Operating concept
After lockout, the red fault LED is steady on. For reading the cause of fault, refer to the
blink code given in the following table:
Diagnosisofcauseoffault
AL
FS
LED on (waiting time 10 s)
Fault
Press lockout reset button
for > 3 s Blink code Off Blink code
Approx.
3 s
ELECTRICEQUIPMENT
CONTROL DIAGNOSIS UNDER FAULT CONDITIONS AND LOCKOUT INDICATION
GAS BURNER CONTROL: LMG ...
AL
• Burner control has initiated lockout • Reset
> RedfaultLED on Press lockout reset button for 0.5 ...3 s
• Diagnosisofcauseof fault
- Wait >10 s
- Press lockout reset buttonj for >3 s
- Read blink code of red fault LED
>«Errorcodetable»
Error code table
Blink code Possiblecause
2x • Noestablishmentof flame at the end of «TSA»
•• - Faulty or soiled detector electrode
- Faultyorsoiledfuelvalves
- Pooradjustmentofburner
3x • Air pressure monitor does not close
••• - «LP»faulty
- «LP» incorrectly adjusted
- Fan motor does not run
4 x • Air pressure monitor does not open or extraneous light on
burnerstartup
•••• -«LP» faulty
- «LP» incorrectly adjusted
5x • Extraneouslightduringpre-purging
••••• - Orinternal device fault
7 x • Loss of flame during operation
••••••• - Pooradjustmentofburner
- Faultyorsoiledfuelvalves
- Short-circuitbetweendetectorelectrodeandground
8...17 x • Free
••••••••
..................
••••••••••
•••••••
18x • Air pressure monitor opens during pre-purging or operation
•••••••••• - «LP» incorrectly adjusted
•••••••• - Four times loss of flame during operation (LMG25)
19x • Faultyoutputcontact
•••••••••• - Wiring error
••••••••• - Externalpowersupplyonoutputterminal
20x • Internaldevicefault
••••••••••
••••••••••
Duringthetimethecauseof
the fault is diagnosed, the
control outputs are deacti-
vated.
- Theburnerremains shut
down
- Exception:faultstatussig-
nal «AL» at terminal 10
The burner is switched on
onlyafter a reset is made.
- Presslockoutresetbutton
for 0.5...3 seconds
RedLEDon