Armcor XCM125 Manuel utilisateur

Installation and
Operation Manual
XCM–COMPACT MULTIFLOW ERV
XCM125 – XCM1225
M
A
D
E
A
U
S
T
R
A
L
I
A
N
Ma
n
ufactured
by Armcor
M
A
D
E
A
U
S
T
R
A
L
I
A
N
Ma
n
ufactured
by Armcor

Contents
Equipment Application 3
Safety 4
Location of Equipment 5
Minimum Access Requirements for Maintenance
Noise Levels
Fresh Air Inlet and Exhaust Air Outlet
Drainage
Installation Instructions 6
Unpacking and Inspection
Unit Handling
Lifting with a Crane
Lifting with a Forklift
Suspending the Unit
Hanging Bracket Fixing
Equipment Connections 7
Ductwork
Filters
Electrical Requirements
Mains Power Supply and Fusing
Equipment Layout 8
OPTIONS FOR EVERY INSTALLATION
XCM With Centrifugal Fans
General Maintenance 12
General
Monthly Maintenance Schedules
Guide to How Frequency According to Usage is
Established
Three Monthly Checks Maintenance Schedules
Annual Maintenance Schedules
Pre-start Checklist 13
Commissioning Checklist 14
Troubleshooting Guide 15
Warranty 16
What The Warranty Policy Covers
What The Warranty Policy Does Not Cover
The Warranty Will Not Apply If;
How to Make a Warranty Claim
2 Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021

The XCM series is a compact, horizontal low prole heat recovery unit
designed for installation within a roof space, underoor or in a plant room.
These ERV units utilize the Xchange plate heat exchanger to recover
the energy from the exhaust air into the incoming fresh air, resulting in
signicant energy savings.
Centrifugal or EC Plug Fans are available with either enthalpy or sensible
heat exchange media.
Every proposed installation must be subject to an engineered design by a
mechanical services consultant.
Armcor Air Solutions is not responsible for performance of equipment in
applications for which the equipment was not designed or specied.
Equipment Application
Model
Number
Airow
Capacity
(I/sec)
Fan Filter Size
(mm)
Number
of lters
Weight
(kg)
Dimensions (mm)
H x W x L
XCM125P1 125 EC Plug 395 x 245 x 45 265 290 x 690 x 920
XCM225P1 225 EC Plug 395 x 395 x 45 280 440 x 690 x 920
XCM325C1 325 Centrifugal 495 x 395 x 45 290 440 x 830 x 1060
XCM325P1 325 EC Plug 495 x 395 x 45 2100 440 x 830 x 1060
XCM425C1 425 Centrifugal 595 x 395 x 45 2100 440 x 970 x 1200
XCM425P1 425 EC Plug 595 x 395 x 45 2110 440 x 970 x 1200
XCM625C1 625 Centrifugal 895 x 395 x 45 2120 440 x 1250 x 1480
XCM625P1 625 EC Plug 895 x 395 x 45 2130 440 x 1250 x 1480
XCM925C1 925 Centrifugal 895 x 595 x 45 2195 700 x 1250 x 1550
XCM925P1 925 EC Plug 895 x 595 x 45 2210 700 x 1250 x 1550
XCM1225C1 1225 Centrifugal 895 x 395 x 45 4 230 830 x 1250 x 1550
XCM1225P3 1225 EC Plug 895 x 395 x 45 4 245 830 x 1250 x 1550
XCM Specications
Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021 3

Warning
Improper installation, service, maintenance, or
use can cause explosion, re, electrical shock,
or other conditions, which may cause personal
injury or property damage and will void the
warranty.
Check with Armcor Air Solutions for any
information required on this equipment.
Danger
Electrical shock can cause personal injury or
death. Before performing any work on this
equipment, the electrical supply must be turned
off to avoid the possibility of shock, injury, or
damage to the equipment. There may be more
than one power supply circuit.
Installation by Authorised Personnel
• Only trained and qualied personnel should install, repair or service heat
recovery and/or air handling equipment.
• Installing and servicing equipment can be hazardous due to electrical and
mechanical components.
• When working on equipment, observe precautions in all literature, tags
and labels attached to or shipped with the unit. Follow all safety codes
and guidelines. Wear work gloves, safety goggles and protective clothing.
• All work must comply with relevant SAA wiring rules and local authority
codes. Installers must ensure that all statutory regulations and by laws
have been addressed.
• Installers must ensure that the structures built to support
the equipment have been suitably constructed for the
purpose, all safety precautions have been applied prior to
installation, and all preparation work has been suitably
sized and installed for its purpose.
Safety
4 Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021

