134 A.8