GST I-9105R Manuel utilisateur


I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
CONTENTS
I Overview.......................................................................................1
II Features........................................................................................1
III Technical Specifications................................................................2
IV Structure and Operation Principle.................................................4
V Mounting and Wiring.....................................................................6
1. Ambient Conditions for Installation............................................6
2. Mounting Height and Position....................................................7
3. Mounting..................................................................................10
4. Wiring......................................................................................13
VI Commission................................................................................14
VII Cautions......................................................................................16
VIII Operation....................................................................................16
1. Reading Information................................................................16
2. Setting Address Code..............................................................17
3. Setting Sensitivity Level...........................................................17
4. Setting the Device Type...........................................................17
5. Other Functions.......................................................................18
IX Troubleshooting ..........................................................................19
X Maintenance ...............................................................................20
XI Accessories.................................................................................21
Appendix 1 Warnings.........................................................................22
Appendix 2 Warranty..........................................................................23

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
1
I Overview
I-9105R Intelligent Reflective Beam detector (the detector) is an
addressable reflective infrared beam smoke detector that has two
signal output ways: loop output and contact output. When the detector is
connected with GST fire alarm control panel directly, state information
will be transmitted through loop between the detector and the control
panel. The detector can be programmed by GST programmer. Code
range is within 1~242. When the detector is not connected with the
control panel, fire and fault information can be transmitted by contacts.
The detector must be used together with a reflector. The number of
reflector(s) to be used (one or four) depends on the distance from the
detector.
With excellent built-in microprocessor, the detector has strong ability of
analysis and judgment. The detector can carry out system adjustment,
compensation of variation of ambient data, and judgment of fire and
fault through fixed algorithm. With new and reasonable design,
esthetical pleasing, flexible judgment and alignment method, it’s easy to
install and adjust. The sensitivity of the detector can be set through
hand held programmer in field, decreasing the demand for cleanliness
of field conditions, and enlarging application areas.
The detector is applicable to historical buildings, warehouses, large
storages, shopping malls, leisure centers, exhibition halls, hotel lobbies,
printing houses, clothing factories, museums and prisons, as well as
places where slight smoke particles.
II Features
1. Wide operating voltage range, big monitoring areas.
2. Combination of the emitting and receiving part makes mounting
easy and optical pathway accurate.

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
2
3. Built-in microprocessor enables intelligent judgment about fire
alarm and fault.
4. The detector can calibrate automatically, which ensures a single
person complete adjustment in short time. It’s also convenient to
operate.
5. Self-diagnosis function can monitor the inner fault.
6. Automatic compensation for factors weakening received signals,
such as a certain of dust contamination, positional excursion and
ageing transmitter.
7. Simple to control and operate by integrating digital bus protocol.
8. Electronically addressed. The address can be programmed in field.
9. Two sensitivity levels can be set in field.
10. The detector’s optical pathway is designed with strong
anti-interference ability.
11. SMT processing technology.
12. Attractive and decent appearance.
13. Standard: EN 54-12.
III Technical Specifications
1. Operating Voltage: 24VDC (15V~28V)
2. Operating Current:
Power current: Commission current ≤20mA
Standby current ≤8mA
Alarm current ≤12mA
3. Loop Output:
Loop Voltage: 24V (15V~28V)
4. Fire, fault contact output
Fire output contact: contact capacity is 28V/2A. Normally open in
normal state, closed in fire condition.
Fault output contact: contact capacity is 28V/2A. Closed in normal

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
3
state, and open in fault condition.
5. Angle of Adjusting: -6°~+6°
6. Maximum angular misalignment: ±0.5°
7. Sensitivity Level:
Level 1: 1.61dB
Level 2: 2.31dB
8. Indication of Detector State:
Commission: Green LED and yellow LED are lit or flashed in a
certain way. Refer to details in Section VI Commission.
Normal monitoring state: Red LED flashes periodically.
Fire: Red LED illuminates when the detector reports fire alarm.
Fire output contact is closed. The fire signal can be transmitted to
the control panel through loop and has to be cleared by the control
panel. Power on the detector again to clear the fire signal if GST
control panel is not connected.
Fault: Yellow LED illuminates. Fault output contact is open. The
detector clears the fault signal automatically if the condition
causing the fault disappears.
Optical pathway obscured totally: the detector first gives fault
signal and turns on yellow LED. 15 second later, it reports fire
alarm, and red LED is turned on; fire output contact is closed.
Yellow LED is turned off, fault output contact is closed. Note: In
this case, it does not necessarily mean there is a fire. After
the obscuration is removed, the detector clears the fault
signal automatically. If fault signal turns to fire signal, it has
to be cleared by the control panel or cutting off power.
9. Operating Environment:
Temperature: -10°C~+50°C
Relative Humidity≤95%, non condensing
10. Monitoring Area: Maximum monitoring area: 14×100=1400m2
Maximum width: 14m

