DIGITIZE System 3505 Prism LX Manuel utilisateur

System 3505 Prism LX™
Custom Interface #0080
Northeastern
OnyxWorks to PrismLX
Operational Notes
Digitize, Inc.
158 Edison Road
Lake Hopatcong, New Jersey 07849
Tel: (973) 663-1011 Part Number: 700300-0001
E-mail:info@digitize-inc.com Revision: B
Website: http://www.digitize-inc.com Issue Date: 10/2021

Digitize, Inc.
158 Edison Road
Lake Hopatcong, NJ 07849-2217
The Digitize logo (stylized) is a registered trademark of Digitize, Inc.
MeshSentryTM and VersAlarmTM is a trademark of Digitize, Inc.
FireTideTM is a trademark of FireTide, Inc.
OnyxWorks® is a registered trademark of Honeywell International Inc.

PROPRIETARY NOTICE
AND
DISCLAIMER
DIGITIZE, INC.
158 EDISON ROAD
LAKE HOPATCONG, NJ 07849-2217
PH: (973) 663-1011
E-Mail: info@digitize-inc.com
Website: http://www.digitize-inc.com
This manual has been prepared by DIGITIZE, INC. for use by its licensees, distributors
and customers. The information contained herein is the property of DIGITIZE, INC. and
may not be copied, disclosed or reproduced, in whole or in part, without the prior written
approval of DIGITIZE, INC. Any unauthorized disclosure to, or use of the enclosed
information by, unauthorized third persons shall void any and all representations,
warranties and obligations on the part of DIGITIZE, INC.
DIGITIZE, INC. reserves the right to make changes to the specifications and material
contained herein without prior notice. The information and/or examples (including, but
not limited to circuitry, wiring diagrams, programming, the operation or use shown)
described in this manual are intended solely to illustrate the operating principles of the
particular product. They are not a warranty, representation or guarantee that a particular
example or use shown will perform in a particular situation. They are given for illustration
purposes only. DIGITIZE, INC. shall not be responsible, nor does it represent, that any
example of illustration will perform in a particular environment or practice unless it
specifically makes a representation to that effect.
The material set forth herein is for informational purposes only, and DIGITIZE, INC.
assumes no patent liability with respect to any information or illustrations contained
herein.

FCC NOTICE
In compliance with Paragraph 15.105 of the FCC Rules and Regulations, the following
notice is provided.
NOTE: This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy, and, if not installed and used in accordance with the
instruction manual, may cause interference to radio communications. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will
be required to correct the interference at his own expense.
P/N 770120 Rev C

Table of Contents
1 Introduction...............................................................................................1-1
1.1 Purpose.............................................................................................................................................. 1-1
1.2 Scope................................................................................................................................................. 1-1
1.3 Serial Communications..................................................................................................................... 1-1
1.4 OnyxWorks Interface........................................................................................................................ 1-2
1.5 Description Field............................................................................................................................... 1-3
1.6 Status Field........................................................................................................................................ 1-3
1.7 Restoral signal................................................................................................................................... 1-3
2 Event Processing.......................................................................................2-1
2.1 Fire Alarm Activation....................................................................................................................... 2-1
2.2 Fire Alarm Restore............................................................................................................................ 2-3
2.3 PrismLX Sounder.............................................................................................................................. 2-3
2.4 Multiple Alarm or Restore Events .................................................................................................... 2-4
3 Remote Annunciator.................................................................................3-1
List of Figures
Figure 1-1, Fire Alarm Activation Signal....................................................................................................1-2
Figure 1-2, Alarm Restoral Signal ..............................................................................................................1-2
Figure 2-1, Fire Alarm as Initiated by OnyxWorks..................................................................................... 2-1
Figure 2-2, FA auto Xmit to BFD after 60..................................................................................................2-2
Figure 2-3, Xmiting Box 328 to BFD ..........................................................................................................2-2
Figure 2-4, FA Restore occurred prior to Teleg Box Transmission............................................................ 2-3
Figure 2-5, Sample Thermal Printout for Multiple Events.......................................................................... 2-4
Figure 3-1, Location of Pop Up box when Alarm event is reported by the OnyxWorks to the PrismLX....3-1
Figure 3-2, BFD Telegraph Box Transmission is active.............................................................................3-2
Figure 3-3, BFD has been notified and Telegraph Box transmission ended...............................................3-2
Figure 3-4, Operator Aborted BFD Dispatch.............................................................................................3-3


