MAINTENANCE MANUAL
WARRANTY CARD
AIR HANDLING UNIT
luna 350
rew. 22.02.2018
EN
test

1. GENERAL INFORMATION.................................................................
1.1. Technical specification................................................................
2. ASSEMBLY..................................................................................
2.1. Required exploitation conditions.....................................................
2.2. Pre-assembly requirements............................................................
2.3. Mounting the unit.......................................................................
2.4. Assmbly of siphon-out condensate...................................................
2.5. Conneting to power gird...............................................................
2.6. Manner of setting anti-freeze protection..........................................
2.7. Electrical connection scheme........................................................
3. STARTING THE UNIT.....................................................................
3.1. General remarks........................................................................
3.2. Starting the unit.........................................................................
3.3. Use and maintenance...................................................................
3.4. Exploitation recommendation.........................................................
4. ....................................................
5. WARRANTY.................................................................................
Controller maintenance manual
3
3
4
4
5
5
6
7
7
8
9
9
10
10
11
12
13
2
www.dospel.com
EN
CONTENTS
luna 350
test

3
Technical specification
Dimension: 1171 x 685 x 450 mm
Connection diameter 198 mm
Air flow (100 Pa): 320 m3/h
Disposal compression: 450 Pa
Max. power consumption max. 234 [W]
Heat recovery efficiency up to 95%
Power supply voltage 230 [VAC] / 50 [Hz]
Motor supply voltage 230 [VAC] / 50 [Hz]
Motor rotational speed (3 gears) 2712 / 1935 / 1307
obr/min
Type of motor's bearing Roller
Acoustic pressure < 52 dB
Insulation class I
International Protection Rating IP X4
Weight 25,60 kg
luna 350
3
snapchat: dospel.com
twitter.com/dospel_com
facebook.com/Dospel.Wentylacja
1.MAINTENANCE MANUAL
Luna 350 air handling unit is designed to assure air exchange in public utility and apartment
buildings. The unit's puprose it to supply fresh air from the outside and dispose used air
from the rooms with simultaneous recovery of thermal energy. As standard, the unit is equipped
with with bypasswhich can be switched on withous opening the casing.
1.1. Purpose
Chart 1. Technical specification
EN
test

198
685
1014
1171
200
551
450
rev. 14.03.2016
4
luna 350
www.dospel.com
WARNING!
Luna 350 should be lifted by holding the casing. It is forbidden to lift by holding
the connectors. It may result in leakage and damage to the device.
2. ASSEMBLY
2.1. Required exploitation conditions
The unit and ducts should be assembled in rooms with temperature above 5°C and heat-separated
form surroundings.
Not following above conditions will cause liquefaction of condensate and cumulate it inside and outside
of the unit which may cause dampness in the room or damage to the unit.
WARNING!
1. Ventilation installation and other belonging elements must be in accordance with Polish Norms
referring to ventilation in residential and public utility buildings.
2. The unit is not destined for drying the unseasoned houses.
3. In case of damage to elements arising from not following the above instructions,
they will be not repaired under warranty.
4. Due to design reasons there is a possibility of mixing the air inside the unit with amount
not exceeding 2%.
EN
Fig.1. Nominal dimensions of Luna 350
test

luna 350
5
snapchat: dospel.com
twitter.com/dospel_com
facebook.com/Dospel.Wentylacja
2.2. Pre-assembly requirements
While planning the assembly of the unit consider:
nensuring the expliotation conditions of the unit
npossibility of bringing about ventilation pipes to the device
npossibility of siphonning of steam condensate
npossility of bringing about electric energy
neasy access to maintenance and repairs
Prior to connecting the unit check elements condition, including casing and wiring.
In order to avoid any damage, the unit should be kept in safe place in original packaging.
EN
Fig.2. Flow efficiency characteristics
First gear
0 50
50
100
100
150
150
250
250
200
200
300
300
350
350
400
3
U[m /h]
400
450
P[Pa] Luna 350 with 3-gear controller
Second gear Third gear
2.3. Mounting the unit
The unit is destined for assembly under dry roofed rooms with basements (attics, utility room).
The unit should be assembled in a way to allow free drain condensate from the tub.
Unit should be connected to ventilation ducts in accordance with designation on connectors
(air inlet, launcher, intake, exhaust). In case of removing the exchanger with tub and replacing
it, pay attention to tub position - necking which remove condensate from the exchanger must
be on the side of connectrs air inlet-launcher.
test

