information to be available in all cases: as one is available as primary information, the other is available as
secondary information.
rPC: Percent returned from last discharge. Because of batteries’ inherent inefficiency, it is necessary to recharge
batteries with more energy than was taken out. Flooded batteries require at least 10% more charge than was
removed, while AGM batteries need only about 5–8% more. While the battery is being discharged, the value
shown is 0. While the battery is being charged, the value is the amount of charge added so far as a percentage
of the amount of charge last removed, or anywhere from 0% to 110% or more.
The following three are not shown on front label. The SC-2030 must be connected and communicating with the
TM-2030. They only display when the sun is supplying power to the SC-2030 charger
ºC: The battery temperature in degrees Celsius
SOL: Solar amperes: the amount of current being delivered from the solar panels from SC-2030.
UPr: Unused solar power: shows if extra power is available from sun that could be used when battery charging is
tapering down in the afternoon. Run appliances such as a dishwasher or vacuum when this extra power is
available, which would otherwise be wasted. Displays “YES” when nearly all solar power available for extra
use. If a number is displayed it is showing watts available.
2.2. Programmable Settings. More details can be found in the SC-2030 user guide.
Two sets of programmable settings are available. The basic set is always available. The advanced set is available only
when the “user level” has been set to L3 or higher using setting P7, which is necessary when using the SC-2030. This
section describes the programmable settings in summary form.
2.2.1.Basic Programmable Parameters
The following parameters comprise the basic set:
⁃P1: Charged voltage set point. Bulk charging of the battery stops when the voltage has reached this limit.
(10-65V)
⁃P2: Current threshold prior to switching to finish charging. When the charging current drops below the level set by
this parameter, expressed as a percentage of the battery’s capacity (P3), the state of the charger changes from
bulk charging to finish charging. The charging current is then limited to the value set in P21 described in the
section below. It is recommended that not more than 5% be used. (OFF or 0.1-9.9%)
⁃P3: Battery system capacity in Amp-hours (10-9990 A-hr)
⁃P4: Current (“A”) or power (“Pr”) in amps primary display mode
⁃P5: Days-since-charged alarm set point (off, 0.0-250 days)
⁃P6: Days-since-equalized alarm set point (off, 0.0-250 days)
⁃P7: User level, required to access the advanced parameters (L1, L2, L3, L4)
2.2.2.Advanced Programmable Parameters
The advanced parameters can be accessed only if the user level has been set to L3 using program P7. Default values
are reinstalled whenever P7 is switched to L1 or L2.
⁃P9: Low-battery beeper alarm threshold (OFF, 1–100%). Setting this parameter to “OFF” disables the beeper
alarm both for low battery charge percentage (this parameter) and for low battery voltage (P13 parameter).
Default: OFF
⁃P10: Efficiency factor (60–100%). This parameter affects how the “% full” and “amp hours from full” values are
evaluated. Discharging amps are always evaluated at 100%. Charging amps are evaluated at this lesser percent
to account for battery charging inefficiency. Default: 94%
⁃P11: Shunt type. “H” means 500A/50mV and “L” means 100A/100mV. Default: H
⁃P12: Auto reset. When “OFF,” percent full and amp hours are never automatically reset. Default: On
⁃P13: Low battery voltage alarm setting (10.0-65.0 V) Default: 10.0
⁃P14: Maximum allowed finish-charge time in hours until float (0.0-5.0) Default: 0.0
⁃P15: Maximum finish-charge voltage (10.0-65.0 V)
⁃P16: Float-voltage setting (10.0-65.0 V)
⁃P17: Hours before history data is recorded: for data H7, H8 and H9 (0-24)
⁃P18: Adjust battery calibration voltage.
⁃P19: Reset TriMetric to factory settings.
⁃P20: Percentage of overcharge compared to last discharge until float (1-20%)
⁃P21: Finish charge current limit: specifies current as a percentage of the battery capacity (0-10%)