Danfoss 176F4190 Manuel utilisateur

4
2
5
e30bf963.10
3
6
Illustration 1: Direction of Airflow with Kit Installed
1
Top cover
2
Cabinet
3
Pedestal
4
Cooling back channel
5
Air flow direction
6
Bottom cover
1.2 Kit Numbers
Use these instructions with the following kits.
Table 1: Numbers for In-back/Out-back Cooling Kits
Number
Kit description
176F4190
FK09c/FB09c in-back/out-back cooling kit
176F4191
FK10c/FB10c in-back/out-back cooling kit
1.3 Items Supplied
Table 2 provides a list of items included in the kit. Refer also to 2.2 Installation Overview.
AN371942578354en-000101 / 136R0290 | 1Danfoss A/S © 2023.09
Installation Guide
In-back/Out-back Cooling Kit
for FK09c/FB09c and FK10c/FB10c
iC7 Series Frequency Converters
1 Overview
1.1 Description
The in-back/out-back cooling kit fits iC7 Series FK09c/FB09c and FK10c/FB10c Frequency Converters. When the kit is installed,
airflows into the lower back duct and out through the upper back duct. See Illustration 1.
1

Table 2: Items Supplied in In-back/Out-back Cooling Kits
Item
Quantity
Top flange spacer
1
Top cover
1
Top cover gasket
1
Drive slot gasket
1
Bottom bracket
1
Base plate gasket
1
Base plate
1
Front spacer
1
Bottom cover gasket
1
Bottom cover
1
M5x12 screw
11–12
M5x16 countersunk screw
4
M5x18 screw
8
Back vent spacer
2
Back vent gasket
4
AN371942578354en-000101 / 136R02902 | Danfoss A/S © 2023.09
Overview
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

-
-
-
-
-
-
-
-
-
-
-
-
2 Installation
2.1 Safety Information
NOTICE
QUALIFIED PERSONNEL
Only qualified personnel are allowed to install the parts described in these installation instructions.
Disassembly and reassembly of the frequency converter must be done in accordance with the corresponding service guide.
Use the standard fastener torque values from the service guide, unless the torque value is specified in these instructions.
WARNING
ELECTRICAL SHOCK HAZARD
The frequency converter contains dangerous voltages when connected to mains voltage. Improper installation, and installing or
servicing with power connected, can cause death, serious injury, or equipment failure.
Only use qualified electricians for the installation.
Disconnect the frequency converter from all power sources before installation or service.
Treat the frequency converter as live whenever the mains voltage is connected.
Follow the guidelines in these instructions and local electrical safety regulations.
WARNING
DISCHARGE TIME (20 MINUTES)
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not pow-
ered. High voltage can be present even when the warning indicator lights are off.
Failure to wait 20 minutes after power has been removed before performing service or repair work can result in death or serious
injury.
Stop the motor.
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery backups, UPS, and
DC-link connections to other frequency converters.
Wait 20 minutes for the capacitors to discharge fully before performing any service or repair work.
To verify full discharge, measure the voltage level.
NOTICE
ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components.
Ensure discharge before touching internal frequency converter components, for example by touching a grounded, conduc-
tive surface or by wearing a grounded armband.
2.2 Installation Overview
NOTICE
APPLYING GASKETS
This kit contains self-adhesive gaskets to ensure a proper seal between metal parts.
Before affixing a gasket, check that the part matches the gasket and that no holes are covered.
AN371942578354en-000101 / 136R0290 | 3Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

1
2
3
11
10
9
4
5
6
7
8
e30bk569.10
15
13
12
14
Illustration 2: Overview of In-back/Out-back Cooling Kit
1
Top flange spacer
2
Top cover
3
Top cover gasket
4
Bottom bracket
5
Drive slot gasket
6
Base plate gasket
7
Base plate
8
Front spacer
9
Bottom cover gasket
10
Bottom cover
11
M5x12 screw (11–12)
12
M5x16 countersunk screw (4)
13
M5 x 18 screw (8)
14
Back vent spacer (2)
15
Back vent spacer gasket (4)
AN371942578354en-000101 / 136R02904 | Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

1.
2.
-a.
-b.
2.3 Installing the Back Vent Spacers
To install the back vent spacers, use the following steps. See Illustration 3.
Procedure
Affix 4 back vent gaskets to the 2 back vent spacers.
Place 1 gasket on the inner side and 1 gasket on the outer side of each spacer.
Attach the back vent spacers around the upper and lower openings in the back of the frequency converter:
Secure 8 M5x18 screws, 4 in the corners of each back vent spacer.
Fasten 4 M5x16 countersunk screws, 2 in each back vent spacer along the upper and lower edges.
e30bk580.10
1
2
3
4
5
Illustration 3: Installation of Back Vent Spacers (Upper and Lower)
1
Back vent spacer gasket (inner)
2
Back vent spacer
3
Back vent spacer gasket (outer)
4
M6x12 screw
5
M5x18 countersunk screw
AN371942578354en-000101 / 136R0290 | 5Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

