TTK FG-NET Manuel utilisateur

1 Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
OPERATION &INSTALLATION MANUAL
DIGITAL UNIT:
FG-NET

2
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
CONTENT
DESCRIPTION 4
CERTIFICATIONS 5
CHAPTER I: FG-NET DIGITAL UNIT INSTALLATION 7
1. MOUNTING THE FG-NET DIGITAL UNIT: E AND F 7
2. ELECTRICAL CHARACTERISTICS 8
3. ELECTRICAL CONNECTION OF THE FG-NET DIGITAL UNIT 10
3.1. Connecting the FG-NET Digital Unit to the earth 10
3.2. Connecting the power supply cable 11
3.3. Connecting the leader cable FG-CLC 13
3.4. Connecting the internal relays 14
3.5. Connecting the serial cable 15
3.6. Closing the FG-NET F Digital Unit 15
CHAPTER II: CABLE AND ACCESSORIES INSTALLATION 16
1. INSTALLING ADDRESSABLE SENSE CABLES 16
1.1. Hold-down adhesive clips 16
1.2. Installing sense cables: FG-EC, FG-AC and FG-ECX 17
1.3. Installing hydrocarbon and solvent sense cables: FG-OD 17
1.4. Labelling with tags 19
2. INSTALLING FG-NC JUMPER CABLES 20
3. INSTALLING CONNECTION ACCESSORIES 26
3.1. FG-DTCS - Addressable Box 26
3.2. FG-DCTL –“Cut-to-Length” Addressable Box 27
3.3. FG-DTC - TTK Bus Diversion 28
3.4. FG-DOD - OD Bus Interface 29
3.5. Installing end termination plugs 30
CHAPTER III: DIGITAL UNIT STARTUP 31
1. FG-NET DIGITAL UNIT –POWERING ON 31
2. MENUS 32
2.1. Setup 32
2.2. Events log 45

3
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
2.3. Cables 47
2.4. Help 56
2.5. SD Card 59
3. WATCHDOG 62
4. COMMUNICATION SETUP 63
4.1. General 63
4.2. Schematics 64
4.3. Modbus communication 66
4.4. TOPSurveillance™ Software 69
CHAPTER IV: EXTERNAL DEVICES 72
1. FG-RELAYS 72
2. FG-BBOX 74
CHAPTER V: TEST PROCEDURES 78
1. LEAK TESTS 78
2. CABLE BREAK TESTS 81
3. FG-NET MAP 82
CHAPTER VI: MAINTENANCE –FAULT FINDING 84
1. CHECKING THE SYSTEM 84
2. SYSTEM MAINTENANCE 84
2.1. Replacing a sense cable 84
2.2. Precautions for use and storage 85
2.3. Adding sense cables to an existing circuit 85
2.4. Addition of a New Circuit of Sense Cables (Circuits no.2 and/or no.3) 86
2.5. Removal of the system 86
3. TROUBLE SHOOTING GUIDE 87
Appendix 91
1. Digital Unit connection diagram and ratings: FG-NET E / F 91
2. Modbus Table 92
3. Commissioning guide 93

4
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
DESCRIPTION
The FG-NET Digital system ensures an immediate detection and the precise location of any liquid leaks
(water, acids, bases, solvents, hydrocarbons) in both industrial applications and buildings.
The FG-NET system is composed of an FG-NET Digital Unit, plus lengths of sense cables and accessories.
The FG-NET Digital Unit is designed to be used with TTK digital sense cables FG-EC (water and bases), FG-
AC (acids), or FG-OD (hydrocarbons and solvents). Different types of sense cables can be connected on
the same unit.
The presence of liquid on the sense cable triggers an audible alarm and activates the relevant relays. The
7’(175mm) touch screen display shows the location of the leak to the nearest metre and details of the
fault in text format; an interactive installation plan (optional) highlights the location of the fault in real
time.
Each sense cable comes equipped with a microchip at the female connector end. The Digital Unit
questions each cable successively; the microchip then digitally transmits the ‘state’of the cable to the
Digital Unit. Due to the autonomy of each cable, several faults can be detected at the same time within
the same circuit.
A Digital Unit can manage three circuits of sense cables; each one of these circuits has a maximum
capacity of 40 sense cables (15 metres I total), or 120 lengths of sense cable, that is 1,800 metres
maximum for an FG-NET unit. In addition to the presence of liquid, the system detects and locates any
faults in cable breaks within the circuit.
The FG-NET Digital Unit is available in a rack-mounted (19’and 4U in height) version (FG-NET E), or a wall
mounted version (FG-NET F).
The touch-screen on the front face makes the setup of the system easy: For example, you can nominate
the zones for detection (by assigning a name to each sense cable), choose and configure the set-up
(relays, serial links), set the system parameters (language, time adjustment, date, user access levels, relay
setup, serial link connection, etc.).
The system's reaction time to faults on each sense cable is adjustable. It is possible to remotely isolate a
sense cable for up to 72 hours. The Digital Unit can store up to 5000 events in the event log.
In order to explore the fault, three types of interface with a centralized technical management system are
available: TCP/IP connection via an Ethernet port; JBUS/MODBUS protocol (Serial links - RS232,
RS422/485 output) and nine relays: eight of which are fully configurable and one to interrupt the power
supply.
This document is available on our web sites: www.ttkuk.com; www.ttk.fr; www.ttkasia.com; www.ttkaustralia.com;
www.ttk.sg.
The information contained in this document is subject to modifications without notice. This information and diagrams have been drawn up carefully, however
TTK UK Ltd., TTK Asia Ltd. or TTK S.A.S. cannot guarantee that the information provided does not contain any errors or omissions, and cannot accept any
comparative responsibility for which the information is used. No part of this guide can be reproduced or transmitted without the express and written
permission of the TTK UK Ltd., TTK Asia Ltd. or TTK S.A.S.
FG-NET and TOPSurveillance® are trademarks of TTK S.A.S.

