Cairox UKUNDA Manuel du propriétaire

18/10/18 1
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
Contents
1.0 INTRODUCTION 2
1.1 PRODUCT DESCRIPTION 2
2.0 MAIN LAYOUTS 3
3.0 MAIN COMPONENTS 4
3.1 SAFETY 5
4.0 INSTALLATION 5
5 DIMENSIONS AND WEIGHT 8
6 ELECTRICAL INSTALLATION 9
7 UNIT OPERATION 12
8 AVAILABLE ACCESSORIES & CONTROLS 13
9 FROST RISK 15
10 CONDENSATE TRAY 16
High efciency heat recovery ventilation units Installation-Operation-Maintenance Manual

2 18/10/18
ⒶⒷ
Ⓒ
Ⓓ
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
High efciency heat recovery ventilation units Installation-Operation-Maintenance Manual
This manual is part of the product and must be deliv-
ered with the ventilation unit.
This appliance is not intended for use by persons (in-
cluding children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowl-
edge.
Children must be supervised.
The manufacturer will not be liable for damages re-
sulting from the failure to observe the safety instruc-
tions or improper use and or installation.
In the event of failure of the appliance and/or break-
age of any of its parts, deactivate it by disconnecting
it from the
electrical supply, and refrain from any attempt repair-
ing the unit and call for a qualied technician and orig-
inal spare parts.
It is responsibility of the installer to ensure that all of
the equipment is installed in compliance with the man-
ufacturers recommendations and with current local
1.0 INTRODUCTION
1.1 PRODUCT DESCRIPTION
legislation and codes of practice.
If these guidelines are not followed, the unit may experi-
ence a shortened life or may present a risk of unsafety.
To guarantee efciency and long working life, a unit in-
spection/maintenance should be carried out annually by
an expert technician.
The high efcient hear recovery unit is ideal for all re-
quirements in restaurants, ofces meeting rooms, class-
rooms, shops and warehouses.
The layout shall take into account the space necessary
for installation of the unit and mainteinance/service pur-
poses, consider the possible noise generation too.
The unit is for indoor installation only
The energy-recovery technology uses the heat of the
stale indoor air to be expelled in order to either heat the
incoming fresh air to a temperature much closer to the
existing indoor air.
ATTENTION :
spigots and rectangular connections are not delivered
The basic unit includes the following separate parts:
Ⓐ 1x unit complete with lter set
Ⓑ 1x manual
Ⓒ 1x touch screen controller
Ⓓ 2x spigot adapters (connections are not included)
ATTENTION :
spigots and rectangular connections are not delivered

18/10/18 3
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
2.0 MAIN LAYOUTS
HOC horizontal side connection layout
BACK
FRONT
supply fresh return exhaust

4 18/10/18
①
⑤
④
⑨
⑩
⑪
⑫
⑨
③
⑤
⑥
⑦
②
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
1Touch screen control (remotable)
2High efciency counterow heat exchanger
3Electronic box with connections
4Air lter
5Air lter
6Condensate discharge
7Bypass valve for free cooling
8Extract and supply fans
9Side panels
10 Unit body
11 IRS (PIR)
12 Accessory comparment (HWD - CWD)
UNIT WITH DUCTED RETURN
2.0 MAIN COMPONENTS