1.
2.
3.
4.
5.
2.4 Installing the Base Plate
Use the following steps to install the base plate. See Illustration 4.
Procedure
Unfasten 9 M5x12 screws (T25) from the cable access plate (gland plate), and remove the plate from the bottom of the
frequency converter.
Keep the cable access plate and screws for reinstallation.
Adhere the base plate gasket to the underside of the base plate.
Fasten the bottom bracket to the upper side of the base plate using 2 M5x12 screws (T25) from the kit.
Position the base plate at the bottom of the frequency converter.
Secure the base plate using 6 M5x12 screws (T25) from the kit.
e30bk579.10
Illustration 4: Installation of Bottom Bracket and Base Plate
AN371942578354en-000101 / 136R02906 | Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

1.
2.
3.
1.
2.
2.5 Installing the Bottom Cover
Use the following steps to install the bottom cover . See Illustration 4.
Procedure
Adhere the bottom cover gasket to the upper surface of the bottom cover.
If mounting the frequency converter on a pedestal, install the bottom cover after the pedestal is attached.
Position the bottom cover over the opening in the base plate at the lower end of the cooling channel.
Secure the bottom cover using 6 M5x16 screws (T25) from the kit.
e30bk581.10
Illustration 5: Bottom Cover Installation
2.6 Installing the Cable Entry Plate
The cable entry plate provides cable entry and cable termination points. The plate is installed to maintain the IP21/Type 1 or IP54/
Type 12 protection rating.
To install the cable entry plate, use the following steps. See Illustration 6.
Procedure
Create cable entry holes in the plate using a sheet metal punch.
Reuse the cable entry plate that was removed during base plate installation.
Position the cable access plate at the bottom of the frequency converter.
AN371942578354en-000101 / 136R0290 | 7Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

3.
-
-
-
-
-
-
Fasten 9 M5x12 screws (T25), attaching the cable access plate to the opening in the base plate adapter.
e30bk603.10
Illustration 6: Installation of Cable Access Plate
2.7 Lifting the Frequency Converter
WARNING
LIFTING PRECAUTIONS
The frequency converter is heavy. Failure to follow local safety regulations for lifting heavy weights can cause death, person-
al injury, or property damage.
Ensure that the lifting equipment is in proper working condition.
Check the weight of the frequency converter and verify that the lifting equipment can safely lift the weight.
Always lift the frequency converter using the eye bolts at the top of the frequency converter.
Ensure that the angle from the top of the frequency converter to the lifting cable is 65° or greater.
Test lift the frequency converter approximately 610 mm (24 in) to verify the proper center of gravity lift point. Reposition the
lifting point if the frequency converter is not level.
Never walk under suspended loads.
Always lift the frequency converter using the recommended lifting method and safety precautions.
AN371942578354en-000101 / 136R02908 | Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

1.
Example
e30bk607.10
≤65°
Illustration 7: Recommended Lifting Method, Fx09 and Fx10
2.8 Wall-mounting the Frequency Converter
FK09c frequency converters can be wall-mounted or pedestal-mounted. To mount the FK09c frequency converter on a wall or
mounting panel, use the following steps. See Illustration 8, Illustration 9, and Illustration 10.
FK10c frequency converters are pedestal-mounted only. Refer to 2.9 Pedestal-mounting the Frequency Converter.
Procedure
Using the dimensions in Illustration 8, prepare the mounting surface.
Determine proper placement of the frequency converter, considering the operating environment and cable access re-
quirements. Ensure that the air intake and exhaust vents at the back of the frequency converter are not obstructed.
AN371942578354en-000101 / 136R0290 | 9Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide

2.
3.
325
(12.8)
246
(9.7)
180
(7.1)
1423
(56)
1380
(54.3)
200
(7.9)
62.5
(2.5)
17
(0.67)
18.7
(0.7)
Ø11
(0.43)
33.1
(1.3)
Ø11
(0.43)
25
(1.0)
e30bk618.10
Illustration 8: Dimension for Mounting FK09c Frequency Converter
Use 4 M10 bolts, 2 in the upper and 2 in the lower mounting holes.
Apply the drive slot gasket over the slots at the back lower edge of the frequency converter.
AN371942578354en-000101 / 136R029010 | Danfoss A/S © 2023.09
Installation
In-back/Out-back Cooling Kit for FK09c/FB09c and FK10c/FB10c
Installation Guide
Ce manuel convient aux modèles suivants