1. WELCOME
Installation Instructions
CONTENTS
CODE: 01693, 01694, 01695
CODE: 01697
Thank you for choosing this quality Ektor product.
This manual is intended to help you install this
product in a way that ensures the safety of yourself
and others. Whilst this Ektor product is designed
to be installed easily, we highly recommend you
take the time to read this manual thoroughly before
commencing installation. When installed correctly
and serviced regularly, this product will provide
hassle free operation for many years.
01693 EV-LEDFIRE
01694 EV-LEDFIRE-PRO
01697 EV-LEDFIRE-PRO-B
01695 EV-LEDFIRE-ULT
1
1. Welcome
2. Overview
3. Safety warnings
4. Installation
5. Maintaining your Ledfire luminaire
6. Replacing the LED dish
7. Replacing the battery
8. Battery life
9. Power and battery charge
10. Wireless daughterboard
11. Self-test wiring / central battery system
12. DALI wiring / central battery system
13. Using the inverter with a switch
14. Using the inverter with a sensor
15. Accessories list
16. Lead and cable accessories
17. Changing/adding the cable set
18. Non maintained / maintained jumper
19. Discharge rating selection
20. Self-test indicator LEDs
21. Self-test / commissioning interval programming
22. Product specifications
23. Australian emergency classification
24. Spacing table
25. Construction sites
26. Testing precautions
27. Problem solving procedure
28. Warranty information
29. Compliance standards
30. Technical support and troubleshooting
MANUFACTURED
TO ISO9001

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
2
2. OVERVIEW
Ektor Generation III platform introduces you to a new era of emergency lighting control. With years in the
making, the third generation platform builds on the Ektor product ranges’ increasing quality, reliability and
performance. In choosing this Ektor product you can be comfortable that you have the best.
Out of the box this product can be wired in any of these configurations:
• Self-testing unit
• Standalone unit
• Standalone unit controlled with a switch or sensor
• DALI controlled remote testing unit
And can be used with a central battery system (monitored and non-monitored)
An optional wireless module can be added to allow you to connect to standard Wi-Fi networks for remote
testing and reporting.
Our Ektor Generation III platform also brings class leading technology which increases performance and
reliability including:
• Smart battery charging technology which reduces power consumption up to 90% while
increasing the service life of the battery
• Smart battery conditioning to ensure the best performance from the battery
• 450V Electrolytic capacitors which increase the products reliability
• Highly efficient design to reduce fatigue on the product
For buildings requiring longer durations such as 3, 4 and 8 hours the installer can change the jumpers found
on the unit for automatic scaling of the output. Moreover should you require non-maintained or maintained
output, the installer can select this on installation.
3. SAFETY WARNINGS
1. THIS PRODUCT MUST ONLY BE INSTALLED BY A LICENSED ELECTRICIAN.
2. BEFORE COMMENCING INSTALLATION TURN OFF AND ISOLATE THE ELECTRICAL SUPPLY.
3. DO NOT ENERGISE WITH PRODUCT OPEN OR DISASSEMBLED.
4. SUPPLY VOLTAGES WITHIN PRODUCT. ISOLATE SUPPLY VOLTAGES BEFORE OPENING OR SERVICING.
5. THE ONLY USER SERVICEABLE PART IS THE BATTERY PACK.
6. DO NOT ATTEMPT TO SERVICE OTHER PARTS OF THE FITTING AS THIS WILL VOID THE WARRANTY.
7. AS THE INSTALLER, IT IS YOUR RESPONSIBILITY TO ENSURE YOU COMPLY TO ALL RELEVANT BUILDING AND SAFETY
CODES FOR EXAMPLE THE BCA, AS3000. REFER TO APPLICATION STANDARDS FOR THE RELEVANT RULES.
8. WHEN THE INSTALLATION IS COMPLETE, LEAVE THIS MANUAL WITH THE BUILDING’S OWNER(S) FOR FUTURE REFERENCE.

