REQUIREMENTS USING TENDERFLAME DL 180 FOR BUILT-IN FIREPLACE
Materials used in areas becoming hot - must be non-combustIble materials. Plasterboards will not bee good enough in this
context.
Recommended materials are e.g. skamol boards, stone slabs, steel/metal, firewall slabs.
We recommend using the steel box provided with the burner. Alternatively the burner can hang on the top plate. If so be
aware of any fuel spills when filling the burner. The materials around the burner must be none-combustible materials.
Burner in the included steel case can be placed in a recess area. This area must be made from non-combustible materials
as the steel box can get hot.
The steel case will get hot on the top and on the top half of the steel box. If the box will be built into wooden boards or
other combustible materials there must be a gap of minimum 3 mm on all sides of the steel box.
If alight opening is to be made (framing the side and above the burner), there must be 40 cm up the ceiling in the light
opening. Walls and ceiling inside the light opening must be made in non-combustible material.
If the burner is placed in areas with non-combustible above the burner, there must be a clearance of 150 cm above the
burner.
There should be no loose fabrics, such as curtains, closer than 1 meter from the burner.