flowair HMI Manuel utilisateur

HMI
MANUAL
INSTRUKCJA
РУКОВОДСТВО
ПОЛЬЗОВАТЕЛЯ
www.flowair.com

This documentation contains key information for HMI controller safety electrical connection and
configuration guidelines.
For your safety it is recommended to comprehensive study HMI manual, before any
operations related to electrical connection.
It is suggested to keep this HMI manual for later use.
The manufacturer reserves the right to make revisions and changes in the operation manual at any
time and without notice, and also to make changes in the device without influencing its operation.

www.flowair.com
HMI MANUAL
3
ENGLISHPOLSKIРУССКИЙ
TABLE OF CONTENTS
1. GENERAL DESCRIPTION ............................................................ 4
2. TECHNICAL DATA ....................................................................... 4
2.1 Dimensions ........................................................................................................ 5
3. HMI PANEL ................................................................................... 5
3.1 Buttons description ...................................................................................... 5
3.2 Main screen ....................................................................................................... 6
4. FUNCTIONS AND MODES ......................................................... 7
4.1 Function modes ............................................................................................. 7
4.2 Fan functions .................................................................................................... 7
4.3 Working modes .............................................................................................. 7
4.4 Temperature sensor ..................................................................................... 8
4.5 Antifreeze ............................................................................................................ 8
5. SETTINGS MENU ......................................................................... 8
5.1 Parameters setting ........................................................................................ 8
5.2 Button lock/unlock ....................................................................................... 9
5.3 Clock setting ..................................................................................................... 9
6. PROGRAMMING ......................................................................... 10
6.1 Setting mode ................................................................................................... 10
6.2 Setting fan speed ........................................................................................... 10
6.3 Programming weekly programmer ................................................... 10
7. INSTALLATION ............................................................................ 12
7.1 Wall–mounting ............................................................................................... 13
8. WIRING DIAGRAM ...................................................................... 13
9. BMS COMMUNICATION ........................................................... 14
10. DECLARATION OF CONFORMITY ........................................... 15

HMI MANUAL
www.flowair.com
4
1. GENERAL DESCRIPTION
• HMI controller is compatible with LEO FB V–type water heaters.
• Automatic or manual 3–step fan speed adjustment.
• Control room temperature (by opening/closing the valve, or by
adjusting air volume automatically).
• Antifreeze mode – protection against dropping room temperature
below critical level.
• HMI controls up to 6 LEO V–type units (it is required to use RX signal
distributor while connecting more than one unit).
• Possibility to connect external NTC temperature sensor.
Power supply 230VAC/50Hz
Regulation Panel buttons / LCD display
Setpoint range +5 ÷ +40°C
Speed of the fan control range 3 steps
Storage conditions temperature –10 ÷ +60°C
Ambient temperature range 0 ÷ +50°C
Temperature sensor Built–in internal/
external NTC (option)
IP 20
Montage surface
Casing ABS & Acrylic material
Weekly programmer ON: 5d+2d, OFF
Rated switching power 830 W (single–phase motor)
2. TECHNICAL DATA

www.flowair.com
HMI MANUAL
5
ENGLISHPOLSKIРУССКИЙ
3. HMI PANEL
3.1 Buttons description
15. Mode changing button
16. Changing the fan speed button
17. Power ON/OFF button
18. Temprature up button (or parameters setting)
19. Temprature down button (or parameters setting)
2.1 Dimensions
15
17
16
18
19
13836,5
94

HMI MANUAL
www.flowair.com
6
3.2 Main screen
1. Fan Speed: LOW, MED, HI and AUTO
2. ROOM TEMP. or NTC EXTERNAL SENSOR TEMP.
(measured temperature)
3. SET TEMP. (desired temperature)
4. Cooling Mode
5. Heating Mode
6. Weekday
7. Clock
8. Buttons Lock
9. ON/OFF Status of time zones
10. Automatic programable mode
11. Manual mode
12. 6 Time Zones for each day
13. Anti–freeze indication
14. Ventilation Mode
6
10
13
2
1
14
8
3
9
11 4 5 12
7

