Vacon NX OPTC2 Manuel utilisateur

vacon nx
ac drives
optc2/c8
modbus/n2 option board
user manual

INDEX Document code: DPD00899A
Date 19.01.2012
1. GENERAL ...........................................................................................................................3
2. RS-485 OPTION BOARD TECHNICAL DATA ........................................................................ 4
2.1 General ......................................................................................................................................... 4
3. RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS...................................................5
3.1 RS-485 OPTC2 option board ......................................................................................................... 5
3.2 RS-485 OPTC8 option board ......................................................................................................... 6
3.3 Grounding ..................................................................................................................................... 7
3.3.1 Grounding by clamping the cable to the converter frame.................................................7
3.3.2 Grounding only one point on the net..................................................................................9
3.3.3 Grounding jumper X1.......................................................................................................10
3.4 Bus terminal resistors................................................................................................................ 11
3.5 Bus Biasing................................................................................................................................. 12
3.6 LED indications........................................................................................................................... 13
4. INSTALLATION OF VACON NX RS-485 BOARD ................................................................. 14
5. COMMISSIONING.............................................................................................................. 16
5.1 Fieldbus board parameters........................................................................................................ 16
6. MODBUS........................................................................................................................... 19
6.1 Modbus RTU protocol, introduction............................................................................................ 19
6.1.1 Supported functions.........................................................................................................21
6.1.2 Exception responses........................................................................................................23
6.2 Modbus interface........................................................................................................................ 25
6.2.1 Modbus registers.............................................................................................................25
6.2.2 Process data ....................................................................................................................25
6.2.3 Process data in ................................................................................................................26
6.2.4 Process data out ..............................................................................................................27
6.2.5 Parameters......................................................................................................................30
6.2.6 Actual values....................................................................................................................30
6.2.7 Example messages..........................................................................................................31
6.3 Start-up test ............................................................................................................................... 33
7. METASYS N2..................................................................................................................... 34
7.1 Metasys N2 Protocol Introduction.............................................................................................. 34
7.2 Metasys N2 interface.................................................................................................................. 34
7.2.1 Analogue Input (AI) ..........................................................................................................34
7.2.2 Binary Input (BI)...............................................................................................................34
7.2.3 Analogue Output (AO).......................................................................................................35
7.2.4 Binary Output (BO)...........................................................................................................35
7.2.5 Internal Integer (ADI).......................................................................................................35
7.3 N2 POINT MAP............................................................................................................................ 36
7.3.1 Analogue Inputs (AI).........................................................................................................36
7.3.2 Binary Inputs (BI) .............................................................................................................37
7.3.3 Analogue Outputs (AO).....................................................................................................37
7.3.4 Binary Outputs (BO) .........................................................................................................38
7.3.5 Internal Integers (ADI) .....................................................................................................38
8. FAULT TRACKING............................................................................................................. 39
APPENDIX 1............................................................................................................................................ 40

general vacon •3
24-hour support +358 (0)40 8371 150 • Email: [email protected]
1
1. GENERAL
Instead of sending and receiving information to and from frequency converters through I/O, you can
connect them to a fieldbus.
Vacon NX frequency converters can be connected to the RS-485 bus using a fieldbus board. The con-
verter can then be controlled, monitored and programmed from the host system.
If you purchase your RS-485 Option Board separately, please note that it shall be installed in slot E on
the control board of the frequency converter.
WARNING!
Internal components and circuit boards are at high potential when the frequency
converter is connected to the power source. This voltage is extremely dangerous
and may cause death or severe injury if you come into contact with it.

4 • vacon technical data
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
2
2. RS-485 OPTION BOARD TECHNICAL DATA
2.1 General
Connections
Interface
OPTC2
: Pluggable connector (5.08mm)
OPTC8
: 9-pin DSUB connector (female)
Data transfer
method
RS-485, half-duplex
Transfer cable Twisted pair (1 pair and shield)
Electrical isolation 500 VDC
Communications
Modbus RTU
Metasys N2
As described in document “Modicon Modbus Protocol
Reference Guide”
Find it for example at: http://public.modicon.com/
As described in Metasys N2 System Protocol Specifica-
tion
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200 and 38400 kbaud
Addresses 1 to 247
Environment
Ambient operating
temperature
–10°C…55°C
Storing tempera-
ture
–40°C…60°C
Humidity <95%, no condensation allowed
Altitude Max. 1000 m
Vibration 0.5 G at 9…200 Hz
Safety
Fulfils EN50178 standard
Table 1. RS-485 technical data