DIAGNOSTIC INDICATOR TABLE
RUN LIGHT CAL. LIGHT PROBLEM or FUNCTION CORRECTIVE ACTION
On Steady Off RUN:
Pump is running—or ready to run—
no problems in operation None
On Steady On Steady CAL:
The PumpSaver®Plus is in the
calibration process. None
Off On Steady
CAL COMPLETE:
The PumpSaver®Plus is calibrated,
the RESTART DELAY/
CALIBRATION knob was left in the
CAL. position. Pump is off.
Pump will restart as soon as
the RESTART DELAY/
CALIBRATION knob is rotated
out of the CAL. position.
Off Off
OFF / MANUAL RESTART:
The pump is not running. Either the
PumpSaver®Plus has tripped on
dry-run, dead-head, or overcurrent
while the RESTART DELAY/
CALIBRATION knob was in the
RESET position or source power is
not present.
If knob is in the RESET
position, rotate out of RESET—
If the CAL. light blinks, check
for an overcurrent condition. If
the RUN light blinks, look for a
dry-run or dead-head condition.
If no lights come on, check
incoming power for adequate
voltage.
Blinking Off
DRY RUN / DEAD HEAD:
The PumpSaver®Plus has shut the
pump off due to a dry-run or dead-
head condition. The unit is timing
through the restart delay and will
try to restart.
Check for restricted flow or
inadequate supply of liquid.
Off Blinking
OVERCURRENT:
The PumpSaver®Plus has shut the
pump off due to an overcurrent
condition. The unit is timing
through the restart delay and will
try to restart if line voltage is at an
acceptable level.
Check for low or high voltage
or jammed pump impellers. If
these conditions do not exist,
recalibrate the unit while it is
drawing higher current (amps
should not exceed SFA).
Blinking
alternately
with the
CAL. LIGHT
Blinking
alternately
with the
RUN LIGHT
VOLTAGE FAULT:
The PumpSaver®Plus is preventing
the pump from starting due to
voltage problems. The voltage is
being interrogated and the unit will
remain in this mode until the
voltage is at an acceptable level.
If the unit remains in this state
for more than 5 seconds, check
for high or low voltage.
Blinking in
unison with
the CAL.
LIGHT
Blinking in
unison with
the RUN
LIGHT
RAPID CYCLE:
The PumpSaver®Plus has shut
down on rapid cycling. Power must
be removed and reapplied to reset
the unit.
Check for a broken bladder in
the pressure tank (if used), or
check for a defective pressure
or float switch.