Seeley CW-H 2020 PLC Manuel utilisateur

OWNER’S MANUAL
CW-H 2020 PLC WALL CONTROLLER
(English)
Original English Instructions
ILL2468-A


CW-H COOLER PLC OWNER’S MANUAL 859731-D |1
TABLE OF CONTENTS
CW-H PLC WALL CONTROL
Models: All CW-H 2
Kit Contents 2
Specications 2
QUICK START
24VdcPowerAndRS485ModbusCommunicationsWiring 3
RS 485 Modbus Cooler Node Address 4
RS 485 Modbus Network Setup - First Time Use 4
PHYSICAL DESCRIPTION & MOUNTING
WallControlDimensionsAndSetupNotes 5
WallControlInstallationInstructions 6
CONNECTING
CommunicationCableSpecication 7
WiringRequirements 7
Power 8
TerminatingResistor 9
OPERATION SCREENS
MainMenu 10
CoolMode(ManualSpeedControl) 11
CoolMode(AutomaticSpeedControl) 12
VentMode 13
ProgramMode 14
EditThe7-DayProgram 15
SETTING SCREENS
ScreenDisplay 16
TimeAndDate 17
Language 17
SecurityLock 18
Conguration 18
Network 19
Auto-Restart 20
RoomSensor 20
AmbientSensor 20
Device 21
Monitor 21
FaultHistory 22
FaultScreenDisplay 23
BMS Lock 24
COOLER FAULTS AND TROUBLESHOOTING
TroubleshootingTable 25
OtherPotentialProblems 26
APPENDIX
ExampleWiringSchematic 27

2 |859731-D
CW-H PLC WALL CONTROL
MODELS: ALL CW-H
TheseinstructionsaretobereadinconjunctionwiththeInstallationandOperationand
Maintenanceguidesuppliedwiththecooler.
KIT CONTENTS
SPECIFICATIONS
General
Powersupply 24Vdc+/-10%
Power consumption 3.2VA1.3Wmax
DegreeofProtection IP20
Mounting VerticalWall,Flush
AmbientoperatingTemperature 0to50oC(32to122oF)
Ambientoperatinghumidity(non-condensing) 0to75%
Ambientstoragetemperature -30to50oC(-22to122oF)
Ambientstoragehumidity(non-condensing) 0to75%
Embedded Temperature Sensor Characteristics
Type 10kNTCtype2thermistor
Resolution +/-0.1oC(+/-0.2oF)
Measurementrange -40to+50oC(-40to+122oF)
Accuracy +/-0.5oC(+/-0.9oF)at21oC(70oF)
typicalcalibration
Embedded Humidity Sensors Characteristics
Typeandcalibration Singlepointcalibratedbulkpolymer
Precision Readingrangefrom10to90%R.H.non-condensing
10to20%precision:10%
20to80%precision:5%
80to90%precision:10%
Stability Lessthan1.0%yearly(typicaldrift)
Communication
Type RS485ModbusMaster
Maximumofnumberofslavedevices 15
ITEM IMAGE ITEM IMAGE
ClimateWizard
WallController
IsolatingScrew
MODBUS120Ω
Terminating
Resistor
Instructions
ITEM 1 ITEM 2
ILL2425-A

CW-H COOLER PLC OWNER’S MANUAL 859731-D |3
ILL3631-C
RS 485 +
RS 485 -
RS 485 GND
W/C +24Vdc
W/C 0Vdc
RS 485 +
RS 485 -
RS 485 GND
SENSOR U1
SENSOR U2
SENSOR G0
SENSOR G
TO WALL CONTROLLER
TO NEXT COOLER TO ROOM SENSOR
(OPTIONAL KIT)
120 OHM MODBUS TERMINATING RESISTER
TO BE FITTED TO LAST COOLER ONLY
SENSOR U1
SENSOR U2
SENSOR G0
SENSOR G
TO AMBIENT SENSOR
(OPTIONAL KIT)
24Vdc POWER AND RS 485 MODBUS COMMUNICATIONS WIRING
120
Ω
ILL3630-B
RS 485 -
RS 485 +
GND
-
ILL3630-B
QUICK START
WALL
CONTROLLER
CW-H
COOLER
ILL3631-C