6
luna 350
www.dospel.com
2.4.Assembly of condensation dreinage system
Steam condensation can be observed during unit's work. It is completely normal and it does
not mean abnormality in working. In order to siphon out condensate the unit is equipped with
stub pipe placed on the right side. It is essental to properly connect the pipe siphoning out
the condensate.
Exemplary way of conneting the pipe is shown below. The pipe should have adequate diameter
to the stub-pipe (16 mm). It shoud be bent into letter "U" and suffused with water until stabilizing
its level. Shipon should be palced around 120 mm from the unit and radius should not be less than
R=30 mm. Given measures should be taken as minimal.
Unit is sold with siphon and pipe,
EN
The manufacturer suggests mounting acoustic silencers in main ventilation ducts
in order to minimize noise.
Fig.3. Description of connectors
Air inlet
Launcher
Intake
Exhaust
WARINIG!
The manufacturer does not provide assembly elements. Required elemsts shall
be bought be buyer separately.
siphon
Fig 4. Place of pipe
test

luna 350
7
snapchat: dospel.com
twitter.com/dospel_com
facebook.com/Dospel.Wentylacja
EN
2.5. Conneting to power grid
Unit should be connected directly to one phase outlet 230V/50Hz in the most accessible place.
All electrical matter should be perfomed by authorized person.
WARNING!
During service or maintenance work unit should be disconnected from power grid by pulling
out power cord.
In case of damaging connection cord, its replacement can only be performed by authorized
service or installer with appropriate permissions.
2.6.Manner of setting anti-freeze protection
Luna 350 ventilation unit has been equipped with anti-freeze protection heat exchange
in the form of a thermostat switching off intake fan. This protection is to protect the exchanger
from freezing during the occurrence of negative temperatures in winter time.
In case of occurrence, exchanger on the exhaust side of the temperature lower than the set
temperature on the thermostat switches off the intake fan. This results in increased exhaust
temperature (after the exchanger) until the intake fan is switched on again.
The suggested temperature for setting the protection thermostat is + 2°C (in Poland).
Fig 5. Manner of conneting and setting anti-freeze protection
Thermostat
temperature
adjuster
test

rev. 14.03.2016
8
luna 350
www.dospel.com
EN
Fig 6. Electrical connection scheme
Main switch Anti-freeze thermostat Power connector Intake fan
~230, 170W
Exhaust fan
~230, 170W
Intake fan
~230, 170W
Exhaust fan
~230, 170W
Thermostat capillary
AIR HANDLING UNIT LUNA 350
Rotation controller
Page:
Electrical connection scheme LUNA 350
WARNING!!! Power supply voltage 230VAC, 50hz
(The current protection should be selected based on the device's power)
Designed by:
Checked by:
connection
box
test

rev. 14.03.2016
luna 350
9
www.dospel.com
3.STARTING THE UNIT
3.1.General remarks
1. Prior to starting the unit read the manual.
2. Check if there is no objects present in the ducts which may damage the unit or endanger
health.
3. It is recommended to test the working mode of the unit prior to connecting it to ventilation.
WARNING!
When performing and testing the installation, appropriate safety measures must
be taken in order to avoid the wrong air flow direction, i.e from an open flue pipe
or other devices with open fire to the room.
EN
2.7. Electrical connection scheme
Fig 7.Manner of connecting 3 gear controller
Power cord
2
3x1,5mm
Control - power supplying cord
2
5x1mm
Switchboard
supplying the building
Main power supply
230V AC 50Hz
connection box
3 gear controller
test

10
luna 350
www.dospel.com
+48 (34) 370 30 00
3.2. Starting the unit
6. Turn the thermostat knob to the desired anti-freeze protection temperature (suggested
temperature approx. + 2°C).
Once all above is performed, the unit can be used. Only periodic maintenance is required.
1. Read the manual.
2. See if there is no damage.
3. Place unit in wanted place.
4. Connect 3 gear controller.
5. Connect connection cord to connection box (in accordance with schemes) then
to 3 gear controller.
7. With 3x1,5 mm2 (secured by fuse) 230v/50Hz connect to 3 gear controller.
8. Turn on the unit switching to wanted gear (LO, MED, HI).
9. Turn off the unit (OFF).
Fig 8. Locations of elements inside the unit;
manner of filter replacement
Fig 9. Summer bypass
3.3 Usage and maintenance
WARNING!
Unit should not work without filters. It is only recommended for testing, but no longer than
10 minutes.
When proprely installed, unit does not require special maintanance work during use. It is
recommended to control filters at least once per quarter and change filters. It is essential for
keeping unit's high efficiency. When high intake air purity of is required, it is recommended to use
external duct filter. In order to replace filters, unscrew the safety screws, disassemble one part of
the control panel housing (revision), gently remove used filters, put on new ones and re-assemble
the housing. Visual indication informs about the need to replace filter. When replaced, reset the
timer.
EN Exchanger Filters
Casing - revison