18/10/18 5
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
3.1 SAFETY
Installation has to be carried on by a qualied technician.
Unit and accessories must be supplied by a dedicated
power line and duly sized differential safety and thermal
protection. Before proceeding with maintenance please
unplug the system.
Unit and accessories must not be used as security ven-
tilation systems. Do not install in potentially explosive
atmosphere.
All control wires need be 50 mm away from power cable
(because of magnetic elds).
Use genuine spare parts only to be sure not to void war-
ranty.
Obey the local re regulations, as well as environmental
law requirements.
The manufacturer does not accept liability for this.
Observe as well the safety regulations and wear protec-
tive gloves.
The unit is designed to provide mechanical ventilation
with heat recovery. The unit can operate with constant
speed, constant air ow or constant pressure, with relat-
ed accessories. The unit is equipped with high efciency
heat exchanger (up to 95% heat can be recovered) and
with low consumption EC motors fan.
The unit is for indoor installation. Operation Temperature
Before starting installation check that the unit has been
supplied complete and undamaged. Visible loss or dam-
age is apparent at the time of delivery must be noted.
Noted loss or damage must be recorded in detail on the
delivery receipt. When recording loss or damage, please
use specic details and try to avoid general or generic
terms such as “box damaged” or “torn”.
Check also size, model and accessories.
The unit must be stored in a dry clean place protected
from frosting and magnetic elds in its original packag-
ing until installation.
In case of long-term storage, or inactivity the unit must
be protected from dust and moisture, and run the test
described in part 1 1995-11 DIN VDE 0702-1.
Don’t run the unit prior to complete installation.
4 INSTALLATION
During installation leave a free space to maintenance
and service. Tha access panels have to be opened for
that purpose, see free space reccomendation for ser-
vicing and to allow internal components to be removed
for cleaning or service (for ex. heat exchangers, fans,
lters).
3.2 UNIT CONSIGNEE AND STORAGE
is 0-40°C (without ambient frosting). For external Tem-
perature lower than -10°C preheater is recommended.
Do not continuously use the unit in the presence of water
vapor (both internal and external to the unit). For high
humidity atmosphere inquiry the manufacturer.
The automatic frost protection is provided by ow imbal-
ancing. Optional integrated heating coil for lower tem-
peratures is recommended.
Electronic controlled bypass damper is provided to sup-
ply ltered outside fresh air. Bypass opens and clos-
es according to the setting available on touch screen
(KTS) or can be driven by an external input. Min exter-
nal temperature to close bypass and threshold internal
temperature to open bypass can be set. High surface
area washable G4 lter (coarse) (on return side) and F7
ePM1 55%(fresh side) are standard.
Clogged lter alarm is by pressure sensors as standard.
Installing conditions and aeraulic system if not adequate
or properly planned can affect the nominal performanc-
es of the unit.

6 18/10/18
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
The unit is factory delivered on a returnable pallet to as-
sure an easy and safe transport. Do not disassemble it,
follow the instruction step by step.
For crane transportation all applicable safety regulations
crane must be respected.
• The unit must be lifted either with disposable pallet by
crane.
• The unit or the pallet edges are separated by a suitable
base (or by transport bars, trusses, wooden spacers, etc.)
to protect against damage.
• The same applies to any protruding Accessories (eg
equipment roof)
• transport bars, trusses, wooden spacers, cable loops,
pull ropes, lifting gear and other accessories required
for the crane transport are not included and therefore be
provided on site.
• Access panels and electronics controls must be always
closed and protected during transport.
4.1 UNIT HANDLING AND INSTALLATION
VERY IMPORTANT : FIX THE RETAINING SCREWS AGAIN
proceed reverse to reinstall the side access panels . x the screws
remove retaining
screws remove panels x the unit to
the ceiling
4.2 HANDLING PROCEDURE
TAKE THE SCREWS AWAY
FROM BACK SIDE
4.2.1 UNIT WITHOUT DUCTED RETURN
4.2.2 UNIT WITH DUCTED RETURN
x the plenum to the unit and x the unit
through the 2 holes
x the rod bars with 4
nuts (locknuts) and 4
washers per rod
use the existing
holes to x the
plenum

