Specifications
Method
Dual Beam Absorption Infrared
Diffusion sample method
Performance
Measurement Range
0-2000 ppm factory default
Adjustable to 10,000 ppm with UIP
Software
Accuracy
@60-90°F (15-32°C)
±50 ppm or 5% whichever is greater
(7% for levels over 1500 ppm)
@32-122°F (0-50°C)
±100 ppm or 7% whichever is greater
Elevation (Pressure) Correction
Add 0.13% of reading per mm Hg
decrease from 760 mm Hg (On-board
correction, user set with UIP
software), preset at sea level
Response Time 0-90%
<1 minute
Warm-Up Time @ 25oC
<2 minutes
Operating Conditions
0 – 50oC (32-120oF)
0 – 95% RH, non-condensing
Storage Temperature
-40 – 70oC
Agency Certification
FCC Part 15 Class B / CE
Plastic Case - UL94-5V Rated
Input/Output
Power
18-30 VAC RMS, 50/60 Hz -half-wave
rectified
18-42 VDC polarity protected
1.75 VA maximum average power
2.75 VA peak power
Analog Output
0-10 VDC (100 Ohms output
impedance)
4-20 mA (RLmax = 500 Ohms)
Both outputs available simultaneously
Relay Output
Normally Open and Normally Closed
(wire either way), gold bifurcated, 2A
max. @ 24VAC. Adjustable setpoint
(with UIP software kit), factory set at
1000 ppm, 50 ppm hysteresis
Wiring
18-28 AWG stranded copper wire
only. 2 wires each for power, analog
output, relay
Digital I/O
RS-232 interface for use with optional
PC software and cable in UIP kit
2072
Warranty/Other
Warranty
18 months parts and labor
Calibration
5-year calibration guarantee
Adjusting Sensor (Display Units Only)
Button Features [CLEAR] - Resets Menu
- Returns to Normal Mode
[MODE] - Toggles to Next Menu Item
[ENTER] - Press to Lock Menu
[UP/DOWN] - Increase/Decrease Selection Value
Altitude Correction and ABC LogicTM (On/Off):
1. After 2 minute warm-up period, press [CLEAR] + [MODE] and hold (at least
5 seconds) until the sensor enters the edit mode.
2. The first menu will be the Altitude correction. The adjustments will increase/
decrease in 500 ft. increments. To do this use the UP/DOWN Rocker Button
to adjust to the proper altitude.
3. Press ENTER to lock in value then press MODE to proceed to ABC LogicTM.
4. Use the UP/DOWN Rocker Button to switch to ON or OFF.
5. Press ENTER to lock in value then press MODE to proceed to Normal Mode.
Note: It is recommended that the ABC LogicTM feature be left ON for the best
sensor operation.
Selecting a Pre-Programmed Setting:
The pre-programmed settings shown in Table 3 are factory set and cannot be
changed. These settings can be selected from the Standard Settings
(STDSET) menu. The Altitude and ABC Logic™ features can be changed
without entering the Standard Settings (STDSET) menu.
1. After 2 minute warm-up period, press CLEAR + MODE and hold (at least 5
seconds) until the sensor enters the edit mode.
2. Press MODE 2 times. You will enter the STDSET menu.
3. Use the UP/DOWN Rocker Button to select the desired pre-programmed
number. Refer to “Configuring the Sensor” for the appropriate setting number.
4. Press ENTER to lock in selection then press MODE to return to Normal Mode.
For Non-Standard (Custom) Settings:
The non-standard (custom) settings can be changed at any time after the
sensor is powered up. The 7 variables are: PPM Range, Scale (proportional or
exponential), Output (V or mA), Output Range V, Output Range mA, Relay
Setpoint, and Relay Hysterisis. The Altitude and ABC Logic™ features can be
changed without entering into the Non-Standard (NONSTD) menu.
1. After 2 minute warm-up period, press [CLEAR] + [MODE] and hold (at least
5 seconds) until the sensor enters the edit mode.
2. Press [MODE] 2 times. You will enter the STDSET menu.
3. Use the [UP/DOWN] Rocker Button to toggle to the NONSTD menu.
4. Press [MODE] to move through the variables. Use the [UP/DOWN] button
to toggle to desired setting.
5. Press [ENTER] to lock in the selection then press [MODE] to continue to
the next variable.
Dual Channel CO2Ventilation Controller
Ventostat®8000 Series
Warranty
6860 Cortona Drive, Suite B - Goleta, California 93117
P- 805-685-4000 F- 805-685-0015 www.telaire.com
Telaire seeks to present reliable information concerning the composition, properties and use of its
products, however; (1)All advice concerning selection and use of any product is provided at no
charge and with no warranty. (2) No warranty is made hereby. Products described herein are
warranted to conform to Telaire specifications only at the time of sale. All sales are subject to
Telaire standard terms and conditions, which are reproduced on the reverse side of each invoice.
All warranties of merchantability and fitness of purpose are disclaimed and remedy for any breach
of warranty is limited to replacement of the defective product. (3) Telaire assumes no responsibil-
ity for any patent liability arising from the use of any product in a process, manner or formula not
designed by Telaire. ©Copyright 1999-2004
62332-007 09/08/2004
6860 Cortona Drive, Suite B - Goleta, California, 93117
P- 805-685-4000 F- 805-685-0015
NOTICE!
Use of cellular telephones or radio transceivers within two (2) feet of the
sensor during calibration process could cause sensor interference, calibration
errors and affect sensor accuracy. Please refrain from using these devices
during sensor calibration.