Transmitter Supply Unit with Limit Values
Series 9162
Contents
1 General Information ............................................................................................3
1.1 Manufacturer .......................................................................................................3
1.2 Information about the Manual .............................................................................3
1.3 Further Documents .............................................................................................3
1.4 Conformity with Standards and Regulations .......................................................3
2 Explanation of the Symbols ................................................................................4
2.1 Symbols used in this Manual ..............................................................................4
2.2 Warning Notes ....................................................................................................4
2.3 Symbols on the Device .......................................................................................5
3 Safety Notes .......................................................................................................5
3.1 Storage of the Manual .........................................................................................5
3.2 Personnel Qualification .......................................................................................5
3.3 Safe Use .............................................................................................................6
3.4 Modifications and Alterations ..............................................................................7
4 Function and Device Design ...............................................................................7
4.1 Function ..............................................................................................................7
4.2 Device Design .....................................................................................................8
5 Technical Data ....................................................................................................8
6 Engineering .......................................................................................................13
7 Transport and Storage ......................................................................................13
8 Mounting and Installation ..................................................................................13
8.1 Dimensions / Fastening Dimensions .................................................................14
8.2 Mounting / Dismounting, Operating Position .....................................................14
8.3 Installation .........................................................................................................17
9 Parameterization and Commissioning ..............................................................18
9.1 Replacement of the Device ...............................................................................19
9.2 Parameterizations .............................................................................................19
10 Operation ..........................................................................................................20
10.1 Indications .........................................................................................................20
10.2 Troubleshooting ................................................................................................20
11 Maintenance and Repair ...................................................................................21
11.1 Maintenance .....................................................................................................21
11.2 Maintenance .....................................................................................................21
11.3 Repair ...............................................................................................................21
11.4 Returning the Device ........................................................................................21
12 Cleaning ............................................................................................................22
13 Disposal ............................................................................................................22
14 Accessories and Spare Parts ...........................................................................22

916260330020
2019-07-30·HB00·III·en·03
General Information
3
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
1 General Information
1.1 Manufacturer
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30
74638 Waldenburg
Germany
Phone: +49 7942 943-0
Fax: +49 7942 943-4333
Internet: r-stahl.com
E-Mail: [email protected]
1.2 Information about the Manual
ID-No.: 916260330020
Publication Code: 2019-07-30·HB00·III·en·03
Hardware version: C
Software version: V01-06
Configuration software ISpac Wizard 3.04.00 or subsequent versions
The original instructions are the English edition.
They are legally binding in all legal affairs.
1.3 Further Documents
• Cabinet installation guide
• Brief instructions for module parameterising with ISpac Wizard
(see ISpac Wizard software)
• FMEDA report
• Safety Manual 9162
• Data sheet 9162 Ex i
• Data sheet 9162
• Operating instructions 9162
For documents in additional languages, see r-stahl.com..
1.4 Conformity with Standards and Regulations
See certificates and EU Declaration of Conformity: r-stahl.com.
The device has IECEx approval. For certificate please refer to the IECEx homepage:
http://iecex.iec.ch/
Further national certificates can be downloaded via the following link:
https://r-stahl.com/en/global/support/downloads/.

Explanation of the Symbols
4916260330020
2019-07-30·HB00·III·en·03
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
2 Explanation of the Symbols
2.1 Symbols used in this Manual
2.2 Warning Notes
Warnings must be observed under all circumstances, in order to minimize the risk due to
construction and operation. The warning notes have the following structure:
• Signalling word: DANGER, WARNING, CAUTION, NOTICE
• Type and source of danger/damage
• Consequences of danger
• Taking countermeasures to avoid the danger or damage
Symbol Meaning
Tips and recommendations on the use of the device
General danger
Danger due to explosive atmosphere
Danger due to energised parts
DANGER
Danger to persons
Non-compliance with the instruction results in severe or fatal injuries
to persons.
WARNING
Danger to persons
Non-compliance with the instruction can result in severe or fatal injuries
to persons.
CAUTION
Danger to persons
Non-compliance with the instruction can result in light injuries to persons.
NOTICE
Avoiding material damage
Non-compliance with the instruction can result in material damage to the device and / or
its environment.