4 |859731-D
RS 485 MODBUS COOLER NODE ADDRESS
Screen Layout
ILL3632-B
RS 485 MODBUS NETWORK SETUP - FIRST TIME USE
IMPORTANT-ThisClimateWizardWallControllercancontrolupto15CW-Hcoolers.Ensure
eachcoolerispoweredupandhasauniquenodeaddressset.Refertoinstallationliterature
providedwiththecoolerforsetupinstructions.
EnterSETTINGS–CONFIGURATION–NETWORKmenu
ILL3633-C
ILL3633-B
Listshowsalldetectedcoolers.
PressSAVEtocommitdetectedcoolerstoWallControlmemory.
QUICK START
ILL3632-A
INTERNAL
TEMPERATURE /
HUMIDITY
TIME
ON - OFF
COOL MODE
VENT MODE
PROGRAM MODE
SETTINGS
DATE
DATE TIME
ON OFF
COOL MODE
VENT MODE INTERNAL
TEMPERATURE /
HUMIDITY
PROGRAM MODE
SETTINGS

CW-H COOLER PLC OWNER’S MANUAL 859731-D |5
ILL3672-A
Number Description
1Colour touchscreen
2Powersupplyconnector
3RS 485 Modbus connector
4Holesfortemperatureandhumiditymeasurement
TheClimateWizardWallControllershouldbeplacedindoors,approximately1.5metres(5’)above
theoor,inthesamezoneinwhichcoolingisrequired.Placementiscriticalforcorrectfunctioning
ofthetemperatureandhumiditysensorsinsidetheController.
Thefollowingpointsmustbetakenintoconsideration:
• Avoiddirectsunlightexposure.
• Avoidmountingonexternalwalls.
• Avoidmountingthewallcontrolnearheatsourcessuchasstovesandtelevisions.
• Donotlocateinthedirectairowoftheductoutlets.
• Donotlocateinstrongdraftsorindeadspotssuchascupboards/drawers.
• Alwayssealthewallcableentryhole.
• AvoidblockingorrestrictingtheventholeslocatedontheundersideoftheController,asthis
iswherethesensorsarelocated.Important!Draftswithinthewallcavitycanimpactthe
temperatureandhumidityreadingofthewallcontrol.Werecommendthatthecableaccess
holebesealed,butinsuchawaythatthecablecanstillretreatintothewallcavity.
• TheControllershallbemountedvertically.
PHYSICAL DESCRIPTION & MOUNTING
WALL CONTROL DIMENSIONS AND SETUP NOTES
ILL3672-A
1
2
3
44

6 |859731-D
ILL3670-A
Step Action
1 Openunitbypullingonbottomsideofthedisplay(1)
2Ensurecorrectsideofbasefacesup
3 Pullcables150mm(5.90in.)outfromwall
4Alignbaseandmarklocationoftwomountingholesonwallorpanel(2)
CAUTION!
Alwaysmakesuretherearenoelectricalcables,gasorwaterpipes,orthelike,behind
whereyouintendtodrill.
5Installanchors(NOTINCLUDED)inwall(3)
6 Insertcableincentralholeofbase
7 Placerearcoveronthewallandalignitwithmountingholes(4)
8Insertscrews(NOTINCLUDED)inmountingholesoneachsideofbase(5)
9 InsertPOWERandCONTROLwiringaccordingtowiringchart
10 Gentlypushexcesswiringbackintohole
11 Gentlyaligncovertotopofbaseandsnapinplacefrombottom(6)
12 Installtheisolatedscrewconnectionforsecuringtheplastichousing(7)
PHYSICAL DESCRIPTION & MOUNTING
WALL CONTROL INSTALLATION INSTRUCTIONS
ILL3671-A
ILL3670-A

