Level and Temperature Alarm System
Installation and Operation Manual
FC-40
SEE WATER, INC.
Panel Installation:
1. Caution: To maintain the NEMA 4X rating, make all wiring connections with
seal tight cable grips or conduit connections.
2. Set motor protectors to FLA of motors.
3. Run pump cables and oats cables through conduit. Make eld connections
as shown on wiring schematic.
4. Run power line conductor through conduit. Wire to terminals per enclosed
schematic.
5. Branch circuit protection to be provided by installer.
6. Panel circuit breakers are shipped in the closed position.
7. Ensure oats are properly mounted at the correct levels. Note: Floats shall
have free range of motion without touching each other or other equipment.
Page 2-2 IM 904 REV. 09/22
Notes:
Troubleshooting:
Caution: Before checking electrical connections within the control or
attempting to replace any components, turn off all branch circuits supplying
power to the main control panel.
Alarm Circuit:
• To test the alarm light and buzzer, press the test button on the front panel.
If either the light or buzzer do not indicate, replace the light bulb or buzzer
with the same type.
Floats:
• Check oats for entanglement, full range of motion. Replace damaged oats.
Warranty:
See Water, Inc. warrants that products of its manufacture
are free from defects in material and workmanship for
a period of 5 years from the date of purchase. This date
shall be determined by the date on the invoice and the
serial number on the product.
Replacement of the product is at the discretion of See
Water, Inc. This warranty is valid when the product
is installed in compliance with the manufacturer’s
installation instructions. The manufacturer’s obligation
under this warranty shall be limited to the repair or
replacement of any parts found by the manufacturer to
be defective, provided that the product is returned to
See Water, Inc.’s factory, postage prepaid with proof of
original purchase included.
The manufacturer of this warranty shall not be liable
under this warranty if the product has not been properly
installed; any alterations/additions/changes to the
product will result in a void warranty. Failure to properly
install and test this product can result in personal injury
or equipment malfunction.
See Water, Inc. shall not be liable for any loss, damage
or expenses from installation or use of its products.
1
2
3
TYPICAL INSTALLATION OF FC-40 ALARM :
Knight SeriesÒ FC-40 Control Panel
Temperature Sensor
Low Level Float
1
2
3
Operation:
1. The temperature display shall indicate the temperature at the location of the
temperature sensor.
2. Lights on the front panel will illuminate under any of the following conditions:
(a) Low Temperature (below 40°F) or (b) Low Level.