CONFIGURATION SETTINGS ___________________________________
OPERATIONAL MODES
Standard power packs (model SWX-900) and secondary packs (model SWX-910) close
their relays automatically when a connected sensor signals occupancy. Versions with the
Auxiliary Switch Input option (e.g. model SWX-900-AX) have several additional modes of
operation that are listed below. Auto On/Auto Off (Setting #2) is the default mode.
TO CHANGE THE OPERATIONAL MODE
1Read through the above list and note the number of the desired setting
2Press and release the unit’s pushbutton twice, then wait 2 seconds.The White LED will
blink back the number of the current setting (e.g. 2 = Auto On / Auto Off).
3Press the pushbutton the number times equal to the new desired setting (e.g. 3 =
Manual On / Auto Off). The White LED will blink back the new setting as conrmation.
4New setting is saved after White LED blinks conrmation 3 times. If Blue LED double
ashes at any time, start process over.
LED OPERATION
To disable the LED from continuously ashing white as a “heartbeat”, press and release the
push-button 4 times, wait 2 seconds, then press and release the push-button 4 times again.
RELAY LOGIC
The power pack’s relay closes in response to occupancy being detected. To reverse this
logic (such that the relay opens in response to occupancy), press and release the push-
button 5 times, wait 2 seconds, then press and release the push-button 3 times again.
ADDITIONAL OPERATION NOTES
When in Auto-on/Auto-off mode, if lights are manually switched off when there are still occupants in a space (to show a presentation for example), they will remain off until either
switched back on manually or the sensor times out once the space is empty.
When in Manual On / Auto Off mode, if the switch is pressed but no occupancy is ever sensed, the lights will come on for 1 minute and then shut off. If no occupancy sensor is
present, tie the power pack’s white input wire to red (+VDC).
SETTING # MODE DESCRIPTION
2 Auto On / Auto Off Mode* (Occupancy Mode) Lights come on automatically when occupancy is detected and turn off automatically after sensor's time delay expires.
3 Manual On / Auto Off (Vacancy Mode) Lights must be manually switched on via a connected switch, but turn off automatically after sensor's time delay expires.
4 Unused NA
5 Override On / Logic High Lights are held on when auxiliary switch input wire is logic high (5-24VDC). Occupancy is ignored.
6 Override On / Logic Low Lights are held on when auxiliary switch input wire is logic low (< 5VDC). Occupancy is ignored.
7 Override Off / Logic High Lights are held off when auxiliary switch input wire is logic high (5-24VDC). Occupancy is ignored.
8 Override Off / Logic Low Lights are held off when auxiliary switch input wire is logic low (< 5VDC). Occupancy is ignored.
CONFIGURATION QUICK REFERENCE TABLE
FUNCTION SETTING DESCRIPTION
2 => Operational Modes 2 Auto-On / Auto Off (Occupancy Mode)
3 Manual On / Auto Off (Vacancy Mode)
4 Not Used
5 Override On, Logic High
6 Override On, Logic Low
7 Override Off, Logic High
8 Override Off, Logic Low
3 => Reset 3 Restore Factory Defaults
4 => LED Operation 2 LED Enabled
4 LED Disabled
5 => Relay Logic 2 Normal Relay Logic
3 Inverted Relay Logic