The unit conforms to the EU directives
-2006/95/EC (low voltage)
-2004/108/EC (electro-magnetic compatibility)
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
The CE mark indicates that this product complies with the European requirements for safety,
health environmental and customer protection.
Alternator voltage: 170-300 V-AC (Phase-Neutral)
Mains voltage: 170-300 V-AC configurable (Phase-Neutral)
Mains frequency: 30 –70 Hz configurable
Generator contactor timer: 1 - 40 sec. configurable
Mains contactor timer: 0 - 999 sec configurable
Mains waiting timer: 0 - 999 sec configurable
Mains fail timer: 0 - 999 sec configurable
Cooldown timer: 0 - 999 sec configurable
Remote start delay: 0 - 999 sec configurable
Mains contactor output: 10A @ 250V-AC
Generator contactor output: 10A @ 250V-AC
Remote start output: 10A @ 250V-AC/28V-DC
Operating temperature: -30C to 70 C
Storage temperature: -30C to 80 C
Maximum humidity: 95% non-condensing.
Dimensions: 70x115x66mm (WxHxD)
Weight: 180g (approx.)
Installation: DIN Rail mounted.
Case material: High temperature, non-flammable ABS/PC
IP protection: IP20