6
5.2 Alarm setting mode
Character Name, Function, Setting range Default value
A1 setting
• Sets A1 output action point.
• Not available if No alarm action is selected in A1 action selection.
•Refer to (Table 5.2-1).
0
A2 setting
• Sets A2 output action point.
• Not available if the option Isolated power output is applied, or
if No alarm action is selected in A2 action selection.
• Refer to (Table 5.2-1).
0
A3 setting
• Sets A3 output action point.
• Not available if No alarm action or High/Low limit range alarm is
selected in A3 action selection.
•Refer to (Table 5.2-1).
0
(Table 5.2-1)
Alarm action type Setting range
High limit alarm Input range low limit to input range high limit value
Low limit alarm Input range low limit to input range high limit value
High limit alarm with standby Input range low limit to input range high limit value
Low limit alarm with standby Input range low limit to input range high limit value
High/Low limit range alarm *1 None
• The placement of the decimal point place follows the selection or input rating.
• When input has a decimal point, negative low limit setting value is –199.9, and positive high limit
setting value is 999.9.
• Setting range of DC current and DC voltage inputs: Scaling low limit to scaling high limit value.
*1: High/Low limit range alarm is available only for A3. If High/Low limit range alarm is selected,
the setting items which are related to A3 (A3 setting, A3 action Energized/Deenergized selection,
A3 hysteresis setting, A3 action delayed timer setting) will not be indicated.
5.3 SV display switching mode
Name, Function Default value
A1 setting value indication
• A1 setting value is indicated on the SV display and A1 setting indicator lights up.
• Not available if No alarm action is selected in A1 action selection.
0
A2 setting value indication
•A2 setting value is indicated on the SV display and A2 setting indicator lights up.
• Not available if the option Isolated power output is applied, or if No alarm
action is selected in A2 action selection.
0
A3 setting value indication
•A3 setting value is indicated on the SV display and A3 setting indicator lights up.
• Not available if No alarm action is selected in A3 action selection, or if High/Low
limit range alarm is selected.
0
5.4 Auxiliary function setting mode 1
Character Name, Function, Setting range Default value
Setting value lock designation
• Locks the setting values to prevent setting errors.
The setting item to be locked depends on the designation.
• (Unlock): All setting values can be changed.
(Lock 1): None of the setting values can be changed.
(Lock 2): Only main setting value can be changed.
(Lock 3): All setting values can be changed. However,
do not change the setting items in the
Auxiliary function setting mode 2.
They return to their former value after power
is turned off because they are not saved in
the non-volatile memory.
Unlock
Sensor correction setting
• Sets the correction value for the sensor.
• Setting range: –100.0 to 100.0 ( ), or –1000 to 1000
0.0
Communication protocol selection
• Selects the communication protocol.
• Available only when the option Serial communication is applied.
• Shinko protocol: , Modbus ASCII mode: ,
Modbus RTU mode:
Shinko protocol