1.4 System box information
There is a DC breaker between battery and inverter and can
cover all the cables as you can see, It will save your room space and
much more beautiful without jumbled wiring.
2 Installation
2.1 Installation site and environment
2.1.1 General
This E-home energy storage system is an indoor
location.
When E-home systems are installed in a room, it must not be hampered by the
structure of the building, the furnishings and equipment of the room.
The E-home system is naturally ventilated. The location should therefore be clean,
dry and adequately ventilated. The mounting location must allow free access to the
unit for installation and maintenance purposes, and the system panels must not be
blocked.
The following location are not allowed for installation:
• abitable rooms;
•eiling cavities or wall cavities;
•n roofs that are not specifically considered suitable;
•ccess/ exit areas or under stairs/ access walkways;
•here the freezing point can be reached, such as garages,
carports or other places as well as wet rooms(environmental category 2);
•ocations with humidity and condensation over 85%;
•laces where salty and humid air can penetrate;
•eismic areas- additional security measures are required;
•ites higher than 2000 meters above sea level;
•laces with an explosive atmosphere;
•ocations with direct sunlight or a large change in the ambient temperature;
•laces with flammable materials or gases or an explosive atmosphere.
2.1.2 Restricted Locations
The E-home shall not be installed—
n restricted locations as defined for panels in AS/ NZS 3000;
ithin 600 mm of any heat source, such as hot water unit, gas heater,
air conditioning unit or any other appliance .
ithin 600 mm of any exit;
ithin 600 mm of any window or ventilation opening;
ithin 900 mm of access to 240Vac connections;
within 600 mm of side of other device.
A E-home installed in any corridor, hallway, lobby or the like and leading to an
emergency exit shall ensure sufficient clearance for safe egress of at least 1 meter.
The E-home must also not be installed in potentially explosive at mospheres for gas
cylinders that are heavier than air gases and have a vent clamp in 3.4.3
To protect against the spread of fire in living spaces where the E-home is mounted or
on surfaces of a wall or structure in living spaces with a E-home on the other side,the
wall or structure shall have a suitable non-combustible barrier. If the mounting surface
itself is not made of a suitable non-combustible material, a non-combustible barrier can
be placed between the E-home and the surface of a wall or structure.