Canovate IP PDU Series Manuel utilisateur

Canovate Elk.End.Tic.A.S 1
IP PDU SERIES
USER MANUAL

Canovate Elk.End.Tic.A.S
2
TABLE OF CONTESTS
CANOVATE IP-PDU.....................................................................................................................................
WARRANTY AND SERVICE INSTRUCTIONS ...............................................................................................
Unboxing Control..............................................................................................................................
Unboxing Control..............................................................................................................................
International Electrical Symbols......................................................................................................
Terms of Use.......................................................................................................................................
IP PDU FEATURES.........................................................................................................................................
CONNECTION TO COMPUTER...................................................................................................................
CONNECTION TO SERVER..........................................................................................................................
IP-PDU WEB INTERFACE OUTLINE ..............................................................................................................
IP-PDU WEB INTERFACE OUTLINE...............................................................................................................
Environmental Monitoring................................................................................................................
Power Monitoring.............................................................................................................................
Outlet Control...................................................................................................................................
Conguration....................................................................................................................................
Tools....................................................................................................................................................
Administrator.....................................................................................................................................
Logout................................................................................................................................................
ACCESSING WEB INTERFACE ....................................................................................................................
ENVIRONMENTAL MONITORING .............................................................................................................
POWER MONITORING.................................................................................................................................
INDIVIDUAL OUTLET CONTROL AND RENAME .........................................................................................
SYSTEM INFORMATION ..............................................................................................................................
MODIFYING NETWORK SETTINGS .............................................................................................................
MODIFYING NETWORK SETTINGS .............................................................................................................
HTTP.............................................................................................................................................................
MANAGE USERS..........................................................................................................................................
TIME SERVER CONFIGURATION (SNTP) .....................................................................................................
SNMP...........................................................................................................................................................
EMAIL..........................................................................................................................................................
WAKE ON LAN............................................................................................................................................
PASSWORD CHANGE ................................................................................................................................
LOGS...........................................................................................................................................................
RESTORING TO FACTROY SETTINGS ..........................................................................................................
LOGOUT ......................................................................................................................................................
PARAMETERS...............................................................................................................................................
FREQUENTLY ASKED QUESTIONS ...............................................................................................................
STANDARTS..................................................................................................................................................
NOTES .........................................................................................................................................................
03
03
03
03 - 04
04
04
05
05
06
07
08
08
08
08
08
08
08
08
09 - 10
11
11
12
13
13
14
15
15
16
16
17
17
18
18
19
19
20
20
21
22

Canovate Elk.End.Tic.A.S 3
CANOVATE “IP PDU”
WARRANTY AND SERVICE INSTRUCTIONS
Unboxing Control:
Safe Operation Limits:
Canovate offers reliable, high quality data center power distribution units (PDUs) designed for maximum per-
formance.
Data centers of industries like Telecom, Hosting & Colocation, Finance, Insurance, Education, Power, Aeros-
pace, Medical, E-government, Utilities like Oil, Gas, Water companies and also Industry 4.0 and Internet of
things etc. where remote monitoring and access is required.
Canovate Outlet based switched INLET-PDU offers real-time remote power monitoring of voltage (Volts), cur-
rent (Amps), power (kW, kVA) and energy consumption (kWh) with billing grade accuracy at the entire PDU
level.
Each socket can be opened and closed remotely and independently of each other.
With the fuses on the IP PDU, it is possible to open / close the socket groups independently of each other.
Read the safety rules carefully before using the product to prevent electric shock or injury.
It is designed for on-off operation at AC voltage.
The manufacturer should be consulted before performing DC voltage control.
If the maximum current and voltage values are exceeded or the total current drawn from the group socket is
exceeded for each socket on the set, permanent damage to the device may occur.
If the device usage limits do not match, the user is responsible for any damage that may occur. (Chapter-18
Parameters)
When the package is opened;
• IP PDU 1 pcs
• User Manual 1 pcs
For your detailed requests and questions;
Eksioğlu Mah. Atabey Cad. No: 12 Çekmeköy ISTANBUL, TR 34794 www.canovate.com teknik.destek@cano-
vate.com [email protected] T: +90 (216) 484 22 22 F: +90 (216) 484 05 06
•The unit can be connected to 110 - 220 VAC network systems.
•Ethernet input; Cat-5 Cat-6 cabling system is supplied with RJ45 type connector.
•Socket features on the device;
240 VAC / 10A (2400 Watt) for C13 type socket
240 VAC / 16A (3840 Watts) for C19, Schuko sockets
Permanent damage to the power outlet can occur when more power than the specied power.
•For IP PDU energy cable;
•240 VAC / 16A / 32A can carry maximum power. Drawing more power from the specied power may result
in permanent damage to the device or may cause re.
Warning:
Warning:
There is low voltage on the device. Place it so that it cannot be reached by children and unauthorized per-
sons. Only authorized technical service personnel can intervene.
In case of opening the device other than authorized service, it will be out of warranty.