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
11. Length of Optical Pathway: 8m~100m
12. Ingress Protection Rating:
It is IP20 in ordinary environment; it is IP66 through glue-seal
treatment in special environment.
13. Dimensions:
Length: 206mm Width: 95mm Depth: 95mm
14. Material and Color of Enclosure: ABS, gray
15. Weight: 450g
16. Mounting Hole Spacing:
Spacing for embedding: 158mm
Spacing for surface mounting: 79mm×96mm
IV Structure and Operation Principle
1. Appearance of the detector is shown in Fig. 1.
Cable Entry
Commission
Zone LEDs
Receiving
Windo
w
Emitting
Window
Fig. 1
2. Internal devices of the detector and positions to be glued are
shown in Fig. 2.
4

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
5
Fig. 2
3. Operation Principle
The detector and reflector are placed oppositely. The detector includes
emitting part and receiving part. Infrared beam of certain intensity sent
out from the emitting part is reflected by the right-angle prisms of the
reflector, and then received by the receiving part of the detector. The
receiving part simultaneously collects and amplifies the returned
infrared beam, analyze and judge the collected signals through its
microprocessor. When the detector is in normal monitoring state, the
intensity of infrared beam received by the receiving part is steady at a
certain level. When smoke particles enter the detecting area, the
intensity of infrared light received by the receiving part falls owing to
light scattering. When the smoke particles reach a certain density, and
the intensity of infrared light received by the receiving part is reduced
below the preset threshold value, the detector alarms fire, illuminates
red LED. And fire output contact is closed. If connected with GST
control panel, the fire signal will be passed to the panel through loop.
Operation principle is shown in Fig. 3.
A
djusting Wheel
To Be Glued
Mounting Direction
Rotary Rack
Flexible Cable
Reed Switch
To Be Glued

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
Smoke
Reflector
Detector Body
Mounting
Bracket
Infrared
Beam
Fig. 3
V Mounting and Wiring
1. Ambient Conditions for Installation
The detector works on light obscuration principle. Avoid any fixed or
moving obscuration in its optical pathway when installing.
The wall for mounting either the detector or the reflector should be firm
and smooth. The detector is mounted vertical to the wall. The wall may
seem to be smooth, but corrugated or uneven, or may be changed by
the environment (in rainy season or in winter) and the installer should
ensure the detector not affected by these factors. If the detector is
installed on sustaining rack similar to metal tube, make sure the
sustaining rack fixed firmly.
Not Fit For Locations where:
¾Space height is over 40m.
¾It is not roofed.
¾Space height is less than 1.5m.
¾There are a lot of dust, powder or vapor.
6

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
¾It is clean normally, but can be dusty in some special cases.
¾Temperature is high. Note: Temperature at top part of a
workshop with transparent roof may be over 50℃when
there is sunshine.
¾There is no access for maintenance.
¾The Mounting wall or fitting is greatly affected by mechanical
vibration.
¾There are fixed or moving objects within 1m from the
detector’s optical pathway.
¾There is strong magnetic field.
2. Mounting Height and Position
The mounting height of the detector and reflector should be most
accessible by smoke into beam zone. The following recommendations
are for reference:
a) When space height is not over 5m, the detector and reflector
should be mounted on the two facing walls 0.5m from the ceiling, as
shown in Fig. 4.
Reflector
Detector
5m
4.5m
Fig. 4
7

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual The Intelligent Solution
b) When space height is between 5m and 8m, the detector and
reflector should be mounted on the two facing walls 0.5m to 1m
from the ceiling, as shown in Fig. 5.
Detector
Reflector
7m
6m
Fig. 5
c) When space height is more than 8m, the roof is normally
gabled without ceiling, the detector and reflector should be
mounted on the two facing walls about 8m from the floor, ensuring
that the vertical distance between the detector/reflector and top of
the building is not less than 0.5m, as shown in Fig. 6. The distance
should be 7m from the detector to the floor.
8
Table des matières
Autres manuels GST Capteur de sécurité

GST
GST DI-9104Exd Manuel utilisateur

GST
GST I-9106 Manuel utilisateur

GST
GST D-9107RExd Manuel utilisateur

GST
GST DC-M9103 Manuel utilisateur

GST
GST I-9602LW Manuel utilisateur

GST
GST I-9101 Manuel utilisateur

GST
GST DC-9103 Manuel utilisateur

GST
GST DC-9103 Manuel utilisateur

GST
GST DC-9103E Manuel utilisateur

GST
GST C-9201 Manuel utilisateur

GST
GST DC-9101(Ex) Manuel utilisateur

GST
GST C-9105R Manuel utilisateur