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
4. INSTALLATION
Ektor Ledfire recessed emergency luminaires can be installed in either accessible or inaccessible ceiling cavities.
To install the Ledfire please follow the steps listed below:
1. Remove the product from the box and inspect it for any damage. If you believe the product to be
damaged or otherwise unsound, DO NOT install the product. Please pack it back into its box and return
it to the place of purchase for replacement. If the product is satisfactory, proceed with the installation.
2. Choose the dish diameter that is suitable for your application, either 140mm or 84mm. If you are
installing the 84mm dish you will have to remove the outer ring first, this is done by twisting it out of its
locking position and sliding it down the ring.
3. Drill the hole in the ceiling to suit the dish size you have chosen; 70mm cut out for the 84mm dish or
120mm for the 140mm dish. Note that this product can be installed into an existing cut out in the ceiling
ranging from 70mm to 120mm.
NOTE: The dish is to be installed
into the ceiling from below.
Pull back the two spring clips
so that they can fit through the
ceiling cut out.
Release the spring clips,
ensuring that the dish is secure
and flush up against the ceiling
NOTE: The Ledfire dish is
pre-wired. Only connect
the Ledfire dish and battery
connections into the Inverter
until a “click” is heard.
Inverter
Inverter
Ledfire dish 140mm
Ledfire dish 84mm
Spring clips
OR
Ledfire dish
Battery
Battery
Figure 1: Ledfire assembly and ceiling installation
3
70 mm min. for 84 mm dish
120 mm max. with ring
2

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
4
7. REPLACING THE BATTERY
6. REPLACING THE LED DISH
5.MAINTAINING YOUR LEDFIRE LUMINAIRE
1. Use only the LiFePO4 battery recommended on the label found on the inverter/battery charger pack.
No other battery will work in this fitting, other than the type listed.
2. Disconnect the battery from the product and if necessary, cut cable ties to release the battery from its
mounting position.
3. Replace the battery as was previously installed and then reinstall inverter/battery pack or install as per all
relevant standard requirements.
4. Replace the Ledfire dish back into its previously mounted ceiling position and ensure the green charge
light is illuminated. Allow a few minutes for the battery to charge.
5. Allow a minimum 24 hours charging time before carrying out any discharge tests as per the
requirements in AS/NZS 2293, BCA or other relevant standards.
The LED lamp cannot be replaced if the LED is found to be faulty. The whole LED dish needs to be replaced.
When replacing the Ledfire LED dish, please follow the installation instructions shown in section 4 (page 3).
The Ektor Ledfire Emergency Luminaire is connected to an unswitched active during normal operating
conditions. When disconnected from the mains supply, the Ledfire is powered by a LiFePO4 battery operated
inverter. Due to this, care should be taken when replacing either the battery or dish.
WARNING
4. To ensure correct battery performance, it is advised to mount the battery away from any direct heat
sources such as air conditioning, heat vents, or ducts. To secure the battery, cable-tie the battery to the
inverter in the ceiling cavity.
5. Ensure the inverter/battery charging pack and batteries are mounted in accordance with the standards on
the site of installation.
6. Connect the battery pack and dish looms into the relevant sized plug adaptors on the inverter/charging
pack unit. These plugs are keyed and can only be installed one way. Ensure the plugs lock-in and are secured.
7. Connect the power to a permanent active power supply and ensure that the units are wired as per the
relevant standard requirements.
To check correct operation of the unit allow battery to charge for a few minutes, ensuring green charging LED
on the dish is constantly illuminated. When the test switch is pressed the LED light source illuminates.

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
5
Charge
current
Max charge current Max charge voltage Savings
Cell voltage
8. BATTERY LIFE
9. POWER AND BATTERY CHARGE
To maintain the economic life of this product it is required that the battery be discharged and recharged
at least once every 6 months. The battery life can be reduced if the battery is not discharged as per the
requirements of AS/NZS 2293 or an equivalent standard. Increasing the number of duration tests above that
as defined in AS/NZS 2293 or an equivalent standard can have a positive effect on the battery performance as
long as 12 discharge cycles per year is not exceeded.
The Ektor Generation III platform uses smart battery charging technology which reduces power consumption
and increases battery life.
During the first stage of operation the battery charger charges the battery until full. Afterwards, the unit goes
into a stage which charges the battery periodically. This reduces the battery temperature and reduces the
loss of electrolytes which ultimately increases the service life of the battery. As a result of stopping the charging
process, the power consumption is reduced and only consumes 1/11th of the typical power.
The smart battery charger also offsets the charger time by a random interval to un-synchronise all the
emergency lighting in the building. This reduces the average loading on a building’s infrastructure and reduces
any impacts of surges created by turning on large numbers of products simultaneously.
Figure 2: Example of included battery
Figure 3: Smart charge rate
1 x LiFePO4 stick battery 01302 / 01303
KIT INCLUDES:
1

