Galmet SG 40 Manuel utilisateur

Installation and operation manual
Buer vessel SG(B)
Type: Spiral coil: Insulation:
40
60
80
100
120
140
200
300
400
500
800
1000
1500
2000
3000
4000
5000
One spiral coil
Two spiral coils (bivalent)
With the maximum size spiral coil
Without spiral coils
Detachable
Nondetachable
Without insulation
Catalogue No. ...............................
Production date ............................
QC
Please read the instructions carefully before beginning the installation and use of the product.
www.galmet.euMade in Poland

Installation and operation manual of the SG(B) buers © All rights reserved - Galmet Sp. z o.o. Sp. K.2
1. Operation and use.........................................................................................................................................................................................................3
1.1. Boiler characteristics.....................................................................................................................................................................................3
1.2. Construction description...............................................................................................................................................................................3
1.3. Remember....................................................................................................................................................................................................3
2. General operating rules.................................................................................................................................................................................................4
2.1. Installation ...................................................................................................................................................................................................4
2.2. Start-up........................................................................................................................................................................................................4
2.3. Turning o the boiler....................................................................................................................................................................................4
3. Exemplary scheme of the installation ...........................................................................................................................................................................5
4. Technical specication ..................................................................................................................................................................................................6
4.1. Scheme - SG(B) 40, 60, 80, 100, 120, 140 wall-mounted, without spiral coils ..............................................................................................6
4.2. Technical parameters - SG(B) 40, 60, 80, 100, 120, 140 wall-mounted, without spiral coils .........................................................................7
4.3. Scheme - SG(B) 200 without spiral coils .......................................................................................................................................................8
4.4. Technical parameters - SG(B) 200 without spiral coils...................................................................................................................................9
4.5. Scheme - SG(B) 300-2000 without spiral coils............................................................................................................................................10
4.6. Technical parameters - SG(B) 300-2000 without spiral coils.......................................................................................................................11
4.7. Scheme - SG(B) 3000, 4000, 5000 without spiral coils................................................................................................................................12
4.8. Technical parameters - SG(B) 3000, 4000, 5000 without spiral coils...........................................................................................................13
4.9. Scheme - SG(B) 200 with one spiral coil......................................................................................................................................................14
4.10. Technical parameters - SG(B) 200 with one spiral coil.................................................................................................................................15
4.11. Scheme - SG(B) 300-2000 with one spiral coil............................................................................................................................................16
4.12. Technical parameters - SG(B) 300-2000 with one spiral coil .......................................................................................................................17
4.13. Scheme - SG(B) 400-2000 with two spiral coils ..........................................................................................................................................18
4.14. Technical parameters - SG(B) 400-2000 with two spiral coils......................................................................................................................19
4.15. Scheme - SG(B) 300 with the maximum size spiral coil ..............................................................................................................................20
4.16. Technical parameters - SG(B) 300 with the maximum size spiral coil..........................................................................................................21
4.17. Scheme - SG(B) 400 with the maximum size spiral coil ..............................................................................................................................22
4.18. Technical parameters - SG(B) 400 with the maximum size spiral coil..........................................................................................................23
4.19. Scheme - SG(B) 500 with the maximum size spiral coil ..............................................................................................................................24
4.20. Technical parameters - SG(B) 500 with the maximum size spiral coil..........................................................................................................25
5. Product che...............................................................................................................................................................................................................26
6. Declaration of Conformity...........................................................................................................................................................................................27
7. Maintenance and warranty.........................................................................................................................................................................................29
Table of contents

