If the level gauge is to display the level from the bottom even if the measuring
range of the sensor used is less than the maximum possible level in the meas-
ured sump/well (third case in the previous figure), then it is necessary to correct
the measured level with the Delta parameter. The numerical value of this pa-
rameter will be permanently added to the measured level height in the H531
unit. It is clear from the principle that the displayed level height will never fall
below the value of the Delta parameter in this case.
The approach to the Delta parameter is given in chap. 3-4-3 Delta on p. 31.
3.1.2. Installing the display unit
The H531 display unit is usually placed close to the measured level. The maxi-
mum possible distance between the submerged transducer and the display unit
is determined by the length of the connection cable between the transducer
and the unit.
If it is necessary to place the display unit
at a greater distance from the measured
sump/cell, then the connection cable can
be extended (see chap. 5.1.3 Extension of
the connection cable on p. 16), or order
an extra length of jumper cable from the
level meter manufacturer.
The mechanical design of the imaging unit
allows it to be placed outdoors, it is only
necessary to protect the unit with a suita-
ble cover from direct sunlight to prevent
gradual degradation of the plastic imag-
ing panel due to UV radiation.
The display unit is factory set to a power
saving display mode, in which the unit's
display wakes up only for a short time af-
ter pressing one of the unit's control but-
tons. The unit is powered by an internal
lithium battery in this mode.
If the level gauge is to be operated in the
mode with permanently switched on dis-
play of the measured level, then it is nec-
essary to connect to the H531 display unit
a source of external power supply voltage of 5 to 28 VDC (see chap. 5.2.2 on p.
19).
The installation of the level gauge is covered in more detail in the chapter 5.
Installation on p. 15.
The installation and commissioning of the level gauges with the H531-G
or H531-N communication module is described in chapter 7-Remote access on
p. 40.