Model
Power supply Ph/V/Hz
Outdoor coil
Number of rows 2 2 2
Tube pitch(a)x row
pitch(b) mm 21*18.186 21*18.186 21*18.186
Fin spacing mm 1.40 1.40 1.40
Fin type (code) Corrugated
Fin Coating Type optional Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum
Salt Spray Test
Duration Hour 500 500 500
Tube outside dia.and
type
Internal thread copper
tube
Internal thread copper
tube
Internal thread copper
tube
mm
Coil length x height mm 1005*1302 1005*1302 1005*1302
Number of circuits 10 10 10
Cabinet
coating
Coating type Powder Coating Powder Coating Powder Coating
Salt Spray Test
Duration Hour 500 500 500
Sheet Metal Material Hot zinc plate Hot zinc plate Hot zinc plate
Sheet Metal
Thickness mm 0.8 0.8 0.8
Control panel enclosure IP class standard IP24 IP24 IP24
m3/h 7200 7200 7200
Outdoor sound level(sound pressure
level ) dB(A) 57 59
Outdoor sound level(sound power
level ) dB(A) 68 70
Outdoor unit
Dimension(W*D*H) mm 950/370/1340 950/370/1340 950/370/1340
Packing (W*D*H) mm 1023/471/1420 1023/471/1420 1023/471/1420
Net weight kg 115 115 115
Gross weight kg 123 123 123
Refrigerant Type R410A R410A R410A
Charged volume kg 4 4 4
Throttle type EXV EXV EXV
Design pressure MPa 4.15 4.15 4.15
Refrigerant
piping
Liquid pipe mm 9.52 9.52 9.52
Gas pipe mm 15.88 15.88 15.88
Total pipe lenth m 300 300 300
Max. pipe
length(Equivalent/
Actual)
m 150 150 150
Max.Diff. indoor/
outdoor unit m50 (Outdoor higher than indoor)
40 (Indoor higher than outdoor)
Max.Diff. indoor/
indoor unit m 15 15 15
Connectable indoor unit ratio % 50%~130% 50%~130% 50%~130%
Maximum indoor units Piece 8 13
Connection
wiring
Power wiring mm210 10
Signal wiring mm2Shield wire:(0.75-2)*2
Operation Range Cooling: -15~48
Heating: -20~27
Cooling: -15~48
Heating: -20~27
Cooling: -15~48
Heating: -20~27
Norminal condition: indoor temperature (cooling): 27 DB/19 WB, indoor temperature (heating): 20 DB/14.5
WB.
Outdoor temperature(cooling): 35 DB/24 WB, outdoor temperature(heating): 7 DB/6 WB The data is
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
AW-YEVFD125-H15 AW-YEVFD150-H15
59
70
10
4
AW-YEVFD150-H16
1/220~240/50/60 1/220~240/50/60
3/380~415/50/60