CW-H COOLER PLC OWNER’S MANUAL 859731-D |7
ILL3669-A
CONNECTING
C
mm2
mm2
AWG
AWG
7
7
0.28
0.28
mm
mm
0.2...2.5
24...14 24...14 22...14
0.5...0.6
4.42...5.31
22...14 2x 24...18 2x 24...16
2x 22...18 2x 20...16
0.2...2.5 0.25...2.5 0.25...2.5 2x 0.2...1 2x 0.2...1.5
2x 0.25...1 2x 0.5...1.5
in.
in.
N/m
Ø3.5mm (0.14in)
lb/in
COMMUNICATION CABLE SPECIFICATION
• SuitableforRS485applications
• Minimum1twistedpair(TP)andathirdconductor
• Copper Conductors
• 0.5mm2/AWG20
• BraidedShieldwithDrainWire
• Characteristicimpedance120Ω
• Nominalcapacitybetweenconductors89pF/m
• Nominalcapacitybetweenconductorsandshielding161pF/m
Usethetwistedpairforthe‘+’and‘-‘signalterminals.Usethe3rdconductorfortheGND
terminals.Attachthebraidedshield/drainwiretoanEARTHpointatoneendonly.
ILL3705-A
ILL3705-A
WIRING REQUIREMENTS
• CommunicationwiringmustbekeptseparatefromACpowerwiring.
• Alwaysroutecommunicationcablesatleast300mm(12”)awayfromhighvoltagecablesand
high-powermachines.
• Crossoverhighpowercablesatrightangles.
• MaximumcablelengthtorstCW-Hcooleris100m.
• MaximumcablelengthbetweeneachCW-His100m.
Note:Non-shieldedcablesarenotprotectedagainstelectromagnetinterferencewhichcancause
signaldegradation.
Attach the 120Ω resistor (supplied with Wall Controller) between the "+" and "-" terminals of
the Wall Controller
Attach the 120Ω resistor (supplied with CW-H cooler) between the "+" and "-" terminals of
the last CW-H cooler on the RS 485 Modbus network.
Donottthe120ΩresistorsuppliedwiththeremainingCW-HcoolerinstalledbetweentheWall
ControllerandthelastCW-Hcoolers.
SeeAnnexAforexamplewiringschematics

8 |859731-D
POWER
Characteristic Specication
Powersupply 24Vdc+/-10%
Power consumption 3.2VA1.3Wmax
FuseRecommendation(notincluded) TypeT500mA
TheClimateWizardWallControllercanbepoweredviaeitheraCW-Hcooleronthenetworkora
dedicatedpowersupply
Note:ShouldtheCW-HcoolerusedforprovidingpowerbeturnedotheWallControllerwillbeun-
abletocontroltheremainingcoolersonthenetwork.
Useproperwiresizestomeetvoltageandcurrentrequirementsandcopperconductors.
Ifusingadedicatedpowersupply,itmustberatedSafetyExtraLowVoltage(SELV)accordingto
IEC61140.Thesesourcesofpowerareisolatedbetweentheelectricalinputandoutputcircuitsof
thepowersupplyaswellassimpleseparationfromground(earth),PELV,andotherSELVsystems.
CONNECTING
ILL3637-A
ILL3637-A
WALL
CONTROLLER
CW-H
COOLER
+24Vdc
0Vdc
W/C +24Vdc
W/C 0Vdc
TO WALL CONTROLLER
ILL3639-B
ILL3639-B
Table des matières
Autres manuels Seeley Contrôleurs

Seeley
Seeley MagIQtouch Manuel utilisateur

Seeley
Seeley Braemar XK76 Manuel utilisateur

Seeley
Seeley MaglQtouch Instructions d'installation

Seeley
Seeley MAGICTOUCH MS1 Manuel utilisateur

Seeley
Seeley MagIQtouch Manuel utilisateur

Seeley
Seeley coolair Braemar Breezair MaglQtouch Manuel utilisateur

Seeley
Seeley MagIQtouch Manuel utilisateur