916260330020
2019-07-30·HB00·III·en·03
Safety Notes
5
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
2.3 Symbols on the Device
3 Safety Notes
3.1 Storage of the Manual
• Read the manual carefully.
• Store the manual at the mounting location of the device.
• Observe applicable documents and operating instructions of the devices to be
connected.
3.2 Personnel Qualification
Qualified specialist personnel are required to perform the tasks described in this manual.
This primarily applies to work in the following areas:
• Project engineering
• Mounting/dismounting the device
• (Electrical) installation
• Commissioning
• Maintenance, repair, cleaning
Specialists who perform these tasks must have a level of knowledge that meets
applicable national standards and regulations.
Additional knowledge is required for tasks in hazardous areas! R. STAHL recommends
having a level of knowledge equal to that described in the following standards:
• IEC/EN 60079-14 (Electrical installations design, selection and construction)
• IEC/EN 60079-17 (Inspection and maintenance of electrical installations)
• IEC/EN 60079-19 (Equipment repair, overhaul and reclamation)
Symbol Meaning
05594E00
CE marking according to the current applicable directive.
02198E00
According to marking, electric circuit certified for hazardous areas.
15649E00
Input
15648E00
Output
11048E00
Safety instructions that must always be observed: For devices with this
symbol, the corresponding data and/or the safety-relevant instructions
contained in this manual must be observed!
20690E00
Marking according to the WEEE directive 2012/19/EU

Safety Notes
6916260330020
2019-07-30·HB00·III·en·03
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
3.3 Safe Use
Before mounting
• Read and observe the safety notes in this manual.
• Ensure that the contents of this manual are fully understood by the personnel in
charge.
• Use the device in accordance with its intended and approved purpose only.
• Always consult with R. STAHL Schaltgeräte GmbH if using the device under operating
conditions not covered by the technical data.
• Make sure that the device is not damaged.
• We are not liable for damage caused by incorrect or unauthorised use of the device or
by non-compliance with this manual.
• Observe the document "Cabinet installation guide" for engineering
(download from r-stahl.com, product documentation, subitem "Engineering").
• Install the device in Zones 2, 22 or outside of hazardous areas.
• When used in Zones 2 or 22, the device must be built into an enclosure which
corresponds to the requirements of IEC/EN 60079-15 or IEC/EN 60079-31.
• Any damage may compromise the explosion protection.
For mounting and installation
• Have mounting and installation performed only by qualified and authorised persons
(see chapter "Qualification of the personnel").
• The device is only to be installed in areas for which it is suited based on its marking.
• During installation and operation, observe the information (characteristic values and
rated operating conditions) on the rating, data and information plates located on the
device.
• Before installation, make sure that the device is not damaged.
• Electrical circuits with the "Ex i" type of protection can no longer be operated as circuits
with this protection type after being operated with circuits with other types of protection.
• When used in Zones 2 and 22, the intrinsically safe devices of Zones 1, 0, 21 and 20
can be connected to the intrinsically safe signal circuits.
• The safety characteristic values of the connected field devices must correspond to the
specifications in the data sheet or in the EC Type Examination Certificate.
• Interconnecting several devices in a single intrinsically safe circuit can result in
different safety characteristic values. This may impair intrinsic safety!
• The device contains components that can be damaged by electrostatic discharge.
Before carrying out work on the device, the body must be discharged on earthed metal
parts or an ESD wrist strap must be put on.
• Connect the device only to equipment which does not carry voltages higher than
253 V AC (50 Hz).
• Ensure that there is a distance of at least 50 mm (tight string length) between
connecting units of intrinsically safe and non-intrinsically safe circuits when setting up
field circuits.
• The power supply of 24 V DC must be able to bridge brief interruptions of 20 ms in
order to ensure power failure bridging according to IEC/EN 61326-3-2 and NE 21.

916260330020
2019-07-30·HB00·III·en·03
Function and Device Design
7
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
Commissioning, maintenance, repair
• Only have commissioning and repairs performed by qualified and authorised persons
(see chapter "Personnel qualification").
• Before commissioning, make sure that the device is not damaged.
• Perform only maintenance work described in this manual.
• For SIL applications observe the safety manual and FMEDA reports.
• Make sure to use suitable cables and cable glands for temperatures below -20 °C.
• The configuration interface of the device can only be connected to a non-sparking
equipment with low power rating (according to IEC/EN 60079/15, chapter 13)
or for maintenance purposes in compliance with IEC/EN 60079-17, chapter 4.6.
3.4 Modifications and Alterations
4 Function and Device Design
4.1 Function
Application range
The transmitter supply unit with limiting values is used for operation of 2- and 3-wire
transmitters or for connection to mA sources. It is suitable for use in Zone 2, Zone 22 or
in the safe area.
The device type 9162/13-11-14 is solely used for operation of intrinsically safe
transmitters or for connection of intrinsically safe mA sources.
In contrast, the device type 9162/13-11-64 can either be used for intrinsically safe
and for non-intrinsically safe transmitters or mA sources.
Mode of operation
The 2- and 3-wire transmitters are supplied with auxiliary power by the transmitter supply
unit. Two limiting values can be defined with which the analog input signal is compared.
Exceeding or falling below the limiting values controls the electrical contacts.
The device can transmit a superimposed HART communication signal bidirectionally.
The parameters of the device can be adjusted using the ISpac Wizard software.
DANGER
Explosion hazard due to modifications and alterations to the device!
Non-compliance results in severe or fatal injuries.
• Do not modify or alter the device.
No liability or warranty for damage resulting from modifications and
alterations.
DANGER
Explosion hazard due to improper use!
Non-compliance results in severe or fatal injuries.
• Use the device only in accordance with the operating conditions
described in this manual.
• Use the device only for the intended purpose specified in this manual.