700300-0001 Rev. B 10/21 1-1
1 Introduction
1.1 Purpose
The purpose of this manual is to inform the user how the OnyxWorks to Digitize PrismLX
operates.
The goal of the PrismLX Custom 0080 interface is to monitor the Unsupervised Printer
output from the OnyxWorks CAD system and pick out the Fire Alarms and Fire Restore
signals.
When a Fire Alarm output from the OnyxWorks is detected, the PrismLX will annunciate
the event and set up to code the appropriate Telegraphic code to the Boston Fire
Dispatch (BFD) via an existing 100Ma Telegraph loop that is routed near the PrismLX at
Northeastern University. The PrismLX will wait 60 seconds prior to automatically coding
out the Telegraphic code to BFD. The operator has the ability to prevent the activation
of the BFD code or initiate it prior to the 60 second finishing its countdown. Should the
OnyxWorks process a restore prior to the end of the 60 second countdown, the PrismLX
will abort the pending transmission. However, should the restore be processed after the
Telegraph code is initiated, only the Dispatcher can abort the coded output.
Note that the accounts and location names used in the examples are for illustration only
and do not match the user’s data.
1.2 Scope
While in most applications using the PrismLX, the PrismLX is used as the Proprietary
Alarm Monitoring System used by the dispatcher to monitor and respond to Alarm,
Trouble and Supervisory events. However, in the case of Northeastern, the function of
the PrismLX is to sort out and notify the BFD, unless canceled, of a fire event. The
PrismLX will stack up multiple Fire and or restore events and will only process the
backed-up events after the current event is either canceled or we reached the end of the
coded output. Thus, for this reason, the PrismLX, with its custom program #0080, would
not comply with the requirement to process an event within the specified NFPA time
requirement
1.3 Serial Communications
For Custom 0080 to work properly, the PrismLX must have OPTION 2 SET for CAPS II
and of course the option should be set for 0080. On power up, the PrismLX will set the
BAUD rate to 9600 8N1 to allow interfacing to the OnyxWorks.

Introduction Digitize Inc
1-2 700300-0001 Rev. B 10/21
1.4 OnyxWorks Interface
The serial data from the OnyxWorks contains a variety of signals. The PrismLX will only
act on two signals. The two signals are noted below:
This signal is for the activation of a Fire Alarm.
This signal is for the Restoral of a Fire Alarm.
The Prism LX only acts on the Description: field and the Status: field, however the
structure of the OnyxWorks string must be as noted in its entirety.
****************************** <CR><LF>
Actual Time: 3/19/2020 11:01:49 AM <CR><LF>
Network: Columbus Place <CR><LF>
Node: Gains. Garage <CR><LF>
Point: 0328 FA GAINSBOR0UG <CR><LF>
Point Type: Track Supervisory <CR><LF>
Description: 0328 FA GAINSBOR0UG (total of 35 Characters) 12345<CR><LF>
Status: Supervisory Alarm <CR><LF>
Action: <CR><LF><CR><LF>
******************************<CR><LF>
Actual Time: 3/19/2020 11:04:24 AM<CR><LF>
Network: Columbus Place<CR><LF>
Node: Gains. Garage<CR><LF>
Point: 0328 FA GAINSBOR0UG<CR><LF>
Point Type: Track Supervisory<CR><LF>
Description: 0328 FA GAINSBOR0UG (total of 35 Characters)12345<CR><LF>
Status: Supervisory Normal<CR><LF>
Action: <CR><LF><CR><LF>
Figure 1-1, Fire Alarm Activation Signal
Figure 1-2, Alarm Restoral Signal

Introduction Digitize Inc
700300-0001 Rev. B 10/21 1-3
1.5 Description Field
The Description field must contain a four-digit number that represents the Telegraph Box
number to be queued up to be transmitted or aborted. If the box number only has one,
two or three digits, they must be preceded by zeroes. The box number must be followed
by the Letters FA. The FA is can be followed by up to 35 Alpha numeric characters
representing the building or address of the Fire Alarm.
There must be a space character separating the various items used to produce the proper
event. A letter ‘b’ will be used to illustrate the required space as follows:
Description:b328bFAbGAINSBOR0UG…
The total number of characters for the “Description:”location of the Fire Alarm and
Restore event can be up to 35 characters Including the “GAINSBOROUG” as noted.
GAINSBOR0UG (total of 35 Characters) 12345<CR><LF>
1.6 Status Field
The Status field must contain either the words ‘Supervisory Alarm’ or ‘Supervisory
Normal’in combination with the Description field information to produce a Fire Alarm
or Alarm Restoral.
1.7 Restoral signal
The OnyxWorks Fire Alarm signal must eventually be followed by a Restoral signal in
order to be removed from the PrismLX (and Remote Annunciator) display.

Autres manuels pour System 3505 Prism LX
1
Table des matières
Autres manuels DIGITIZE Matériel réseau
Manuels Matériel réseau populaires d'autres marques

Matrix Switch Corporation
Matrix Switch Corporation MSC-HD161DEL Manuel utilisateur

B&B Electronics
B&B Electronics ZXT9-IO-222R2 Manuel utilisateur

Yudor
Yudor YDS-16 Manuel utilisateur

D-Link
D-Link ShareCenter DNS-320L Manuel utilisateur

Samsung
Samsung ES1642dc Instructions d'utilisation

Honeywell Home
Honeywell Home LTEM-PV Instructions de montage