Energomera CE102 Manuel utilisateur

CAHT.411152.165.1 РЭ
Operation manual
Manufacturer:
JSC «Electrotechnical factories «Energomera»
415, Lenin str. Stavropol, Russia, 355029
tel.: +7 (8652) 35-75-27, fax: 56-66-90,
free hotline 8-800-200-75-27
e-mail: concern@energomera.ru
www.energomera.ru
SINGLE-PHASE
MULTI-TARIFF
ACTIVE ENERGY METER
Russian National
Product Classifier 42 2861 5
Case type R5.1
Warranty service:
217, Gagarin str, Nevinnomyssk
Stavropol region, 357106
CE102
FRAME

2

2 3
TABLE OF CONTENTS
1 SAFETY REQUIREMENTS....................................................................................................................................... 4
2 APPLICATION AND OPERATING CONDITIONS ..................................................................................................... 4
2.1 Functionality ..................................................................................................................................................... 5
2.2 Operating conditions ......................................................................................................................................... 8
2.3 Environmental conditions ................................................................................................................................. 8
2.4 Specifications .................................................................................................................................................... 8
2.5 Meter design and operation ............................................................................................................................ 11
3 METER PRE-OPERATION..................................................................................................................................... 13
3.1 Unpacking ...................................................................................................................................................... 13
3.2 Pre-operation .................................................................................................................................................. 13
3.3 Installation procedure ...................................................................................................................................... 13
3.4 Time setting and correction ............................................................................................................................. 14
4 OPERATIONAL PROCEDURE ............................................................................................................................... 14
4.1 Meter reading modes ...................................................................................................................................... 14
4.2 Group 1 – «Consumption on a cumulative total, date/time» ............................................................................ 16
4.3 Group 2
– «Network parameters» .................................................................................................................18
4.4 Group 3 – «Service information» ..................................................................................................................... 20
4.5 Automatic reading mode ................................................................................................................................. 22
4.6 No-voltage reading mode ............................................................................................................................... 22
4.7 Information messages ..................................................................................................................................... 22
4.8 Automated mode ............................................................................................................................................ 22
5 METER VERIFICATION ........................................................................................................................................ 23
6 TECHNICAL MAINTENANCE ............................................................................................................................ 23
7 STORAGE AND TRANSPORTATION ...................................................................................................................... 23
ANNEX А .............................................................................................................................................................. 24
ANNEX B .............................................................................................................................................................. 25

4
This operation manual (hereinafter – РЭ) contains decription of meter functioning principle and information
required to ensure the correct and safety operation of single-phase multi-tariff electricity meter CE102
(hereinafter – meter). Detailed technical parameters, information required to ensure the full use of its technical
capabilities and maintance is provided in the САНТ.411152.165 РП (hereinafter – User Manual), which is located
on the following Internet address www.energomera.ru/ru/products/meters/ce102r5_1.
Information about certificates, manufacturer warranties and factory settings is provided in the Technical
passport ИНЕС.411152.090 ФО (hereinafter – Technical passport).
Only persons who studied this operation manual are allowed to take meter readings.
1 SAFETY REQUIREMENTS
1.1 By the requirements of operating safety, the meter meets the safety requirements in accordance with
GOST 22261-94 and IEC 61010-1:2001.
1.2 By methods of person protection against electric shock, the meter corresponds to the class II
IEC 61010-1:2001.
1.3 The meter installation and operation should be carried on according to the actual rules of electric installation
technical operation.
2 APPLICATION AND OPERATING CONDITIONS
Meter is designed for active energy measurement in single-phase AC circuits, multi-tariff metering organization
and network parameters measurement.
The meter has communication interfaces and may be used both locally and in automated information and
measuring system of commercial energy metering (AMR system) for measured or calculated parameters
transmission to the electric energy control, metering and distribution dispatch center .

4 5
The meter is designed for installation inside buildings or in cabinets, which protects against evironmental
influences.
2.1 Functionality
2.1.1 The meter has an electronic register and performs metering per four +1 (emergency) tariffs. The meter
has an opportunity to programm up to 16 tariff zones within a day (one daily schedule) in steps of one minute,
individually per every day in a week in a seasonal program.
2.1.2 In a case of clock fault, error or absence of tariff scheldule, the meter accumulates readings per
«emergency tariff». «Emergency tariff» is 5 by default.
The meter archives consumed active energy values per (4+1) tariffs and in total:
– on a cumulative total (in total from zeroing);
– for the current and 12 previous months;
– at the end of the month for 12 months;
– for the current and 36 previous days;
– at the end of the day for 44 days.
2.1.3 Time of register readings changing complies with requirements of IEC 62053-21:2003, IEC 62052-
11:2003.
2.1.4 Network parameters measurement
Meter measures mean square values of current and voltage, network frequency and active power.
2.1.5 Impulse output
The meter has an electric test output. Telemetric pulse frequency is proportional to consumed power. Meter
constant is a number of pulses per kW•h, depends on meter modification and is shown on the front panel.
2.1.6 Meter logs
The meter keeps events/states logs, logs of parameters programming. The events are recorded in the logs with
the time / date of their occurrence.

