MEASURES AND CHECKS BEFORE START-UP, 1-STAGE BURNER
INNER ASSEMBLY
Ensure that the ignition and ionisa-
tion electrodes are correctly adjus-
ted. The sketch shows the correct
measurements.
GAS QUALITY
Ensurethattheburnerheadismeant
for the gas quality to be used (see
fig.).
VENTING
The gas line is vented by loosening
the screw on the test nipple for the
inletpressure.Connectaplastichose
and conduct the gas into the open.
After having vented the gas line tigh-
ten the screw again.
LEAKAGE CONTROL
Whenmakingaleakagecontrolofthe
gassupplysystemthesolenoidvalve
shouldbe closed. Connecta pressu-
regaugetothetestnipplePa,seefig.
Thetestpressureinthesystemshould
be 1,5x max. inlet pressure or min.
150 mbar. If any leakage, locate the
source bymeansofsoapywaterora
leak location spray. After tightening
repeat the test.
ELECTRIC FUNCTION TEST:
Ensurethatphaseandneutralarenot
reversed. The gas shut-off cock
should be closed.To prevent the gas
pressure switch from locking out it
should be linked temporarily.
After the main switch has been swit-
ched on and the thermostats have
beenadjustedthepre-purgingperiod
begins(30-35sec.).Attheendofthis
period the pre-ignition period starts
(0,5-2,5 sec. dependent on the de-
signofthegascontrol).Thegasvalve
is energized and opens and flame is
established. At the end of the safety
time (2-3 sec.) the gas control locks
out.Thesolenoidvalveandthemotor
will be "dead". Remove the link from
thegaspressureswitchafterthetest
is finished.
NOTE! APPLIES ONLY TO GAS
BURNER CONTROL LFL1.
When using LPG (Propane) the bur-
ner should be connected for post-
purge.Moveconnectiontoterminal6
to terminal 7 in the base of LFL1.
172 205 33 97-02
LEAKAGE CONTROL