The instrument is shipped with the following default values :
PAGE PARAMETERS VALUES AVAILABLE DEFAULT
PASSWORD REQUEST 0000 ... 9999 0000
RS485
RS485 Address 1 ... 247 27
Rate 2400, 4800, 9600, 19200, 38400 38400
Data Bit 7 o 8 8
Parity N = no parity, E = even, O = odd N
Stop Bit 1 or 2 2
NETWORK
Type (note n.1) 3PH-4W, 2PH-2W, 1PH-2W, 3PH-4W-BAL,
3PH-3W-2CT 3PH-4W
Export NO, YES NO
CT 10000/1 o 5 5/5
VT 400000/300 1/1
AVG-MD TIME (note n.2)
POWERS 1...60 (minutes) 15
CURRENTS 1...60 (minutes) 8
ALARM 1 / A (note n.8)
MODE (note n.3) Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Controlled measure. See table n.1 for register
selection 200
THRE (note n.5) Threshold value 0
ALARM 1 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ALARM 2 / A (note n.8)
MODE (note n.3) Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Controlled measure. See table n.1 for register
selection 200
THRE (note n.5) Threshold value 0
ALARM 2 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ALARM 3 / A (nota n.8)
MODE (note n.3) Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Controlled measure. See table n.1 for register
selection 200
THRE (note n.5) Threshold value 0
ALARM 3 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ALARM 4 / A (note n.8)
MODE (note n.3) Normale, 1-OF-3, 3-OF-3, DERIV, UNBAL NORMAL
TYPE (note n.4) MAX, MIN MIN
MEAS (note n.5) Misura controllata. Vedi tabella n.1 per la
selezione del registro 200
THRE (note n.5) Valore soglia 0
ALARM 4 / B
HYST 1...100 (%) 1
DELAY 1...99 (seconds) 1
AVG (note n.6) 1...99 (seconds) 1
OUT (note n.7) Normal, Hold, Pulse-L, Pulse-S NORMAL
ANALOG OUT 1
MEAS (note n.5) Controlled measure. See table n.1 for register
selection
200
MODE 4-20, 0-20 4-20
LOW (note n.9) 000.00
HIGH (note n.9) 000.00
ANALOG OUT 2
MEAS (note n.5) Controlled measure. See table n.1 for register
selection
200
MODE 4-20, 0-20 4-20
LOW (note n.9) 000.00
HIGH (note n.9) 000.00
NOTE n.1
3PH-4W 3 phases 4 wires, Star
2PH-2W 2 phases 2 wires, biphase
1PH-2W 1 phase 2 wires, monophase
3PH-4W-BAL 3 phases 4 wires, Star Balanced
3PH-3W-2CT 2 phases 3 wires, triangle
NOTE n.2
POWERS Integration time of the average value (AVG) and peak value (MD) for
power (from 1 to 60 minutes)
CURRENTS Integration time of the average value (AVG) and peak value (MD) for
current (from 1 to 60 minutes)
NOTE n.3
NORMALE Classic Alarm with reference to a fi xed threshold or to maximum and
minimum delay and applicable hysteresis. “AVG” parameter is not used.
1-OF-3 Consider also the 2 following registers of the selected one in “MEAS”.
Works on a fi xed max or min threshold with delay and applicable
hysteresis. If one of the three register exceed the threshold the alarm goes
on. “AVG” parameter is not used.
3-OF-3 Consider also the 2 following registers of the selected one in “MEAS”.
Works on a fi xed max or min threshold with delay and applicable hysteresis.
When all the three register exceed the threshold the alarm goes on. “AVG”
parameter is not used.
DERIV “THRE” parameter becomes a % value, “AVG” parameter is used. The
instant value applied to the alarm on “MEAS” is compared with its value
mediated obtained on the basis of the time set on “AVG”. When the
instantaneous value combined alarm differs in more (setting “Max”) or less
(setting “MIN”) from the average value (“ AVG “) of the percentage set on
“THRE” the alarm goes on. With delay and applicable hysteresis.
UNBAL Consider also the 2 following registers of the selected one in “MEAS”.
“THRE” parameter becomes a % value. Alarm goes on when one of the
three register is different from the percentage set on “THRE” comply with
the higher value of the three read register if “MAX” is set on “TYPE”, or
comply with the lower value of the three register if “MIN” is set on “TYPE”
With delay and applicable hysteresis.
NOTE n.4
MAX Alarm setting in excess compared with the established conditions.
With the exception of “UNBAL”.
MIN Alarm setting in decrease compared with the established conditions.
With the exception of “UNBAL”
NOTE n.5
MEAS Indicates which register (and thus measure) the alarm is related.
See table n.1 input register.
THRE Alarm threshold in absolute value, with the exception made for “DERIV”
and “UNBAL” in which the value inserted becomes a percentage.
NOTE n.6
AVG Parameter to be used only in “DERIV” mode. Is the duration of the refe-
rence (in seconds) used to create a reference value for the istantaneous
readings.
NOTE n.7
NORMAL Physical output of the alarm excited during the duration of the alarm. It
restores automatically
HOLD Output remains excited until manual reset made via Modbus
PULSE-L Output generate a 500ms impulse when the alarm goes on.
PULSE-S Output generate a 100ms impulse when the alarm goes on.
NOTE n.8
ALLARME 1 Only MODBUS alarm
ALLARME 2 Only MODBUS alarm
ALLARME 3 Only MODBUS alarm
ALLARME 4 Only MODBUS alarm
NOTE n.9
LOW Associated scale value starts at 0 and 4 mA
HIGH Full scale value associated with 20 mA
COMMUNICATION PROTOCOL
It is possible to obtain the communication protocol of the instrument by sending a request