E+E Elektronik EE23 series Manuel utilisateur

BA_EE23_B2_e // v1.0 // technical data are subject to change // 194768
Operation Manual
EE23
Humidity/Temperature Sensor

E+E Elektronik Ges.m.b.H. doesn’t accept warranty and liability claims neither upon this publication nor in case of
improper treatment of the described products.
The document may contain technical inaccuracies and typographical errors. The content will be revised on a
regular basis. These changes will be implemented in later versions. The described products can be improved and
changed at any time without prior notice.
© Copyright E+E Elektronik Ges.m.b.H.
All rights reserved.
EMC note USA (FCC):
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
EMC note Canada (ICES-003):
CAN ICES-3 (A) / NMB-3 (A)

CONTENT
1 General .................................................................................................................................................4
1.1 Explanation of Symbols.................................................................................................................................4
1.2 Safety Instructions.........................................................................................................................................4
1.2.1 General Safety Instructions..................................................................................................................................4
1.2.2 Safety Instructions for the Alarm Output Module with Voltage >50V....................................................................4
1.2.3 Safety Instructions for the Integrated Power Supply (Option AM3)......................................................................4
1.3 Environmental Aspects..................................................................................................................................5
2 Scope of Supply ..................................................................................................................................5
3 Operating Components ......................................................................................................................6
3.1 Electronics Board for Model T1, T2, T4 and T6.............................................................................................6
3.2 Display for Model T1, T2, T4 and T6 .............................................................................................................7
3.3 Electronic Board for Model T5.......................................................................................................................8
3.4 Display for Model T5 .....................................................................................................................................9
4 Intallation ...........................................................................................................................................10
4.1 Mounting the Enclosure...............................................................................................................................10
4.2 Mounting the Sensing Probe .......................................................................................................................11
4.3 Electrical Connection...................................................................................................................................12
4.4 Connection Versions ...................................................................................................................................12
5 Calibration / Adjustment ...................................................................................................................14
5.1 Denitions....................................................................................................................................................14
5.2 Adjustment of EE23 Model T1, T2, T4 and T6 via Push Buttons on the Electronics Board........................14
5.2.1 2-Point RH Adjustment Procedure / T Adjustment Procedure............................................................................ 14
5.2.2 1-Point RH Adjustment Procedure / T Adjustment Procedure ........................................................................... 15
5.2.3 Return to Factory Calibration .............................................................................................................................15
5.3 Adjustment of the EE23 Model T5 via the USB Service Interface...............................................................16
6 Maintenance.......................................................................................................................................16
7 Troubleshooting ................................................................................................................................16
7.1 Fuse Replacement for Option AM3 .............................................................................................................16
8 Accessories and Spare Parts ..........................................................................................................17
9 Technical Data ...................................................................................................................................18
9.1 Operating Range Humidity Sensor..............................................................................................................19

4
Operating manual EE23 humidity / temperature sensor
1 General
This operation manual is part of the scope of supply and serves for ensuring proper handling and opti-
mal functioning of the device.
The operation manual shall be read before commissioning the equipment and it shall be provided to all
staff involved in transport, installation, operation, maintenance and repair.
The operation manual may not be used for the purposes of competition without the written consent of
E+E Elektronik® and may not be forwarded to third parties. Copies may be made for internal purposes.
All information, technical data and diagrams included in these instructions are based on the information
available at the time of writing.
1.1 Explanation of Symbols
This symbol indicates safety information.
It is essential that all safety information is strictly observed. Failure to comply with this information can
lead to personal injuries or damage to property. E+E Elektronik® assumes no liability if this happens.
This symbol indicates instructions.
The instructions shall be observed in order to reach optimal performance of the device.
1.2 Safety Instructions
1.2.1 General Safety Instructions
• Avoid any unnecessary mechanical stress and inappropriate use.
• Replacetheltercapwithutmostcare,sothattheltercapdoesnottouchthesensingelementsof
the sensing head at any time.
• Do never touch the sensing elements.
• Forsensorcleaningandltercapreplacementpleasesee“Cleaninginstructions”atwww.epluse.com.
• Installation,electricalconnection,maintenanceandcommissioningshallbeperformedbyqualied
personnel only.
1.2.2 Safety Instructions for the Alarm Output Module with Voltage >50V
(not available for model T5 with remote probe up to 180 °C (356 °F))
• The alarm output module must be separated from the screw terminals
by the partition plate (see picture).
• The enclosure must be properly closed before power on.
• Power off the device before opening the enclosure.
1.2.3 Safety Instructions for the Integrated Power Supply (Option AM3)
• The back cover and the middle (active) part of the EE23 with
metal enclosure must be grounded during operation.
• The E23 enclosure must be properly closed before power on.
• Power off the device before opening the enclosure.

5
Operating manual EE23 humidity / temperature sensor
1.3 Environmental Aspects
Products from E+E Elektronik® are developed and manufactured observing of all relevant requirements
with respect to environment protection. Please observe local regulations for the device disposal.
For disposal, the individual components of the device must be separated according to local recycling
regulations. The electronics shall be disposed of correctly as electronics waste.
2 Scope of Supply
Included in
all versions
According to ordering
guide
EE23 according to ordering guide x
Operation manual in English x
InspectioncerticateaccordingtoDINEN10204–3.1 x
Allen key 3.0 only for metal enclosure
Mating cable connector for integrated power supply AM3
Mating cable connector RSC 5/7 AM3 / E4
M16 cable gland except AM3, E4

