EV Connection EVC63A 1P-Mod Protocol V1.0
EV Connection Sdn Bhd Tel: +603-78872912 Fax: +603-78062677
Add ess: Unit B716, Block B, Level 7, Kelana Squa e, Jalan SS7/26,
Kelana Jaya, 47301, Petaling Jaya, Selango , Malaysia
Website: www.ev-connection.com
Powe facto 1% of Unity
Active powe 1% of ange maximum
Reactive powe 1% of ange maximum
Appa ent powe 1% of ange maximum
Active ene gy Class 1 IEC62053-21
Class B EN50470-3
Reactive ene gy 1% of ange maximum
Environment
Ope ating tempe atu e -25
℃
to +55
℃
Sto age and t anspo tation tempe atu e -40
℃
to +70
℃
Refe ence tempe atu e 23
℃±
2
℃
Relative humidity 0 to 95%, non-condensing
Altitude up to 2500m
Wa m up time 10s
Installation catego y CAT III
Mechanical Envi onment M1
Elect omagnetic envi onment E2
Deg ee of pollution 2
Output
Pulse Output
The mete p ovides two pulse outputs. Both pulse outputs a e passive type.
Pulse output 1 is configu able. The pulse output can be set to gene ate pulses to ep esent total / impo t/expo t
kWh o kVa h.
The pulse constant can be set to gene ate 1 pulse pe : 0.001(default) /0.01/0.1/1kWh/kVa h.
Pulse width: 200/100/60ms
Pulse output 2 is non-configu able. It is fixed up with impo t kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The mete p ovides a RS485 po t fo emote communication. Modbus RTU is the p otocol applied. Fo Modbus RTU,
the following RS485 communication pa amete s can be configu ed f om the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parit : NONE/EVEN/ODD
Stop bits: 1 o 2
Modbus Address: 1 to 247
Mechanics
Din ail dimensions 36x99x63 (WxHxD) DIN 43880