Following these instructions allows for the Ethos IS100 wood fire
to be safely installed in a timber frame wall without the need for
further heat protection past that supplied as part of the Zero Clearance
Cabinet and the Econ-Air flue system (see notes regarding installation
on combustible surfaces).
WARNING: It is critical that these instructions are followed fully and
that no substitute parts are used.
INSTALLATION NOTES
1. Combustible materials must be kept a minimum of 25mm away from
all parts of the Zero Clearance Cabinet and the diameter 250 liner.
2. Adequate ventilation must be available for cooling the Zero Clearance
Cabinet - see installation diagram for supplied ventilation plate
mounting detail (page# 5).
3. Ethos insulation base panel (part# ZC1140) is required below the Zero
Clearance Cabinet when in direct contact with combustible materials
such as timber flooring (refer to page# 3 for further detail).