18/10/18 7
300 mm
600 mm 600 mm
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
Ceiling, wall, oor or surface must be hard, at and level.
Please also check the local atmosphere: the humidity in
the room where should no more than 65% rel. Particular-
ly, the structure in new attic buildings should be checked
prior to installation with the installer.
The ambient temperature and operating temperature
should not exceed + 40 ° C. The air temperatures in
and production facilities must be observed and may not
exceed 45 ° C.
The ventilation unit is not suitable for use in technological
processes when explosive or aggressive substances are
contained in the air stream.
Non-compliance with the instructions will void any war-
ranties for the proper function of the equipment as well as
the manufacturer responsibility.
4.2.3 BASIC REQUIREMENTS
Important:
Check the unit air ow layout and installation: it is not
possible to change the ordered layout in site and specic
user requirements are to be factory tted with dedicated
customization.
The installation place must be indoor and frost free.
Leave a free space for panel opening for service oper-
ation, for example lter extraction and eventual mainte-
nance.
The unit must be placed leveled: this is important to drain
the condensate. Remember the condensate ducting with
siphon.
VERY IMPORTANT : The unit can be mounted to the
ceiling using the two holes in the bracket .
Make sure that the backside panel is airtight .
See table of weight and dimensions for each size .
The supporting rods must be sized to carry at least 2
times the weight .
4.2.4 REQUIREMENTS FOR THE INSTALLATION PLACE
CEILING VOID
free space for service
and operation
free space for
service
and operation
free space for
service
and operation

8 18/10/18
DRAWN
CHECKED
ENG APPR
MGR APPR
Classe di tolleranza*:
ISO 2768-M
*Ove non diversamente specificato
NAME
Tech. Dept.
DATE
03/23/18
NAME:
SIZE
A2
FILE NAME: SG_TOP_PLENUM.dft
SHEET 1 OF 1
Material: LAM. ZINCATA
1,00 mm
Spessore:
SG_TOP_PLENUM
PROJECT:
Raggio di piega
R=1.3
Cava V10
Tutte le pieghe si
intendono a 90°
dove non
diversamente
specificato
O
200
O
200
O
200
O200
1530
1580 330
280
500
500
A /A1
[mm] B /B1
/
B2
[mm] C[mm] D[mm] E[mm] F[mm]
G[mm]
H[mm] [kg]
40 1560/1400 1850/1400/150 250 190 260 365
200 1280 170
70 1860/1700 1850/1400/150 250 190 260 365
200 1580 201
120 1860/1700 1850/1400/150 350 250 300 365
315 1580 310
A
B
C
E
D
F
G
B1
B2
A1
F
H
H- 50
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
VIEW FROM TOP
VIEW FROM FRONT
VIEW FROM BACK SIDE
DO NOT SCALE
PLENUM FOR DUCTED RETURN
5 DIMENSIONS
SIZE WEIGHT

18/10/18 9
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
6 ELECTRICAL INSTALLATION PROCEDURE
Warning! Always unplug the unit during the installation.
The unit must be earthed, a fuse is available , protect each unit by residual-current circuit breaker (RCCB) and
thermomagnetic cut-out device.
We recommend to check if the supply system is already in accordance to your regional safety regulations.
Connect the wiring to the electrical box.
Touch screen control has to be connected to the board with a RJ45 8-pole Ethernet straight cable of Cat.5 (or
higher).
The unit can be equipped with two external control (Input 0-10 V) to set unit on-off, bypass on-off or proportional air
ow control; it can also give two output signals congurable on unit run-bypass open-unit fault.
Important: Input and output conguration is to be set in the touch screen control - service menu -.
Priority: when the unit receives an off command, whatever the input has given it, this has always the priority.
6.1 ELECTRIC CONNECTIONS
POWER CONNECTION :
1. Unscrew the electric box
small lid
2. Remove the cover to reach
the power plug and pull it
out, Connect the power cable
in conformity with the labels
located on the board
3. Close the box and lay the
cable under the cover recess
remove the left hand side panel

10 18/10/18
UKUNDA
SIG AH
Heat Recovery unit Installation-Operation-Maintenance
reserves the right to change the specications of the product at any time without prior notice
See power intake table for sizing the power cable. Always protect each unit with proper indipendent main
switch and safety protection (in accordance to the local laws).
Cable for remote control must be in accordance to the recommendatios you nd in the IOM of the remote control.
VERY IMPORTANT : cable through the cable guide