Tescom i-com Series Manuel utilisateur

- 1 -
i-com SERIES EXTERNAL
UPS – MODBUS (TCP/IP)
COMMUNICATION ADAPTER
(MDX-NET)
INSTALLATION AND USER MANUAL


Thank you for selecting our product to protect your electrical equipment.
The Modbus adaptor has been designed with the utmost care. We recommend that you take the time to read this
manual to take full advantage of the many features of your new equipment.
Environment
Our staff pays great attention to the environmental impact of its products during the design and manufacture
stages, through to the end of its life cycle.
This product complies with the most strict regulations.
It does not contain CFCs or HCFCs
Recycling of packing materials
Packing materials were selected to facilitate recycling. Please make sure they are correctly recycled in
compliance with all applicable regulations.
Special precautions
If the adaptor must be stored prior to installation, storage must be in a dry place
The admissible storage temperature range is -10 C to +70 C.
CONTENTS
1. Introduction ..................................................................................................... 1
1.1 Unpacking and Checking Contents ........................................................... 1
1.2 Overview .................................................................................................. 1
1.3 Functions .................................................................................................. 1
1.4 Technical Specifications ........................................................................... 1
2. Installation ....................................................................................................... 2
2.1 Configuration Of The Modbus Communication Parameters ...................... 2
2.2 RS232 Connection to UPS ....................................................................... 3
2.3 MDX-NET Network Connection ................................................................ 3
2.4 Installation ................................................................................................ 4
2.5 MDX-NET Configuration using Device Installer……………………………..4
3. Operation ........................................................................................................ 8
4. Indicator Lamb………………………………………………………………………...8
TX300 Protocol HOLDING REGISTER Table (3 Phase UPS) ......................... 9
TX301 Protocol HOLDING REGISTER Table (3 Phase UPS) ......................... 11
TX100 Protocol HOLDING REGISTER Table (3 Phase UPS) ......................... 15
STS Protocol HOLDING REGISTER Table (Static transfer switch)……….…...17

- 1 -

- 1 -
1. Introduction
1.1 Unpacking and Checking Contents
EXTERNAL MODBUS ADAPTOR
5 volts DC power supply
RS232 UPS-ADAPTOR cable (CC05)
Utility CD
Installation and user manual
1.2 Overview
1.3 Functions
The MODBUS TCPIP communication adaptor provides UPS (Uninterruptible Power supply) data (states and
measures) to be sent a computer system.
The system provides a communication channel between ethernet(PC side) and RS232(UPS side) interface.
1.4 Technical Specifications
Function
Parameter
Value
RS232 Baud rate 2400 bauds
RS232 Parity No parity
RS232 Stop bit 1 stop bit
RS232 UPS Connection RX,TX,Gnd (3 wire)
Ethernet Interface 10Base-T or 100Base-TX (Auto-Sensing)
Ethernet Connector RJ45
Ethernet Protocols TCP/IP, UDP/IP,ARP, ICMP,SNMP,TFTP,Telnet,DHCP, BOOTP, HTTP,AutoIP

- 2 -
2. Installation
2.1 Configuration Of The Modbus Communication Parameters
The device takes the device number during power on please select device number from 1 to 255 by setting
device number dip switches
Where Dn is the nth dip switch. For example, if we need to set the device’s address to 183 then we need
to set 7th, 5th, 4th, 2nd, 1st, and 0th dip switch pins. The address is calculated using above equation as
follows:

- 3 -
2.2 RS232 Connection to UPS
Connect CC05 RS232 cable from serial port connector of the MODBUS adapter to the serial port of the
UPS.
CC05 RS232 Data Cable
Max. Length = 25 meters.
parts
pcs
9 pins D type connector (male) 1
9 pins D type connector(female) 1
3 wired shielded cable Max 25 meters
2.3 MDX-NET Network connection
UPS
connector
Pin Nr
PC port
Pin Nr
6 3
7 5
9 2
MODBUS
Adaptor serial port
9 pins D type male
9 pins D type female
4
3
5
2
1
8
7
6 9
4
1
8
7
6
2
9
5 3
UPS
Com port

- 4 -
2.4 Installation
Check RS232 UPS connection ,check ethernet connection if connections are OKAY
Connect the power cord of the MODBUS TCPIP adapter to mains power (The power of the adapter
must be supplied from UPS output otherwise during line failure the power of the MODBUS adapter
shutdown)
2.5 MDX-NET Configuration using Device Installer
Run device installer software. (Start-Programs-Lantronix Device Installer)
This utility program finds all network connected MDX-NET adaptor devices.
If it fails please change your network settings (IP address and subnet mask) as static IP to the following values
İt is only for adjustment purpose after you adjust adaptor you can return to your old network settings.
X-Port factory settings:
IP: 10.0.0.xxx
Subnet Mask: 255.0.0.0
Gateway : 0.0.0.0
If the MDX-NET adaptor device is showned on the list double click on it and device details will be showned at the
window. Select the related MD-NET device and click on *Assign IP* button for adjusting the adaptor to your
network settings.

- 5 -
At “Assign IP” window select *Static IP* option from configuration window and click on *NEXT* button.
NOTE : The new IP address is different from 10.0.0.xxx or subnet mask is different from 255.0.0.0 value the
adaptor connection may be lost in this case please re adjust your PC network settings to these network values.

- 6 -
After adjust MDX-NET IP addresses the new assigned IP address will be showned at device installer program
window.
For detailed configuration we must connect to adaptor as WEB page to do this from device installer program click
on WEB configuration. Than click on *GO* button and device main WEB PAGE comes to screen. Ignore
username and password values for the first time.
Autres manuels pour i-com Series
3
Ce manuel convient aux modèles suivants
1
Table des matières
Autres manuels Tescom Adaptateur