It is important that the selected location for the equipment is suitable and
can adequately accommodate the unit physical size, the unit weight and
has safe and suitable access for correct operation and future maintenance
requirements.
Location of Equipment
Minimum Access Requirements
for Maintenance
• The unit must be mounted so that sufcient space is
allowed for installation and service access.
• Maintenance personnel need to gain access to all
parts of the unit and be able to remove components
such as fans and lters via access doors as required.
• Unless otherwise specied the following minimum
access should be available:
• 800mm clearance for electrical connections
• 1200mm for all access doors on the unit or if no
access door is provided 1200mm from the front of the
unit. Be very mindful that internal lters need to be
accessed regularly for cleaning.
• Every proposed installation must be subject to
an engineered design by a mechanical services
consultant. Armcor Air Solutions is not responsible
for installation of equipment in situations for which
the equipment was not designed or specied.
Noise Levels
• Do not locate equipment adjacent to sleeping
quarters unless background noise levels have been
checked and permitted by the appropriate authority.
• It is recommended that rubber supporting or
vibration absorbing pads be used to support the unit
to minimise any vibration being transmitted into the
building structure. We recommend wafe pad to be
used under the base frame and exible couplings be
tted to the supply and return ducts to reduce any
vibration transfer.
Fresh Air Inlet and Exhaust Air
Outlet
• The location of the fresh air inlets must adhere to the
Australian Standards 1668.2.
• The fresh air intake should be positioned clear of
any objects which could obstruct the airow and be
a minimum distance of 6 metres from any exhaust
discharge ducts from this unit or any other adjacent
equipment. Refer to Australian Standards AS 1668.2.
• The fresh air inlet and exhaust air outlet should
be tted with a cowl or other suitable means of
weatherproong.
• The exhaust discharge should be directed away from
any openable windows.
Drainage
Due to different moisture content levels of incoming
fresh air, heat exchange equipment can be subject
to some condensation. It is recommended that units
located in ceiling spaces or plant rooms are installed
with external drain trays under the complete unit.
Where an internal drain tray is tted, the condensate
drain outlet must be tted with a ‘P-Trap’ and have a
minimum ll of 20mm per metre length.
• Equipment should be installed with a positive fall
to ensure water drains away freely through drain
outlets. Drain lines must be as large as or larger than
the tting to which the line is being connected.
• All condensate drains must have a ‘P” Trap Fitted and
have a minimum fall of 20mm per metre length.
• If drain lines are to be extended from the inside to
the outside of the building, they must be extended
beyond walls of the building to eliminate the
possibility of damage caused by drain water running
down the exterior surface of the building wall.
• When a drain is exposed to freezing temperatures or
subject to the formation of condensation, the drain
should be insulated.
IMPORTANT: ALL UNITS LOCATED INDOORS MUST HAVE
DRAIN TRAYS UNDER THE COMPLETE UNIT.
Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021 5

Installation Instructions
Unpacking and Inspection
• The unit was tested and inspected prior to packing and
was in perfect condition at the time at time of despatch.
• The unit should be inspected upon delivery for
possible external damage incurred during transport.
If damage is evident it should be noted on the freight
docket and contact is to be made with the Armcor
Air Solutions sales ofce. A claim should be lodged
with the shipping company within 3 days if goods are
damaged or incomplete. No claims will be recognised
after this date.
• IF MAJOR DAMAGE IS APPARENT, DO NOT INSTALL UNIT
ON TO SITE WITHOUT PRIOR APPROVAL FROM ARMCOR.
• Check unit rating plate to ensure the correct unit
matches the job specications.
Unit Handling
• Protective crating or packaging and the pallets
should not be removed until the unit is at the point of
installation.
• When removing packaging or crating, be careful not
to damage, scratch or dent the unit.
• After removal of packaging, all removable access panels
should be opened to inspect for unit internal damage.
Lifting with a Crane
• SAFETY – when installing or working on equipment,
always adhere to safety codes and guidelines.
Wear safety goggles, work gloves, work boots and
protective clothing.
• All units should be lifted into position using SLINGS
and not CHAINS. (Chains may damage exterior nish
on the fan unit).
• Where units must be craned into position, installers
must check unit weight is within the safe tolerance of
the working capacity of the crane.
• Prepare for lifting with spreaders as you would do
with lifting air conditioning equipment.
• When lifting equipment never stand under the load.
• Beware of lifting equipment on to roof areas in windy
conditions. Only lift when weather conditions are
favourable.
Lifting with a Forklift
• Exercise extreme caution when lifting with a forklift.
Do not exceed the height limit of the forklift and
never allow the forklift forks to make contact directly
with the bottom panel of the unit.
• Make careful consideration of the unit’s centre
of gravity and distribute the weight equally
on both forks. Test load to see if the weight is
equally distributed. Do this by lifting the unit a
few centimetres off the ground level and checking
stability before lifting any further or before
transporting the unit.
Suspending the Unit
• Before suspending the unit, check the supporting
beams have sufcient load carrying capacity to
support the weight of the unit. Equipment is supplied
with brackets to support the unit.
• We recommend that all compact multiow units
be suspended or supported with suitable mounting
springs to eliminate the transmission of vibration.
• At each corner of the unit, there are 6mm bolts and
captive nuts. The bolt can be removed and a hanging
bracket attached to this xing point if required.
Hanging Bracket Fixing
• Remove 6mm corner bolt.
• Align bracket and re-t corner bolt.
• Secure with two additional self-drilling screws
through base
6 Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021

