Calibration
•If using Modbus sensor then the Wind speed Sensor is factory calibrated.
•If using analog output senor then use the following info to calibrate:
oOutput: 0 ‐ 5 VDC (0 to 250 km/hr)
oWind Speed in km/hr = 50*Sensor Output voltage (in Volt)
oOutput: 4‐20mA (0 to 250 km/hr)
oWind Speed in km/hr = 15.625*(Output in mA ‐ 4)
If the cable length is insufficient for the installation, additional cable can be added to the existing cable. If this is done, an
accuracy de‐rating factor must be added to the overall wind speed accuracy of this sensor.
It is highly recommended that the calibration be checked annually
Logger Connections
•For ANALOG output connections (Voltage or Current) , please search for ‘Installation Guide – Analog
Sensors’ on: https://trackso.in/trackso‐installation‐manuals/
•For MODBUS output connections, please search for ‘Installation Guide – MODBUS Sensors’ on:
https://trackso.in/trackso‐installation‐manuals/
Sensor Maintenance
•Maintenance includes inspection of mechanical operation and cleaning.
•Rotate wind cup assembly; look for smooth rotation and a gradual stop. If the cup wheel or the vane is not
rotating smoothly or it creates detectable noise, the bearings must be replaced
•Inspect mounting hardware for secure fasteners; mounting pipe must be vertical.
•Replace any loose or corroded fasteners.
•Inspect the cable and connections.
•It is recommended to check the ball bearings of the anemometer every year. If the cup wheel is not rotating
smoothly or it creates detectable noise, the bearings/sensors must be replaced.
•Clean any accumulation of dirt, dust, or bird droppings that may affect proper rotation of the wind speed sensor.
Use only soapy water and a soft cloth. Never use solvents or abrasive cleansers. Do not immerse the
anemometer in water.