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
6
10. WIRELESS DAUGHTERBOARD
The Ledfire inverter supports an optional wireless daughterboard. The driver must be disconnected from
mains and battery must be removed, before installing or changing any expansion module. More information
and a list of other accessories can be found in the Wireless design and installation guide. The assembly for
this part onto the inverter is shown below:
When installing the inverter with a wireless daughterboard, careful attention needs to be taken to the
positioning of the antenna. There is also the option of adding an antenna. The antenna can be mounted in a
vertical position, depending on the installation. Care should be taken to mount the antenna away from metal
objects or behind large concrete walls. More information and a list of other accessories can be found in the
wireless design and installation guide.
Figure 4: Daughterboard assembly diagram
Figure 5: Mounting position of the inverter antenna
NOTE: If possible antenna is to be
orientated vertically when mounting.
Antenna position
when suspended
OR
Antenna when the
inverter is mounted flat
Direction to router Direction to router
2
1
Wireless daughterboard (06118)(optional)
Ledfire/Pro/Ultimate inverter (01201/01202/01203)
1
2

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
11. SELF-TEST WIRING/ CENTRAL BATTERY SYSTEM
The inverter can be used in an automatic self-test mode which reduces the need for a test switch timer.
The self-test ability automatically disables if the unit is wired to DALI or the wireless daughterboard is attached.
Additionally the third generation platform can be wired to a central battery system. With this wiring the system
feedback cannot report the light status (refer to the Configurations: Status LEDs and Device Modes document.).
Figure 6: Inverter standard wiring diagram
7
12. DALI WIRING/ CENTRAL BATTERY SYSTEM
The Ledfire inverter supports DALI out of the box, a hardwiring diagram is shown below, optionally an
installer can order a soft wiring cable set found in section 16. The inverter also supports central battery
systems and can be monitored through DALI. When used as a central battery system the devices can be
tested with DALI.
Figure 7: Inverter DALI wiring diagram
13. USING THE INVERTER WITH A SWITCH
A mains rated switch can be wired with this product to turn ON/OFF the non-emergency light in normal use.
This does not affect operation in emergency mode.
Figure 8: Inverter switch wiring diagram
Mains rated switch
Installer wired Prewired

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
14. USING THE INVERTER WITH A SENSOR
A mains rated sensor can be wired with this product to turn ON/OFF the light in normal use. This does not
affect operation in emergency mode.
Figure 9: Inverter sensor wiring diagram
8
15. ACCESSORIES LIST
Below are the listings of the accessories and replacements compatible with the Ledfire.
PART CODEEVOLT CODE
COMPLETE UNITS
Ledfire (White)
Ledfire Pro (White)
Ledfire Pro (Black)
Ledfire Ultimate (White)
01693
01694
01697
01695
PARTS/REPLACEMENTS
Ledfire inverter
Ledfire Pro inverter
Ledfire Ultimate inverter
Ledfire Dish (White)
Ledfire Pro Dish (White)
Ledfire Pro Dish (Black)
Ledfire Ultimate Dish (White)
Battery, Stick 1500mAh 6.4V, 2 Cell LifePO4 to suit Ledfire
Battery 3000mAH 2 Cell LiFePO4 to suit Ledfire Pro & Ult
Ledfire inverter antenna
Ledfire strain relief cover
Wireless daughterboard
Antenna extension
Easy commissioning module - DALI
Easy commissioning module - Ektor
EV-LEDFIRE
EV-LEDFIRE-PRO
EV-LEDFIRE-PRO-B
EV-LEDFIRE-ULT
EV-LEDFIRE-INV
EV-LEDFIRE-PRO-INV
EV-LEDFIRE-ULT-INV
EV-LEDFIRE-RD
EV-LEDFIRE-PRO-RD
EV-LEDFIRE-PRO-B-RD
EV-LEDFIRE-ULT-RD
EV-1500mAh-6.4V-LiFePO4
EV-3000mAh-6.4V-LiFePO4
EV-LEDFIRE-ANT
EV-LEDFIRE-EXTENSION-LOOM
EV-WIFI-DAUG
EV-ANTENNA-EXTE
EV-ECM-DALI
EV-ECM-EKTOR
01201
01202
01203
02101
02102
02104
02103
01302
01303
02111
02112
06118
06125
05304
05305
Mains rated sensor