Canovate Elk.End.Tic.A.S
4
• • Ethernet input;
It contains insulation up to 1000 VAC.
Larger interference that may occur over the Ethernet cable may cause permanent damage to the
device. For this reason, the communication Ethernet cable must be kept away from places containing
high magnetic elds.
• ADSL splitter inputs comply with Telecom standards and may cause data loss in areas with high magnetic
elds.
• The device is designed to operate between 0-70 ° C.
• The device is operating at %0-80 rh humidity range.
• IP PDU is designed and manufactured in accordance with indoor usage conditions.
Uluslararası Elektrik Sembolleri:
Terms of Use:
Warning:
Read the safety rules carefully before using the tool to prevent electric shock and injuries.
• Check the device body. If it is damaged, do not use it.
• Do not apply a voltage higher than the specied voltage to the device.
• Do not insert any objects other than the proper electric plug into the socket on the device.
• Fit the electrical plugs tted to the sockets properly and properly. Do not leave a space.
• Place it in such a way that children cannot reach it.
• Connect the Ethernet port via a Hub / Switch / Router / DSL / Gateway.
• Do not use or store it in environments with high humidity, high temperature, explosive and high magnetic
elds.
• Before unplugging any other device connected to the device sockets, bring the corresponding outlet to
the off position.
• Never interfere with the internal circuit of the device.
• Never clean the appliance with damp or wet material.
AC AC or DC
Earthing
DC

Canovate Elk.End.Tic.A.S 5
• 10/100 Mbyte Ethernet,
• Built-in web server,
• 2 channel dry contact input
• SMTP client (sending an alarm by e-mail at the limit exceeded)
for temperature and humidity sensor
• SNMPV1, SNMPV2, and SNMPV2C
• SNTP (Time Protocol)
• Authorized access feature
• 1 admin 12 restricted users
• Timer function for each socket and periodic ON/OFF
• Energy management and wake-up of computers over the network during sleep-mode
• Remote power monitoring of voltage (Volts), current (Amps), power (kW, kVA)
and energy consumption (kWh) entire PDU level
• Outlet based switching capability
• Sudden shock suppression
• High frequency lter
• Aluminum body
• Suitable for 1.5U rack mounting
IP PDU HIGHLIGHTS
CONNECTION TO COMPUTER
DSL
Power ADSL DATA ETHERNET
Ethernet connection to Router / Hub / Switch / ADSL for IP PDU
DSL/Router/Hub/Switch
DSL
Power ADSL DATA ETHERNET
Ethernet connection
of IP PDU to PC
Cable Type: Automatically detects.

Canovate Elk.End.Tic.A.S
6
A-PDU
B-PDU
CONNECTION TO SERVER
Ethernet Cable
POWER INPUT

Canovate Elk.End.Tic.A.S 7
PRODUCT PICTURE AND DESCRIPTION
8
7
6
5
4
32
1
1’to.................. 8’
ON/OFF
Combo Temperature and Humidity Sensor
Reset Button
Ethernet Entry
Led Indicators
Dry Contact Input
Circuit Breaker
Circuit Breaker
Socket Group
Power Cable
Commando
1 Phase

IP- PDU WEB INTERFACE
ENVIRONMENTAL MONITORING
- SENSORS
- TEMP & HUMIDITY GRAPHS
POWER MONITORING
- ENERGY METER FEEDS
OUTLET CONTROL
- INDIVIDUAL
CONFIGURATION
- SYSTEM
- NETWORK
- SENSORS
- HTTP
- USERS
- SNTP
- SNMP
- EMAIL
- OUTLETS
- WAKE ON LAN
TOOLS
- CHANGE PASSWORD
ADMINISTRATION
- LOGS
- RESTART
LOGOUT
Shows measurement values for any attached sensors
Shows measurement values for any attached sensors
Voltage, current, power and energy measurements
Turn on-off, operate in time schedule
System information, rmware revision, etc.
Network settings
Sensor settings
Enable/disable web server, change port number
Manage users and access to web interface
Time server settings
SNMP settings
SMTP server (e-mail sender) conguration
Rename outlets
Change password
Restart to web server
Log for last 50 activities
Reset to factory defaults
Logout
Settings to remotely turn on computers on LAN

Canovate Elk.End.Tic.A.S 9
1- Accessing Web Interface
Use your favorite web browser to access PDU’s web interface:
Varsayılan IP adresi: 192.168.1.45
Varsayılan giriş: admin
Varsayılan şifre: admin1
For restricted user, user name can be entered as user and password as user. The restricted user can not ac-
cess the device’s network settings
Your computer must be in the same network subnet.
If not, change your computer’s IP address to 192.168.1.99, as shown in example below:
By checking the PC’s netmask and gateway settings,
Netmask : 255.255.255.0,
Gateway : 192.168.1.1

Canovate Elk.End.Tic.A.S
10
IP adres: 192.168.1.99
Subnet mask: 255.255.255.0
Gateway: 192.168.1.1
If you log in successfully, you will see the following screen, you can start to check your IP PDU after seeing
the screen.
Ce manuel convient aux modèles suivants
3
Table des matières
Manuels Matériel réseau populaires d'autres marques

Matrix Switch Corporation
Matrix Switch Corporation MSC-HD161DEL Manuel utilisateur

B&B Electronics
B&B Electronics ZXT9-IO-222R2 Manuel utilisateur

Yudor
Yudor YDS-16 Manuel utilisateur

D-Link
D-Link ShareCenter DNS-320L Manuel utilisateur

Samsung
Samsung ES1642dc Instructions d'utilisation

Honeywell Home
Honeywell Home LTEM-PV Instructions de montage