Technical Data
8916260330020
2019-07-30·HB00·III·en·03
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
4.2 Device Design
5 Technical Data
Marking
Type designation 9162/13-11-a4 (a=1,6)
CE marking C0158
Type 9162/13-11-14
#Device
component
Description
15202E00
1 Black/green
terminals
Connection terminals for the safe area
2 Parameteriza-
tion interface
Configuration of the device by means of
ISpac Wizard software Type "9199"
3 "PWR" LED,
green
Auxiliary power indication
4 "LF" LED, red Indication of line fault detection
5 "A" / "B" LED,
yellow
Indication for limit contacts A and B
6 DIP switch "RL" Release the anti-pumping device
7 Blue/black
terminals
Connection terminals for the field area
Explosion Protection
Global (IECEx)
Gas and dust IECEx BVS 15.0013X
Ex nA nC [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
Europe (ATEX)
Gas and dust BVS 15 ATEX E018X
E II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
E II (1) D [Ex ia Da] IIIC
Certifications and certificates
Certificates IECEx, ATEX, Canada (cFM), USA (FM)
2
3
5
1
7
6
4
9162

916260330020
2019-07-30·HB00·III·en·03
Technical Data
9
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
Type 9162/13-11-64
Safety data
When connecting
transmitters
When connecting
current sources
Explosion Protection
Global (IECEx)
Gas IECEx BVS 15.0013X
Ex nA nC IIC T4 Gc
Europe (ATEX)
Gas BVS 15 ATEX E017X
E II 3 G Ex nA nC IIC T4 Gc
Certifications and certificates
Certificates IECEx, ATEX, Canada (cFM), USA (FM)
Explosion Protection
2-wire transmitter 3-wire transmitter
max. voltage Uo27 V 27 V
max. current Io87.9 mA 88.3 mA
max. power Po574 mW 574 mW
max. connectable capacitance Co
IIC 90 nF 90 nF
max. connectable inductance Lo
IIC 2.3 mH 2.3 mH
internal capacitance Cinegligible negligible
internal inductance Linegligible negligible
Safety-related maximum
voltage
253 V 253 V
max. output voltage Uo4.1 V
max. output current Io~ 0 mA
Max. output power Po~ 0 mW
max. connectable voltage Ui30 V
max. connectable current Ii100 mA
internal capacitance Cinegligible
internal inductance Linegligible

Technical Data
10 916260330020
2019-07-30·HB00·III·en·03
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Transmitter Supply Unit with Limit Values
Series 9162
Type 9162/13-11-14 + Type 9162/13-11-64
Technical Data
Electrical data
Auxiliary power
Nominal voltage
UN
24 V DC
Voltage range 18 to 31.2 V
Residual ripple ( 3.6 VSS
Nominal current
at UN, 20 mA
85 mA
Power
consumption
at UN, 20 mA
2 W
Power dissipation
at UN, RL = 250 Ω
1.5 W
Polarity reversal
protection
yes
Operation
indication
LED green "PWR"
Undervoltage
monitoring
yes (no faulty devices / output states)
Input
Input signal 4 to 20 mA with HART
Functional range 2 to 22 mA
Max. input current
for mA sources
50 mA
Supply voltage for
transmitter
) 16 V at 20 mA (TAmb > - 10 °C, TAmb < -10 °C: US - 0.2 V / 10K)
Residual ripple of
supply voltage
( 25 mVeff
Open-circuit
voltage
( 26 V
Short-circuit
current
( 35 mA
Input resistance
(AC impedance
HART)
> 250 Ω
Input resistance
for mA sources
30 Ω
Communication
signal
bidirectional HART transmission, 0.5 to 10 kHz (in 2-wire transmitters)
Output
Output signal 4 to 20 mA with HART
Load
resistance RL
0 to 600 Ω (terminal 1+ / 2-)
Functional range 2 to 22 mA
Autres manuels pour 9162 Series
3
Ce manuel convient aux modèles suivants
2
Table des matières
Autres manuels Stahl Alimentation

Stahl
Stahl 9160/19-11-10k Manuel utilisateur

Stahl
Stahl 9143/10-065-200-10 Manuel utilisateur

Stahl
Stahl 9143 Series Manuel utilisateur

Stahl
Stahl 9412/00-300-10 Manuel utilisateur

Stahl
Stahl ispac 9143 Manuel utilisateur

Stahl
Stahl ISpac 9143/10-065-150 0 Series Manuel utilisateur

Stahl
Stahl 9162 Series Manuel utilisateur

Stahl
Stahl 9412 Series Manuel utilisateur

Stahl
Stahl Series 9160 Manuel utilisateur

Stahl
Stahl Series 9160 Manuel utilisateur