© All rights reserved - Galmet Sp. z o.o. Sp. K. Installation and operation manual of the SG(B) buers 3
1. Operation and use
1.1. Boiler characteristics
Buer tanks are used as batteries, which store the heat energy prepared by solid fuel boiler, which is then transmitted in a continuous mode to the heating
system of a central heating and warm usable water.
Buer tanks are not enamelled, thus they are suitable for storage of neutral medium only (e.g., demineralized boiler water, glycol, etc.). The maximum
allowable operating pressure is 3 bar (0,3 MPa) for buer tanks and 6 bar (0,6 MPa) for spiral coils.
Buer tanks complement the following: systems equipped with a heat pump; solar systems; CH boilers.
Buers can be supplied without thermal insulation or with high quality insulation made of hard polyurethane foam, which reduces heat loss to a minimum.
The tank may have a permanent insulation of hard polyurethane foam or detachable insulation made of soft polyurethane foam.
1.2. Construction description
The main part of the buer is the tank in which the heating medium is heated. It is made out of a steel sheet and painted with undercoat from the outside.
The buers have nine 6/4” (internally threaded) hydraulic connections, which makes it possible to connect them in various variants. Three ½" (internally
threaded) connections for the sensor covers are also included, as well as a 1" or 5/4”for type 3000 only (internally threaded) water drain connection at the
bottom of the tank.
1.3. Remember
1. Installation of the buer tank should be started by reading the installation and operation manual provided with the device. The manual should always
be in the place of use of the buer tank, as it is often required for inspection by the service.
2. Do not operate the buer tank without a properly functioning safety valve (applies to closed system).
3. The company is not responsible for safety valve malfunction caused by incorrect installation of the valve and installation errors.
4. Defects discovered during the warranty period should be reported to the manufacturer's service.
5. Vent the heating circuit before the start of the heating season.
6. Periodically check the lling level of the heating system.
7. If the buer tank is installed in a closed system, an expansion vessel must be installed. If the vessel is already installed, its capacity should be increased
accordingly.
8. It is not allowed to prevent water from dripping from the safety valve – do not clog the safety valve outlet. If the safety valve is leaking water all
the time, the pressure in the water supply installation is too high or the safety valve is defective. The valve outlet should be pointing down. It is
recommended to place a funnel for draining water under the valve. A hose can also be attached to the water outlet for draining leaks caused by opening
of the safety valve. The hose should be resistant to a temperature of +80°C, have an internal diameter of 9 mm and a maximum length of 1.2 m, be
led from the outlet with a downward grade (min. 3%) in an environment where the temperature does not drop below 0°C.The hose should be secured
against reduction in ow capacity (crushing, clogging) and its end should be visible (in order to check the functioning of the valve).
9. Galmet Sp. z o.o. Sp. K. reserves the right to make any modications and technical changes.
10. The tank has an outer casing made of articial leather (skay, PVC foil), while the thermal insulation is made of polyurethane or polystyrene foam. It is
not allowed to manipulate open re directly next to the tank, as it may damage the outer casing as well as the thermal insulation
11. All maintenance and installation works must be performed in accordance with applicable health and safety regulations.
1. Operation and use

Installation and operation manual of the SG(B) buers © All rights reserved - Galmet Sp. z o.o. Sp. K.4
2. General operating rules
2. General operating rules
2.1. Installation
- Buer tank should be installed in a dry room. The tank cannot be installed in rooms where the ambient temperature may fall below 0°C.
- The tank should be connected by a qualied installer. Conrmation of installation in the warranty card is required.
- Due to the design of the tank, it should only be installed in an upright position.
- Buer tanks are recommended to be installed close to the main heat source in order to avoid unnecessary heat loss.
- Buer tanks can be connected to open and closed systems.The heating system pressure (closed system) must not exceed the maximum operating pressure
of the tank (0,3 MPa).
- Buer tanks used in an open installation should be connected to an open vessel protected in accordance with PN-B02413.
- Buer tanks used in closed systems should be protected by a properly selected safety valve with a pressure not higher than the maximum operating
pressure of the tank (0,3 MPa). The installation should be additionally equipped with an expansion vessel of appropriate capacity.
2.2. Start-up
After connecting the entire central heating system you should:
1. Fill the heating system with a heating factor.
2. Check the hydraulic connections for any leaks.
3. Insulate the pipelines and tank connections.
4. Bleed the installation.
After completing all the steps, the central heating installation is ready to work. The rst heating of the buer tank should be carried out in the presence of
the installer in order to correctly check the operation of the whole installation.
Before bleeding the buer tank, make sure that the heating device is switched o and the heating system is not hot.
Before the rst start-up or after a long break in operation, check whether the entire installation is lled with the heating medium.
2.3. Turning o the boiler
In the event of interruption in use and the risk of freezing of the heating medium in the tank, the tank and the entire heating system associated with it
should be emptied.
Caution!
- It is prohibited to start the heating circuit if the buer tank is not lled with heating medium.
- The buer tank must not be used if a malfunction of the safety valve is found.
- It is forbidden to install devices (e.g. shut-o valve, non-return valve, etc. between the tank and the safety valve, or an open expansion vessel (a tee is
the only exception).
- It is forbidden to make any unauthorized repairs to the tank.
- It is not allowed to prevent the water leakage from the safety valve.

