Medical Gas Supply System
4109992485.00
Modular manifold headers for gas cylinders can be
connected to the Manifold Changeover System to
congureitsgassupplycapacity.
The Manifold Changeover System is connected to the
pipelinedistributionsystemupstreamoftheemergency
supply, or downstream of the primary supply system
when used as backup. It can be isolated from the
pipeline distribution system by the lockable isolation
valvesupplied.Whenusedasabackupsupplythisvalve
should be left open during normal operation, so the
unit will automatically supply the pipeline distribution
system with medical gas in the event of the primary
systemfailingtosupply.
When used as a backup manifold system the line
pressureshouldbeset slightlylower thanthe primary
supplypressuretopreventtheunitfromsupplyinggas
duringnormaloperationoftheprimarysupplysystem.
1.2 1stStagePressureRegulator.
Forsafe operation regardingperformance, mechanical
strength, resistance to ignition in pure high pressure
oxygensupplyandcleanliness,thedevicefullyconforms
toBSENISO10524-2.Apressurereliefvalveconnected
totheregulatorprotectsthedownstreampressureand
isseta2410kPa(24.1bar).
1.3 2ndStagePressureRegulator.
Forsafe operation regardingperformance, mechanical
strengthandcleannessthedevicefullyconformstoBS
ENISO10524-2,thesecondstagepressureregulatoris
a manually set diaphragm type and is used to set the
systempressure to suit typical nominalvalues for 4, 8
and11barpipelinesystems.
NOTE - To maximise performance each 2nd stage
pressureregulatoristtedwithinternalspringsspecic
tomatchthenominallinepressure.
1.4 LinePressureReliefValve.
Thelinepressure reliefvalves arepreset tothe values
shown in table 1 for the dierent line distribution
pressures.
Table 1: Line Pressure Relief Valve Set Points.
ReliefValveSetPoint Nominal Distribution
Pressure
520kPa(5.2bar) 400kPa(4bar)
1100kPa(11bar) 800kPa(8bar)
1300kPa(13bar) 1100kPa(11bar)
The line pressure relief valve is tted between the
pressure regulator and the isolation valve, thus
protectingthedeliverysystemfromoverpressurisation
bydischargingtoatmosphereintheeventofregulator
failure.
1.5 Modular Header for Cylinder
Connection.
The Medical Gas Supply System is compatible with
BeaconMedaesstandardmodularheaderssuppliedup
to2x6cylinderconnections,seetable2forreference.
1.6 Halogen Free Components.
The Medical Gas Supply System contains NO
HALOGENATEDpolymerslocatedinthegasstreamthat
may experience pressurised oxygen in excess of 3000
kPa(30bar)innormaloperationorsinglefaultcondition,
as recommended for safe practise of the medical gas
pipelinesystem.
GASTYPE 2 x 1 2 x 2 2 x 3 2 x 4 2x5 2 x 6
Oxygen (O2) 4109150303 4109150304 4109150305 4109150306 4109150307 4109150308
Nitrous Oxide (N2O) 4109150309 4109150310 4109150311 4109150312 4109150313 4109150314
Oxygen/Nitrous Oxide (O2/N2O) 4109150315 4109150316 4109150317 4109150318 4109150319 4109150320
Medical Air & Surgical Air 4109150321 4109150322 4109150323 4109150324 4109150325 4109150326
Nitrogen (N2) 4109150327 4109150328 4109150329 4109150330 4109150331 4109150332
Carbon Dioxide (CO2) 4109150333 4109150334 4109150335 4109150336 4109150337 4109150338
Table 2: Cylinder Modular Header.
Note-Kitscontainheadersforbothsides