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
17. CHANGING/ADDING THE CABLE SET
Figure 10: Lead and cable accessories
Figure 11: Changing the cable set
Clip into place to connect
the inverter and wiring.
Slide the strain relief down
into it’s slot as shown on
the right.
Unscrew the safety screw.
Carefully disassemble
cover with flat blade
screwdriver.
16. LEAD AND CABLE ACCESSORIES
The following cord-sets can be ordered and attached to the inverter depending on the site requirements.
CORD-SET
STANDARD
OPERATION
PRODUCT CODE DESCRIPTION
DALI OPERATION
LENGTH
A
B
C
D
E
F
2.4M
2.4M
2.4M
2.4M
2.4M
1.4M
00709
00707
00705
00706
00710
00708
Wire By Click 5-Pin Lead L1025/5
Wieland Plug GST18I5S B1 ZR1 S PB02
CMS 5 Pin Plug Set
WAGO Plug 5-P Blue WAGO 51110475
CMS 6 Pin Plug Set
Flex and Plug (Standard)
9
M3
1
2
A B C D E F
3
NOTE: Connector is included with the above cord-set accessories.
NOTE: If there is already
a cable set attached, this
must first be removed
Phillips
screws

LEDFIRE / PRO / ULTIMATE EMERGENCY INSTALLATION INSTRUCTIONS
DRAF
T
DRAF
T
10
18. NON MAINTAINED / MAINTAINED JUMPER
19. DISCHARGE RATING SELECTION
A user can select the mode of operation for the Ledfire inverter. If the inverter is using a
switch input this is disregarded and not used.
The inverter supports a number of discharge ratings which can be selected by the user. The output from
the LED scales based on the discharge rating (see section 23 for output classification information).
Figure 12: Maintained/non-maintained jumper
Jumper
Figure 13: Discharge rating selection
Remove expansion cover
C
B
A
HOURS
INDICATOR
A
STATUS
B C
DESCRIPTION
1 Hour
2 Hours (default)
3 Hours
4 Hours
8 Hours
Central battery operation
N/A
N/A
NON MAINTAINED
MAINTAINED MODE
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
LED is only ON in
emergency
LED is ON in normal and
emergency operation
Ce manuel convient aux modèles suivants
7
Table des matières
Manuels Luminaire populaires d'autres marques

Emos
Emos CLASSIC ZY1431T Manuel utilisateur

Westinghouse
Westinghouse Outdoor Lighting Fixture Manuel utilisateur

Hedler
Hedler C 12 silent Manuel utilisateur

Blizzard Lighting
Blizzard Lighting Puck: CSI Manuel utilisateur

Energetic Lighting
Energetic Lighting ELYSL-5004 Series Manuel utilisateur

Lightmaxx
Lightmaxx Shaft 5R Manuel utilisateur

Cooper Lighting
Cooper Lighting Halo L3232E Manuel utilisateur

Stageline
Stageline ODW-2410RGBW Manuel utilisateur

Light Sky
Light Sky Tornado Series Manuel utilisateur

Lightolier
Lightolier Paralyte 2424 PLA2G9LS26U Manuel utilisateur

Lightolier
Lightolier Lytespan 83ED17S Manuel utilisateur

Lightolier
Lightolier Calculite CS8226 Manuel utilisateur