Supplied By www.heating spares.co Tel. 0161 620 6677
Entering the swit hing program
Individual days may be programmed with up to 3 entries (P1-P3) and a Monday to
Friday block may also be set with a further 3 entries.
A block temperature is set which is automatically entered into every switching
program.
As each switching program is enterd the required temperature may be adjusted
without affecting any other entry. If the block temperature setting is subsequently
adjusted then all program entries will revert to this temperature
Blo k temperatures
From the main screen press to enter the
password screen
From the password screen
press
to enter the main
menu
From the main menu screen
press
to enter the
programs screen
From the programs screen
press
to enter the block
day temp screen
Note: A basi program of Monday to Friday on at 08:00 (8am) and off at 17:00 (5pm)
and a blo k tempereature of 20ºC is preprogreammed into the eurotrol 2.
From the block day temp
screen press
to enter the block
day temp data
screen
Use the arrow keys to adjust
the block temperature
Press to enter the block day temp and
return to the previous screen
From the block day temp
screen press
to enter the
programs screen
From the programs screen
press
to enter the
programs data
screen
Press to alter the day (individual days are
selectable together with MO-FR as one
entry)
The program
Press to select the program number
(3 programs P1-P3 are available for each
day)
Press to select the
temperature
to alter (if
required)
Press to select the
or
to alter ( will
temporarily disable
the program entry)
Press to select the
first figure
to alter (if
required)
Press and to alter the subsequent
figures in the on and off
time
Press to select the day again. Work through
subsequent days and programs as
required for your program
Press to enter the program and return to the
program screen
Press to alter the program number (if required)
Press to return to the main display
Override
Sample program
The screens pictured below show the settings required for the following program:
Monday to Friday on between 8am and 1pm controlled at 20ºC
Monday to Friday on between 2pm and 5pm controlled at 20ºC
aturday on betweent 8.30am and 12pm controlled at 18ºC
1. Set Block temperature to 20ºC
ets all day temperatures to 20ºC
2. Set MO-FR Program 1: On 08:00 Off 1 :00
ets these times for Monday through to Friday
. Set MO-FR Program 2: On 14:00 Off 17:00
ets these times for Monday through to Friday
4. Set SA Program 1: Temp 18ºC: On 08: 0 Off 12. 0
ets these times and temperature for aturday
Menu and data input screens are selected and data is input,
using similar button sequences to that used in setting the clock.
Menu Options
Run log
Advanced menu: Extension time
Extends the current program when
is pressed once.
Extension time
Override
Main menu: Run log
Displays burner hours run and approximate running cost.
Constant fan
Advanced menu: Constant fan.
Heater fan runs constantly during program times in
heating mode.
Night temp
Advanced menu: Night temp.
ets temperature that heater operates during
program OFF times. May be turned On or OFF
Frost temp Advanced menu: Frost temp.
ets temperature that heater operates during fan only
and OFF mode. May be turned On or OFF
Set Mode
Main menu: Set mode
ets the operational mode for the controller.
Holiday dates
Main menu: Holiday dates
uspends the program while the buiding is unoccupied..
No. of sensors
Advanced menu: No. of sensors.
ets the number of sensors connected.
Optimum stop
Advanced menu: Optimum stop.
ets the temperature differential for optimum stop to begin.
Optimum stop:
et temperature differential (preprogrammed to 0ºC).
Optimum stop will switch off the heating to save energy before the end of the
program time.
Example: If the heating program calls for the building to be heated to 20ºC, but
it is felt that at the end of the heating program this temperature could drop to 18ºC
with no detrimental effect, then the optimum stop should be set to 2ºC (20ºC -
18ºC). This 2ºC will be applied to any of the programs in use.
Note: A setting of 0ºC effectively turns optimum stop off.
Differential
Advanced menu: Differential.
ets the switching differential for all set points.
Button A ess
Advanced menu: Button access.
ets the level of user button access.
Power and ost
Advanced menu: Power and cost.
Enters data to calculate approximate running cost.
New passsword
Advanced menu: New password.
ets new password.
Control mode
Extended menu: Control Mode.
Currently unavailable on this model.
Engineer
Extended menu: Engineer.
This menu only available to powrmatic engineers.
Note: Run log may also be displayed from the main display py
pressing and holding for 10 secs. (Password not required)
Servi e Date
Advanced menu: Service Date.
Displays service reminder and contact phone No.
e
e