Zoning Zity Manuel



ZITY Advanced Installation Manual
WEE (RAEE)
This product may not be treated as household waste. Instead it shall be handed over to the applicable
collection point for the recycling of electrical and electronic equipment. For more detailed information
about recycling of this product, please contact your local city office or your household waste disposal
service.
NOTES ON RADIO TRANSMISSION
The control unit should preferably be located in a high place and away from metal masses and conductive elements.
The range between the thermostats and the control unit may be reduced if this is not the case.
Radio transmission does not take place on an exclusive frequency, so the possibility of interference cannot be
excluded. Frequency inhibitors and radio equipment operating in a permanent transmission mode in the same
frequency band (433 MHz) may impair the normal operation of the ZONING. The system is designed to work on two
different frequencies (433.92 and 434.33 MHz) to minimise this type of problem.
Connecting the system .......................................................... 4
Wiring diagrams .................................................................... 5
NTC probe functions ............................................................... 9
Control LEDs and output relays functions ............................ 10
System settings .................................................................... 11
Learning Mode ...................................................................... 14
Most common errors ........................................................... 15
ZOE-RC Thermostat advanced settings ............................... 17
ZEUS-RC Thermostat advanced settings ............................. 18
ZEBRA Thermostat advanced settings ................................. 19
SW1 central ZITY Advanced settings: ................................. 21
Technical characteristics ..................................................... 22
Warranty terms .................................................................... 23

1 Connecting the system
All system components are wired to the control unit or to its
expansion modules.
It is advisable to locate the equipment preferably in a high
place away from metal masses and conductive elements;
place the control unit in a protected place that can only be
accessed by authorized personnel and with appropriate
Tools for opening and subsequent handling of the equip-
ment in question.
Place at a height of approximately 1.5 m, avoiding di-
rect heat sources and unwanted air currents
Avoid to location the thermostats near metal masses and
conductive elements.
1. Supply voltage, (230VAC/ 50 Hz/
1)
2. 10kOhm NTC temperature sen-
sors (see location according to
type of machine)
3. 12 VDC output voltage for wired
thermostats
4. Control LEDs, to monitor the
status of the control unit
5. 433/434 MHz Radio
transmission antenna (only
in ZITY-RC control units)
6. Digital inputs, potential-free inputs
7. RS485 local communication
bus. For wired thermostats and
expansion modules.
8. RS485 local communication
bus, for communication with
equipment interfaces (connect
in parallel with the previous
bus)
9. RS485 remote communication
bus for home automation com-
munication/ BMS or NetBox
(MODBUS RTU-SLAVE protocol)
10. 24 VDC outputs for control of
motorised zone dampers (maximum
2 dampers per zone) (24Vdc –200
mA)
11. Control relays of the climate-control
equipment (see connection
depending on the type of equipment).
Maximum current 6A
12. Thermostats: Wired or via radio
Fig.1 Connecting all ZONING SYSTEM components in the ZITY control unit.

1.1-A Direct expansion system with via radio thermostats and NetBox gateway
1)
2)
3)

-Direct expansion system with wired thermostats and NetBox gateway.
-
1)
2)
3)

1.1-C Hydronic systems. Fancoil
For the connection of thermostats, motorized dampers and NetBox, Refer to diagrams above.
2– Pipe FANCOIL
Installation
Type Individual Collective Location
NTC 1 Optional*3 Optional*3 Battery inlet
pipe
NTC2 Remove
resistor Optional*3 Battery inlet
pipe
4– Pipe FANCOIL
Installation
Type Individual Collective Location
NTC 1 Optional*3 Optional*3 Heat battery
inlet pipe
NTC2 Optional*3 Optional*3 Cold battery
inlet pipe

1.1-D Radiant system
A Radiant heating installation (radiators or
radiant/ cooling floor) can be zoned.
The system manages the zone thermostatic
valves (ON/OFF) and the switching (ON/OFF)
of the production equipment.
The NTC probes (optional) are used as supply
temperatures protection. NTC1 for the pro-
duction equipment output and NTC2 for the
inlet temperatures to the radiant floor.
To activate in the ZITY the radiant protocol, the
switches must be positioned as follows:
1.1-E Direct Expansion/ Radiant combined hybrid systems
For the connection of thermostats, motorized dampers and NetBox, Refer to diagrams above.
For the connection of thermostats, motorized dampers and NetBox, Refer to diagrams above.

1.2 Power supply
1.3 NTC Probes
DIRECT EXPANSION 1x1 and VRF
Installation type With gateway No gateway Location
NTC 1 Do not connect Do not connect -
NTC2 Leave resistor (1) Advisable or leave resistor Air return
*1: Only install in FUJITSU– GENERAL machines with gateway. The other brands do not require a sensor.
Installation type Individual Collective Location
NTC 1 Optional (3) Optional (3) Battery inlet pipe
NTC2 Remove resistor (4) Optional (3) Battery inlet pipe
FANCOIL 4 PIPES
Installation type Individual Collective Location
NTC 1 Optional (3) Optional (3) Heat battery inlet pipe
NTC2 Optional (3) Optional (3) Cold battery inlet pipe
*3: For fancoil water input temperature protection.
*4: Remove the resistor if a Master thermostat is installed. When using auto-mode detection (no Master), remove the resistor and install the NTC2 sensor in the
water delivery pipe.
RADIANT SYSTEM
Installation type Heating, radiant or cooling floor Location
NTC 1 Optional (5) Boiler output pipe
NTC2 Superficie radiante
*5: For boiler delivery temperature protection.
*6: For input temperature protection in radiant/cooling floor
Optional (6)
-
-

1.4 Installations with more than 6 zones
In installations with more than 6 zones, 1 or 2
zone expansion modules will be connected. The
first expansion module controls zones 7 to 12. A
third module can be added, which will control
from zone 13 to zone 18. These modules
1.6 Control LEDs
The control unit has 2 rows of LEDs (red/green) that are used to monitor its status.
LEDs Colour Description
R1 to R7 Static red
Flashing red
Static red: The associated relay is active (see paragraph 2.11 relays)
Flashing red: Error or learning mode (see error list)
Z1 to Z6
Static red
Static green
Flashing red
Static red: Damper closed
Static green: Damper open
Flashing red: Zone communication error
Tx Random flashing red Flashes every time radio communication arrives
1.7 Control relays
The control unit has 7 control relays. The function of each relay depends on the protocol
chosen in Sw1.
Protocol R1 R2 R3 R4 R5 R6 R7
Direct expansion On/OFF
4 Pipe Fancoil Cold valve Heat valve ON / OFF OFF=Heat
ON= Cool Speed 1 Speed 2 Speed 3
Radiant Zona 1
valve
Zona 2
valve
Zona 3
valve
Zona 4
valve
Zona 5
valve
Zona 6
valve
Boiler
ON/OFF
2 Pipe Fancoil Valve Valve (1) ON / OFF OFF=Heat
ON= Cool Speed 1 Speed 2 Speed 3
1.5 Connecting the motorized dampers. Parallel connection.
Connect the motors of each regulator to wire clamps 1 to 6 on the board (10). Use a red (+) / black (-) wire with a section of be-
tween 0.75 mm2 and 1.0 mm2. If there are two regulators per zone (maximum recommended), connect them in parallel