Equipment Connections
Ductwork
• Air distribution ductwork must be designed to allow
for the specied air ow without excessive pressure
levels. The unit should be situated as close as
possible to the point of use to prevent unnecessary
long runs of ductwork.
• Sheet metal ductwork is recommended for use with
all Armcor Air Solutions equipment.
• Ducts should be insulated in accordance with BCA
Section J-5.
• Fan inlet conditions can affect the fan performance,
particularly where duct bends cause a non-uniform
ow and swirl at the inlet. To reduce losses due
to fan systems effect, adequate length of straight
duct between any elbow and the fan inlet should be
provided or turning vanes used in the elbow.
• Poor fan outlet conditions will also affect the fan
performance. We recommend a minimum of 1000mm
of straight duct directly after the fan outlet.
Filters
• 50mm panel lters are a minimum recommendation
for all equipment.
• Filters must be tted to fresh air and/or return air.
• If the lters in the unit are not accessible for cleaning,
the installing contractor is responsible to incorporate
lters in the ductwork system external to the unit.
• It is recommended that temporary disposable lters
are used during construction and commissioning.
IMPORTANT: NEVER OPERATE A UNIT WITHOUT FILTERS
FITTED TO THE RETURN AND FRESH AIR INTAKES.
WARRANTY IS VOID IF THE FILTERS ARE NOT FITTED
AND REGULARLY CLEANED OR REPLACED.
Electrical Requirements
• The power requirement and voltage are detailed on
the equipment technical specications (available
on our website armcor.com.au) and are on the
identication/serial no. plate attached to each unit.
• An electrical diagram is attached to the electrical box
on the unit.
Mains Power Supply and Fusing
• A single-phase power supply rated at 240v (+/- 5%)
50Hz or a 3-phase power supply rated at 415 volts is
required to operate the unit within manufacturer’s
tolerance. Check the name plates for correct voltage.
• We recommend an isolator be mounted externally
to the unit (not supplied) and a suitably sized
circuit breaker mounted back at the distribution
board to provide local isolation during service and
maintenance periods.
• Main cables and control circuit wires are to be
connected as per wiring diagram.
• All wiring must comply with relevant local wiring
regulations.
• The units require a main circuit breaker or HRC fuse
capable of handling the full load of the unit and
selected in accordance with SAA Wiring Rules.
• All wiring is to be independently colour coded.
• Single phase fan motors are internally protected and
there is no need for external overloads.
Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021 7

Equipment Layout
The Armcor Compact Multiow ERV is designed to provide multiple options for duct connection and access
to fans/lters. Interchangeable panels can be removed and repositioned on-site to provide options for every
installation.
Return Air Air that is drawn from conditioned area.
Exhaust Air Ducted to outside the building or into the roof space if adequate ventilation is available.
Fresh Air Use a fresh air cowl or grill to introduce fresh air.
Supply Air Connect to the Airconditioning system or directly into the conditioned area.
XCM with EC Fans
XCM with Centrifugal Fans
INTERCHANGEABLE
DUCT & ACCESS PANELS
(ALL SIDES)
INTERCHANGEABLE
DUCT & ACCESS PANELS
(ALL SIDES)
8 Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021

ENERGY RECOVERY
Exhaust Air
Supply Air
Fresh Air
Return Air
ENERGY RECOVERY
Exhaust Air Fresh Air
Return Air
Supply Air
ENERGY RECOVERY
Exhaust Air
Supply Air
Fresh Air
Return Air
ENERGY RECOVERY
Exhaust Air
Fresh Air
Return Air
Supply Air
ENERGY RECOVERY
Exhaust Air
Fresh Air
Supply Air Return Air
ENERGY RECOVERY
Exhaust Air
Supply Air
Fresh Air
Return Air
ENERGY RECOVERY
Exhaust Air Fresh Air
Supply Air Return Air
ENERGY RECOVERY
Exhaust Air
Supply Air
Fresh Air
Return Air
OPTIONS FOR EVERY INSTALLATION
Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021 9

ENERGY RECOVERY
Exhaust Air
Supply Air
Fresh Air
Return Air
ENERGY RECOVERY
Exhaust Air Fresh Air
Supply Air Return Air
ENERGY RECOVERY
Exhaust Air
Supply Air
Fresh Air
Return Air
ENERGY RECOVERY
Exhaust Air
Fresh Air
Supply Air Return Air
ENERGY RECOVERY
Exhaust Air
Supply Air Return Air
Fresh Air
ENERGY RECOVERY
Exhaust Air
Return Air
Fresh Air
Supply Air
ENERGY RECOVERY
Exhaust Air
Supply Air Return Air
Fresh Air
ENERGY RECOVERY
Exhaust Air
Return Air
Fresh Air
Supply Air
10 Armcor_XCM–Compact Multiow ERV Installation and Operation Manual 2021