1.0 General System Information
to prevent surface ponding. Seed or sod excavated areas
to protect against erosion.
1.8 EFFLUENT FILTERS: Efuent lters are recommended
as a means of preventing solids from leaving the tank.
1.9 DISTRIBUTION PIPE LAYOUT: No additional
distribution pipe is needed to connect units to one another.
The Support Distribution Pipe runs through the center of the
units and provides distribution for all congurations. For
bed systems, the distal ends of rows may be connected with
non-perforated pipe.
1.10 GARBAGE DISPOSALS: The use of a garbage
disposal is not recommended as they can cause septic
system problems by generating an increased amount of
suspended solids, grease and nutrients. Design drawings
shall include a note “Garbage disposals shall not be used
with this system”.
However, if such units are proposed to be used, other
measures must be taken to prevent solids from leaving the
tank and entering the drain eld system such as:
· Increasing the septic tank capacity by a minimum
of 30%, or
· Installation of a second septic tank installed in
series, or
· Installation of an appropriate sized septic tank outlet
efuent lter.
NOTE: Eljen recommends the use of septic tank outlet
efuent lters on all systems, especially on those systems
that a garbage disposal is installed, even if the tanks design
capacity has been increased. Filters with higher ltration are
recommended for systems with garbage disposals.
1.11 ADDITIONAL FACTORS EFFECTING RESIDENTIAL
SYSTEM SIZE: Homes with expected higher than normal
water usage should consider increasing the septic tank
volume as well as increasing the size and number of units
in the disposal area. For example: Homes with tubs holding
more than 100 gallons or utilizing other high use xtures and
homes with higher than normal occupancy should consider
septic tank and drain eld modications.
1.12 WATER SOFTENERS OR CONDITIONERS: Discharge
of water softener or conditioner backwash to Eljen Products
is not allowed. Discharge from these devices shall be into a
separate disposal system meeting the requirements of State
and Local Regulations.
1.1 SYSTEM FIELD SIZE AND NUMBER OF UNITS:
System size will vary depending on design ow and soil
analysis. Tables 2 - 4 indicate the minimum number of
Mantis units required for various soil percolation rates and
design ows.
1.2 NON-RESIDENTIAL BUILDINGS & RESIDENTIAL
INSTITUTIONS: Commercial systems require different
sizing and design criteria as compared to residential systems.
Please contact Eljen’s Technical Resource Department
at 1-800-444-1359 for more information on commercial
systems.
1.3 DEPTH TO GROUND WATER OR RESTRICTIVE
LAYER: As required by state regulations; the bottom of
the Mantis M5Series system requires an 18-inch minimum
separation distance from the maximum seasonal high
groundwater table or bedrock. Note: For GMP’s 116, 127, &
135 – 18” separation distance must be measured from the
bottom of 6” sand layer.
1.4 Specied Sand SPECIFICATION FOR TRENCH
SYSTEMS: The rst 6 inches of Specied Sand immediately
under, between Filter Support Modules, between unit rows
and around the perimeter of the Mantis M5Series system
must be an ASTM C33 WASHED CONCRETE SAND WITH
LESS THAN 10% PASSING A #100 SIEVE AND LESS
THAN 5% PASSING A #200 SIEVE.
1.5 VEHICULAR TRAFFIC AND PAVED AREAS OVER
SYSTEM: All vehicular trafc is prohibited over the Mantis
system. This is due to the compaction of material required
to support trafc loading. Compaction greatly diminishes
absorption below the system and reduces the void space
that naturally exists in soils for oxygen transfer and water
migration. For shallow installations, light-weight track-
mounted machines are best for setting the nal grade. It is
also permissible to back-blade the soil to set nal minimum
cover.
1.6 SYSTEM VENTING: Eljen mandates venting when the
system has greater than 18” of cover material as measured
from the top of the unit to nished grade. This will ensure
proper aeration of the units.
1.7 BACKFILL & FINISH GRADING: Complete backll over
the Mantis M5 units followed by topsoil to a depth of 6” –
18” as measured from the top of the units. 1” of the ll is
Specied Sand, immediately on top of the unit. Systems
with total cover that exceeds 18” as measured from the top
of the units to nished grade shall be vented at the distal
(far) end of the system. Backll material shall be well graded
sandy ll; clean, porous, and devoid of large rocks. Divert
surface runoff with diversion ditches or berms. Finish grade
2013 Virginia Mantis M5Design & Installation Manual Page 9 www.eljen.co3