© All rights reserved - Galmet Sp. z o.o. Sp. K. Installation and operation manual of the SG(B) buers 5
3. Exemplary scheme of the installation
3. Exemplary scheme of the installation
ch boiler
for solid fuels
buer
replace
open equalising tank
oor heating radiator
safety valve
control valve
return valve
circulation pump
expansion vessel
equalising tank

Installation and operation manual of the SG(B) buers © All rights reserved - Galmet Sp. z o.o. Sp. K.6
4. Technical specication
4.1. Scheme - SG(B) 40, 60, 80, 100, 120, 140 wall-mounted, without spiral coils
460
200
50
GS1
GS2
Gw 1/2'
Gw 6/4'
Gw 6/4'
375
45°
140
Gw 1/2'

© All rights reserved - Galmet Sp. z o.o. Sp. K. Installation and operation manual of the SG(B) buers 7
4. Technical specication
4.2. Technical parameters - SG(B) 40, 60, 80, 100, 120, 140 wall-mounted, without spiral coils
Type SG(B) unit SG(B) 40 SG(B) 60 SG(B) 80 SG(B) 100 SG(B) 120 SG(B) 140
Storage capacity l 40 63 75 106 118 136
Tank’s maximum working temperature °C 95 95 95 95 95 95
Tank’s minimum working temperature °C 30 30 30 30 30 30
Tank’s maximum working pressure bar 3 3 3 3 3 3
Dimensions
CH boiler water connection height GS1 mm 175 175 175 175 175 175
CH boiler water connection height GS2 mm 305 505 690 840 940 1090
Height L mm 480 680 865 1015 1115 1265
External diameter (without insulation) d Ø 400 400 400 400 400 400
External diameter (with insulation) D Ø 460 460 460 460 460 460
Insulation - polyurethane foam
External housing - metal casing; ABS cover
Connections
CH boiler water connections - side Gw 6/4" 6/4" 6/4" 6/4" 6/4" 6/4"
CH boiler water connection - bottom Gw 1 ½" 1 ½" 1 ½" 1 ½" 1 ½" 1 ½"
Upper connection - bleeding Gw ½" ½" ½" ½" ½" ½"
Bottom connection - sensor cover Gw ½" ½" ½" ½" ½" ½"
Weight without insulation (empty) kg 25 31 35 40 49 55

Installation and operation manual of the SG(B) buers © All rights reserved - Galmet Sp. z o.o. Sp. K.8
4. Technical specication
4.3. Scheme - SG(B) 200 without spiral coils

© All rights reserved - Galmet Sp. z o.o. Sp. K. Installation and operation manual of the SG(B) buers 9
4. Technical specication
4.4. Technical parameters - SG(B) 200 without spiral coils
Type SG(B) unit SG(B) 200
Storage capacity l 223
Tank’s maximum working temperature °C 95
Tank’s maximum working pressure bar 3
Dimensions
CH boiler water connection height GS1 mm 220
Sensor cover or thermometer connection
height GS2 mm 312
CH boiler water connection height GS3 mm 483
Sensor cover or thermometer connection height GS4 mm 603
CH boiler water connection height GS5 mm 785
Sensor cover or thermometer connection height GS6 mm 885
CH boiler water connection height GS7 mm 220
CH boiler water connection height GS8 mm 553
Sensor cover or thermometer connection height GS9 mm 785
CH boiler water connection height GS10 mm 885
Height L mm 1105
External diameter (without insulation) d Ø 550
External diameter (with insulation) D Ø 670
Insulation mm 55
External housing - skay
Connections
CH boiler water inow / CH boiler water outow Gw 1 ½"
Sensor cover or thermometer Gw ½"
Water drain Gw 1"
Weight without insulation (empty) kg 60

Installation and operation manual of the SG(B) buers © All rights reserved - Galmet Sp. z o.o. Sp. K.10
4. Technical specication
4.5. Scheme - SG(B) 300, 400, 500, 800, 1000, 1500, 2000 without spiral coils
Ce manuel convient aux modèles suivants
33
Table des matières
Autres manuels Galmet Chaudière
Manuels Chaudière populaires d'autres marques

Vaillant
Vaillant uniSTOR VIH SW GB 500 BES Manuel utilisateur

Radijator
Radijator BIO max 23.1 Manuel utilisateur

Brunner
Brunner BSV 20 Manuel utilisateur

Buderus
Buderus Logamax GB062-24 KDE H V2 Manuel utilisateur

Potterton
Potterton 50e Fiche technique

UTICA BOILERS
UTICA BOILERS TriFire Manuel utilisateur