Shenzhen Beilai Technology Co., Ltd. V1.0
1.3 Features
Support Modbus RTU protocol
RS485 serial port with ESD protection
DC9~36V power supply with anti-reverse connection protection
Industrial grade chip, reliable performance with in-built watchdog
LED for status indication makes it easy to program in filed
Support configure parameters, load/export profiles via PC
Wall mount or 35mm standard DIN rail installation
Digital Input: Wet Contact/Dry Contact, compatible with pulse counting, TTL
Digital Output: Relay (5A/250VAC), compatible with pulse output
Analog Input: 4~20mA/0-20mA/0~5V/0~10V, 16-bit AD acquisition and
processing, the maximum and minimum values of the analog input can be
configured, and the actual value can be converted automatically
Thermal Resistance: The accuracy of the PT100 input can be adjusted online
through the configuration software
Thermocouple: B, E, J, K, N, R, S, T type Thermocouple, Thermocouple model
and compensation can be set online through the configuration software
1.4 Specification
Typically≤0.3W; Models with Relay Output≤3W; Peak voltage
must not exceed +40V
Modbus RTU (RS485, Modbus Address: 1~247)
Not isolation. Common ground. Relay contact independent
output.
“n,8,1”, “e,8,1”,”o,8,1”,”n,8,2”, etc
2400, 4800, 9600, 19200, 38400, 57600, 115200Bps, etc
Logic level: 0~0.5V or shorted is 0, +3~30V or open circuit is 1
Input electrical level range: 0 ~ 30V, limit range is -10 ~ 40V