www.flowair.com
HMI MANUAL
7
ENGLISHPOLSKIРУССКИЙ
4. FUNCTIONS AND MODES
4.1 Function modes
MANUAL MODE – Fan is operating with chosen speed (LOW, MED or
HI). There are three additional modes: Heating, Cooling and Ventilation.
According to set temperature, valve is opened/closed.
AUTOMATIC MODE – air volume V is regulated automatically
depending on differential between pre–set Set Temperature (3) and
measured Room Temperature (2) (there is no possibility to change fan
speed manually). In this mode there is possibility to resign from the
valve, heating source will control ow and proper temperature of
water.
4.2 Fan function
To choose fan function see point 5.1.
Continuous – after reaching pre–set temperature (3) valve is closed,
fan operating with:
MANUAL MODE - pre set speed (1)
AUTO MODE - low speed
Thermostatic – after reaching pre–set temperature (3) valve is closed,
fan stops operating.
4.3 Working mode
Heating – valve is open and fan is on when Room Temp. < Set Temp.
Cooling – valve is open and fan is on when Room Temp. > Set Temp.
Ventilation – fan is turned ON and operate with pre–set V.

HMI MANUAL
www.flowair.com
8
4.4 Temperature sensor
To choose sensor see point 5.1.
Internal – room temperature is measured by built–in sensor.
External – room temperature measured by external sensor NTC
(optional). It is possible to connect one external NTC sensor to one HMI.
NOTE!
Alarm will appear if there is error with internal or external
temperature sensor: E0.
4.5 Antifreeze
When external sensor or internal sensor detect temperature below 5°C
(default setting), valve and fan is about to open immediately even if the
thermostat is set on OFF status.
5. SETTINGS MENU
5.1 Parameters setting
• When HMI is switched off, press and hold MODE for 3 seconds.
• To change option use MODE button.
• To change value use +/– buttons.

www.flowair.com
HMI MANUAL
9
ENGLISHPOLSKIРУССКИЙ
Menu
setting Option Value
1 Temperature
calibration
–9°C ~ +9°C
2 Fan status C1: Thermostatic mode
C2: Continuous mode
3 Temperature
sensor
0: Internal Sensor
1: External Sensor NTC
4 Antifreeze 0: Off
1: On
5 Antifreeze +5°C ~ +10°C
6 Modbus ID setting 1~247( 01~F7)
5.2 Button lock/unlock
• To LOCK all buttons press and hold + and then – buttons for
5 seconds.
• To UNLOCK all buttons press and hold + and then – buttons for
5 seconds.
5.3 Clock setting
• When HMI controller is turned off, press and hold FAN button for
3 seconds and enter into time clock setting.
• Option sequence as follows: hour, minute weekday.
• To change option use FAN button.
• To change value use + and – buttons.

HMI MANUAL
www.flowair.com
10
6. PROGRAMMING
6.1 Setting mode
• Push shortly MODE button (15) to select Manual Mode
and Programmable Mode.
• Push MODE button (15) for 3 seconds and select Cooling Mode,
Heating Mode or Ventilation Mode.
6.2 Setting fan speed
• Push shortly FAN button (16) to select the fan speed: LOW, MEDIUM,
HIGH, AUTO.
6.3 Programming weekly programmer
• Push and hold FAN button for 3 seconds and program time, setpoints
and time zones accordingly.
Monday to Friday
1st time setting (Hour and Minute), 1st time zone ON or OFF, 1st
setpoint setting …….. 6th time setting (Hour and Minute), 1st time
zone ON or OFF, 6th setpoint setting.
Saturday
1st time setting(Hour and Minute), 1st time zone ON or OFF, 1st
setpoint setting …….. 6th time setting(Hour and Minute), 1st time
zone ON or OFF, 6th setpoint setting.
Sunday
1st time setting(Hour and Minute), 1st time zone ON or OFF, 1st
setpoint setting …….. 6th time setting(Hour and Minute), 1st time
zone ON or OFF, 6th setpoint setting.
Table des matières
Langues :
Manuels Thermostat populaires d'autres marques

EWELLY
EWELLY EW-181 Manuel utilisateur

Prolon
Prolon T1100 Instructions d'installation

Computherm
Computherm Q20 Manuel utilisateur

Heatmiser
Heatmiser neoStat Manuel utilisateur

Aube Technologies
Aube Technologies TH111GFCI-NP 240 VCA Manuel utilisateur

Mars
Mars HEAT CONTROLLER IR Wireless Thermostat Manuel utilisateur