Operational Instruction (Original) Distribution box Type 07-56..-…./….
BARTEC
Varnost d.o.o.
Cesta 9.avgusta 59
1410 Zagorje ob Savi
Slove ia
Tel.: +386 59 221 471
Fax: +386 59 221 470
i fo@bartecvar ost.si
www.bartecvar ost.si
Reservatio Tech ical data subject to cha ge without otice. Cha ges, errors a d
mispri ts may ot be used as a basis for a y claim for damages.
EN 2/3
– 11 01 351 (issue No I / 2.11.2016)
The distributio box
specified temperature class a d the tempera-
ture ra ge i dicated for it (see type label).
distributio box is
ot suitable for use i Zo es
0/20.
As for distributio
dust,
the ig itio temperature of the dust/air
mixture a d the glowi g temperature of the
dust co cer ed must be greater tha the
maximum surface temperature of the distribu-
tio box taki g i to accou t of the give safe
factor specified i EN 60079-0.
The distributio box may be operated o ly if
is
clea a d ot damaged i a y way. Dust
deposits > 5 mm (> 0.2 i ) must be removed.
U
tilizatio i areas other tha those specified or
the modificatio of the product by a yo e other
tha the ma ufacturer is ot permitted a d will
exempt BARTEC Var ost
defects a d a y further liability.
The ge erally applicable statutory
other bi di g directives relati g to workplace
safety, accide t preve tio a d e viro me tal
protectio must be observed.
Observe the applicable laws a d directives
whe commissio i g or restarti g operatio .
Always follow the safety i structio
operati g equipme t.
Marking
Particularly importa t poi ts i these i struc-
tio s are marked with a symbol:
DANGER i dicates a hazardous situatio
which, if ot avoided, will result i death
serious i jury.
WARNING i dicates a hazardous
which, if ot avoided, could
serious i jury.
CAUTION i dicates a hazardous situatio
which, if ot avoided, could result i mi or
moderate i jury.
NOTICE is used to address practices ot
related to perso al i jury.
Note
Important instructions and information on
effective, economical and environmentally
compatible handling.
2014/34/EU
as well as
EN 60079-0:2012/IEC 60079-0:20011
EN 60079-7:2007/IEC 60079-7:2006-7
EN 60079-11:2012/IEC 60079-11:2011
EN 60079-31:2009/IEC 60079-31:2008
as well as
EN 62208:2011/IEC 62208:20011
EN 60445:2010/IEC 60445:2010
EN 60529:1991 + A1:2000
Transport, storage
Risk of injury due to heavy loads.
Use a appropriate carryi g aid or a
appropriate mea s of tra sport (e.g. a fork-
lift) with a adequate load-carryi g ability.
E sure that the lifted load will ot tip over
or slip off.
Damage through incorrect transport or
incorrect storage.
Tra sport the distributio box
packagi g, ha dle with
drop.
Store the distributio box
packagi g.
Assembly, installation, and
commissioning
Risk of serious injury due to incorrect
proceedings.
O ly qualified perso el who are
authorized a d trai ed to assemble electri-
cal
compo e ts i hazardous (pote tially
explosive) areas may do a y of the as-
sembly, disassembly, i st
commissio i g work.
For assembly a d operatio of explosio
protected electrical equipme t, releva t i -
stallatio a d operati g regulatio s are
adhere (e.g. Betr.SichV, IEC/EN 60079-
a d series DIN VDE 0100).
The data o the label a d the EEC desig
test data are to be observed. Further tech-
ical i formatio
are provided i the Bartec
catalog a d o the product itself.
User may ot drill holes i the
boxes a d add termi als
Do ot ope the distributio box
e ergized.
Death or serious injury because of a miss-
ing protective earth connection.
Metallic distributio boxes
areas require equipote tial bo di g with at
least 4 mm².
Protective earth co ectio s have to be
protected agai st self-loose i g.
Risk of serious injury due to incorrect pro-
ceedings.
The assembly with co ecti g a d/or rail-
mou ted termi als must be impleme ted
u der the co sideratio of the EEC desig
i spectio certificate.
Check whe assembli g:
• Use suitable tools.
•
Pay atte tio to the type of mou ti g
required (for fitti g i to e clo-
sure/attachme t with ju ctio box).
• For distributio box
steps must be take to e sure smooth
operatio , for example rai protected
roofs, a d if ecessary, sufficie t e clo-
sure protectio .
Note
Metallic distribution boxes fo
facilities do not have to be attached to an
equipotential bonding system, except if it is
required by equipment documentation.
Installation
Risk of serious injury due to incorrect pro-
ceedings.
Exte sio s or modificatio s to the distribu-
tio box are o ly permissible if the ma u-
facturer’s approval is obtai ed first.
The IEC/EN60079-14 must be observed.
I stallatio s for the highly combustible ra g
must exhibit a EEC desig i spectio certifi-
cate. I stallatio of these compo e ts
take place i such way, so that at least the
e closure remai s IP54.
Co ectio of cables a d co ductors to equip-
me t i hazardous areas require Ex-
e tries, which are suitable for re
a d co ductor types. They must possess the
protectio type e” a d co tai a suitable seali g
gasket.
U used holes for cable e tries must bee
sealed with Ex-
certified plugs. Co ectio of
cables a d co ductors of zo e 21 a d 22
equipme t require at least the protec
IP66.