5
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
CERTIFICATIONS
Electromagnetic compatibility E.M.C.
FG-NET E and FG-NET F fully conform to the requirements of generic harmonized European
standards:
EN 61000-6-3:2007 for emissions
EN 61000-6-2:2005 for immunity
ATEX Certification
FG-ECS, FG-ACS and FG-OD can be used in explosive atmospheres when connected to the FG-NET panel.
-30°C < T < +100°C
Equipment intended for use in explosive atmospheres, according to Directive 94/9/EC
Certification number: LCIE 05 ATEX 6065 X
International safety requirements
FG-NET E and FG-NET F are currently undergoing testing in order to conform to German and
American safety requirements.
IEC 61010-1:2010

6
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
Conditions of Use
FG-NET shall be installed indoor only in environments meeting the Rated Pollution Degree 2 or better
according to IEC 61010-1: Edition 3.
This panel contains soldered, non-replaceable and not-serviceable lithium battery. Please
dispose properly after removal, refer to the applicable laws in the country of installation and use!
Symbols used in this document and on FG-NET panel
Direct current
Alternating current
Protective conductor terminal
Caution, risk of electric shock
Caution, risk of danger: please consult the current
document where this symbol is marked on the panel
L
Live
N
Neutral

7
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
CHAPTER I: FG-NET DIGITAL UNIT INSTALLATION
1. MOUNTING THE FG-NET DIGITAL UNIT: E AND F
The FG-NET E Digital Unit is available in a rack mounted version (in a bay or a 19’casing).
It is advised to choose a location at eye-height level in order to facilitate reading the display.
The dimensions are as follows:
Width: 483 mm
Height: 177 mm
Depth: 74 mm
Weight: 3 kg
FG-NET (E) Rack mounted version
FG-NET F Digital Unit is also available in a wall-mounted version.
The dimensions are as follows:
Width: 228 mm
Height: 303 mm
Depth: 67 mm
Weight: 2.3 kg
FG-NET (F) Wall-mounted version

8
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
Open the cover of the wall-mounted Digital Unit in order to reach the motherboard which is fixed to
the interior of the casing (as shown below):
PLEASE DISCONNECT POWER PRIOR TO MOUNTING, OPENNING OR CONNECTING THE
PANEL TO ANY ELECTRIC CABLE.
2. ELECTRICAL CHARACTERISTICS
- Power Supply: 100-240V , 50/60Hz (1).
- Power Consumption: 36 VA Max.
- Input Current Rating: 1.3 A
- Overvoltage Category: Class II
- Temperature Range: 0 –40 °C
- Relative Humidity: 80% Max (2).
- Altitude Max.: 2000 m
- Ingress Protection Rating: IP40/NEMA1 –Indoor Use Only
- Sound level: Max. 70 dB @ 30 cm (buzzer annunciating an alarm)
(1) Mains supply voltage fluctuations not to exceed ± 10 percent of nominal voltage
(2) Maximum relative humidity 80 percent for temperatures up to 31°C decreasing linearly to 50
percent relative humidity at 40°C
A readily accessible disconnect device (of Live or Live + Neutral wires) shall be
incorporated external to the equipment in the electrical cabinet powering the panel. The
disconnect device shall meet the requirement of the relevant to the country of equipment
installation standard. The nominal rating of the disconnect device is 2 A.

9
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
Dry contacts Characteristics:
Type: 1 RT
Max. switching voltage: 125 V / 60 V
Max. switching current: 2 A
Max. switching power: 62,5 VA / 60 W
Working load min.: 5 V - 1 mA
Nominal load: 0,5 A at 125 V
2 A at 30 V
Please note embedded relays are signal relays used for interfacing to BMS and other
low-current signaling purposes. Do not use the dry contacts for direct connection to power
loads as solenoid valves, etc.
Sensing Cables Outputs:
- Rating: 12 V
- Nominal Voltages on the sense cable circuit (all voltages referred to Ground):
- 1A, 2A, 3A, 1B, 2B, 3B: 5 V
- 1D, 2D, 3D: 12 V
- 1C, 2C, 3C: 0 V (electrically connected to Ground)
Please use only FG-EC, FG-AC sensing cables supplied by TTK or authorized distributors!

10
Sep 2018 –Version 3.1.5
FG-NET_Operation & Installation Manual_UK_v3.1.5_201809.docx
3. ELECTRICAL CONNECTION OF THE FG-NET DIGITAL UNIT
All connections are made on the Digital Unit’s motherboard. The connector blocks are directly
accessible and removable on the FG-NETF E; for the FG-NET F however (the metal wall mounted
version), it is necessary to remove the three screws on the lower section to open the front panel.
See Appendix no.1: ‘FG-NET E / F Digital Unit Connection’at the end of this guide.
3.1. Connecting the FG-NET Digital Unit to the earth
Respect the rules for Electromagnetic Compliance and Electrical Safety:
It is absolutely necessary to connect the Protective Ground (PE) to the AC Power terminal connector!
The use of the cable tie to hold together the three wires of the power supply is compulsory!
Autres manuels pour FG-NET
4
Table des matières
Manuels Intervenants populaires d'autres marques

Bowers & Wilkins
Bowers & Wilkins 4 Manuel utilisateur

Sonance
Sonance SONOS OUTDOOR Series Manuel utilisateur

Electro-Voice
Electro-Voice EVID FM4.2 Manuel utilisateur

Pioneer
Pioneer XW-HTD630 Manuel utilisateur

Onn
Onn BWA16AA002 Manuel utilisateur

HP
HP GL313AA - USB Speakers PC Multimedia Manuel utilisateur