6
Operating manual EE23 humidity / temperature sensor
3 Operating Components
3.1 Electronics Board for Model T1, T2, T4 and T6
Fig. 1 Electronics board model T1, T2, T4 and T6
1. Jumpers:
Selection of the output signal and output range
voltage output current output
2. Display:
Connectors for the optional display
3. Status LEDs
D1 (red) - continuously on during the calibration routine
-oneshortashconrmsresettofactorycalibration
D2(green) -ashesduringnormaloperation
- continuously on indicates sensor damage
4. Push-Buttons
The S1 and S2 push buttons are used for the EE23 adjustment as well as for returning to the factory
calibration (see Calibration / Adjustment).
5. Level / Hysteresis
Potentiometers for setting the threshold / hysteresis (available with alarm module only)

7
Operating manual EE23 humidity / temperature sensor
3.2 Display for Model T1, T2, T4 and T6
The display is plugged into the connectors on the electronics board and it can easily be replaced. For
upgradinganEE23originallywithoutdisplaypleasesee“Replacementparts/accessories”.
1 2 3 4
5
6
Fig. 2 Display description T1, T2, T4 and T6
1. CAL
Indicates that the device in calibration/adjustment mode
2. > <
>: indicates measured value above the alarm threshold (with alarm module only).
visual feedback when depressing the S1 push button (Fig. 1)
<: indicates measured value below the alarm threshold (with alarm module only).
visual feedback when depressing the S2 push button (Fig. 1)
3. SET
Indication for EE23 with optional alarm output
4. Td / Tf
Dew point temperature / frost point temperature
5. °C / °F
Unit for temperature (T) and dew point temperature (Td) and frost point temperature (Tf)
6. %RH
Unit for relative humidity (RH)

8
Operating manual EE23 humidity / temperature sensor
3.3 Electronic Board for Model T5
T5 = remote probe up to 180 °C (356 °F)
1. Display
2. Status LEDs
3. Interface
Fig. 3 Electronics board model T5
1. Display:
Connectors for the optional display
2. Status LEDs:
Green LED
ashing-->Supplyvoltageapplied/Microprocessorisactive
Red LED
constantly lit --> Error category 1 = non-critical error, can be solved by the user
ashing-->Errorcategory2=criticalerror,returnthedeviceforservice
Blue LED
constantly lit --> analogue output is set to voltage.
Orange LED
constantly lit --> analogue output is set to current.
3. Interface:
USB-Interface for service use

9
Operating manual EE23 humidity / temperature sensor
3.4 Display for Model T5
Fig. 4 Display description T5
1. Measurand 2. Units 3. Mesurand selection
SI US
RH Relative humidity % %
Press the ∆or ∇ button
to select the measurand
to be displayed.
T Temperature °C °F
h Enthalpy kJ/kg ftlbf/lb
r Mixture ratio g/kg gr/lb
dv Absolute humidity g/m³ gr/ft
Tw Wet-bulb temperature °C °F
Td Dew-point temperature °C °F
e Water vapour partial pressure mbar psi
Tab. 1 Mesurand selection
Error description Error code
(display)
Error
category Recommended action
Short circuit - on voltage output 11)
ERROR: 01
1
Check wiring of outputsShort circuit - on voltage output 21)
Short circuit - on both voltage outputs*
Current loop open - output 1
ERROR: 02 Check wiring of outputsCurrent loop open - output 2
Current loop open - both outputs
RH sensor dirty ERROR: 03 Clean the sensor2)
Hardware error
ERROR: 05
2Return the faulty unit for
service
ERROR: 06
ERROR: 08
Temperature measurement failure ERROR: 07
Humidity measurement failure ERROR: 09
ERROR: 10
1) not available with 0 - 1 V output
2)see“CleaningInstructions”atwww.epluse.com/ee23
Tab. 2 Description of error messages on the display

10
Operating manual EE23 humidity / temperature sensor
4 Intallation
4.1 Mounting the Enclosure
1. Only for model T2 (duct mounting). Drill the hole for inserting the probe into the duct wall,Fig. 7 on
page 11. The relevant position of top left mounting screw of the back cover with respect to the probe
center:
2. FixthebackcoverofEE23ontothewall/panelusing4screws(diametermax.4.2mm(0.2”);not
included in the scope of supply).
The device shall be mounted with the cable glands pointing downwards or horizontal.
3. Wiretheterminalsinsidethebackcoveraccordingto„Fig.10Connectiondiagram“onPage12.
4. Insert the middle (active) part into the back cover. By this the connection pins of the middle part will
plug into the terminals of the back cover and thus realize the electrical connection.
5. Place the front cover onto the middle part and close tight the enclosure using the four screws included
in the scope of supply.
Drilling for round holes:
Drilling for long holes:
Fig. 5 Mounting of metal enclosure
116 (4.5“)
50.8 (2“)
Fig. 6 Mounting of polycarbonat enclosure
Metal enclosure: x=28.5mm(1.1”) y=37.5mm(1.5”)
Polycarbonate enclosure: x=20.5mm(0.8”) y=25.4mm(1”)
Autres manuels pour EE23 series
2
Table des matières
Autres manuels E+E Elektronik Régulateurs de température
Manuels Régulateurs de température populaires d'autres marques

Swegon
Swegon LUNAd MB Manuel utilisateur

Lucky Reptile
Lucky Reptile Thermo Control II Manuel utilisateur

SENSORMETRIX
SENSORMETRIX Argon 100 Manuel utilisateur

Fuji Electric
Fuji Electric PXE4 Manuel utilisateur

Yuyao gongyi
Yuyao gongyi XMT-808 series Manuel utilisateur

Selec
Selec TC544C Manuel utilisateur