6
2.1.7 Display
The meter has a liquid-crystal display (LCD) for measured energy, measured values, current date and time and
other parameters displaying and «FRAME» control button.
2.1.8 Communication interfaces
The meter has an optical port and EIA-485 interface (EIA-485 interface depends on meter modification).
Work with the meter through the communication interfaces can be performed using the technlogical software
«AdminTools» (hereinafter – TS).
The meter provides the ability to read archival data and measured parameters via the communication interfaces,
as well as to read / write the programmable parameters specified in the User Manual.
For information exchange via optical interface optical probe which meets GOST IEC 61107-2011 requirements
is used.
Access to parameters and data via the communication interfaces is protected by a password.

6 7
2.1.9 Meter modifications
Meters modifications are specified by designation structure, given in the Figure 2.1.
СЕ 102 R5.1 145 JАN
Interfaces and additional options:
N
– Interface external supply
А
– EIA-485
J
– optical port
Base (max.) current:
5
– 5 (60)
Nominal voltage:
4
– 230 V
Accuracy class according to IEC 62053-21:2003:
1
– 1
Case type:
R5.1
– for Din-rail mounting
Figure 2.1 – Designation structure

8
2.2 Operating conditions
The meter is connected to a single-phase AC circuit and is designed for indoor mounting with following
operating conditions:
– ambient temperature from – 45 to + 70°С;
– relative humidity (30-98) %;
– atmospheric pressure 70 to 106,7 kPa (537-800 mm of mercury);
– measuring network frequency (50±2,5) Hz;
– measuring network current and voltage waveform – sinusoidal with non-sinusoidal ratio not more than 8 %.
2.3 Environmental conditions
2.3.1 In terms of resistance to the climatic influence the meter belongs to group 4 according to GOST 22261-94,
with expanded temperature and humidity range, meets T-design of category 3 according to GOST 15150-69.
2.3.2 The meter is protected against dust and water. The protection rate is IР51 according to GOST 14254-96.
2.3.3 The meter is resistant to single impacts and vibration according to GOST 31818.11-2012.
2.4 Specifications
2.4.1 The meters meet the requirements of IEC 62052-11:2003 and IEC 62053-21:2003 in terms of active
energy measuring.
2.4.2 The basic specifications are given in Table 2.1.

8 9
Table 2.1
Name of characteristic Item Note
Active energy accuracy class according
to IEC 62053-21:2003 1
Base (max.) current, А 5(60)
Nominal phase voltage (Unom), V 230
Operation phase voltage from 0,75 to 1,15
Unom
Nominal network frequency, Hz (50 ±2,5)
Measuring network current and voltage
non-sinusoidality ratio, %, not more than 5
Threshold sensitivity, mA 10
Apparent power consumed in current circuit,
not more than V*A 0,1
Apparent (active) power consumed in voltage circuit,
not more than V*A (W) 10,0 (2,0) Under the nominal voltage
Clock rate basic absolute error limit, sec/day ± 0,5
Manual clock rate correction, sec ± 29
Clock rate temperature complementary error limit,
sec/°С•day
±0,15 From minus 10 to 45 °С
±0,2 From minus 45 to 70 °С
Data storage without external supply voltage, years 30

10
Name of characteristic Item Note
Number of tariffs Up to 4 + 1 emergency
Number of seasonal programs Up to 12
Number of exceptional days Up to 32
Number of daily tariff programs Up to 36
Number of tariff areas per daily tariff program Up to 12
Storage depth of month consumption per tariff Up to 13
Storage depth of day consumption per tariff Up to 44
Nominal (permissible) voltage of electrical pulse
outputs, not more than, V 10 (24) DC voltage
Nominal (permissible) current of electrical pulse
outputs, not more than, mA 10 (30) DC voltage
Output pulse width, milliseconds 35
Exchange rate via optical port and via EIA-485 interface,
baud 9600
Meter readings updating time, sec 1
Initial start-up, not more than, sec 5
Table 2.1
Table des matières
Autres manuels Energomera Instrument de mesure
Manuels Instrument de mesure populaires d'autres marques

Endress+Hauser
Endress+Hauser Proline Promag 50 Caractéristiques techniques

Siemens
Siemens SITRANS F Coriolis FCT030 Manuel de la liste des pièces

KLINGER
KLINGER CMF V Series Manuel utilisateur

EXFO
EXFO FTB-2 Manuel d'exploitation et d'entretien

Keysight
Keysight M8290A Manuel utilisateur

ADTEK
ADTEK MW-5 Manuel utilisateur