1. DESCRIPTION
The SA-Control remote control panel is designed for:
• SALDA ventilation units and other devices based on PRV (RIS EKO 3.0, RIRS
EKO 3.0, Smarty 3R VER/VEL 3.0), MCB/MiniMCB (Smarty, AmberAir, AmberAir
Compact) controllers;
• Modbus-controlled devices.
Attention!
• Some of the articles in this guide may not apply to you. It depends on
the type of the control board on your device.
• Always choose accessories manufactured by Salda UAB. Otherwise,
the warranty will be void.
2. DIMENSIONS
In pic. 1 (page 63) the dimensions are shown: 123 x 82 x 15 (mm).
3. ACCESSORIES
• 1x SA-Control control panel;
• 2x Cables (RJ45 for MCB/MiniMCB and RJ10 for PRV);
• 2x Fastening elements (screw 3,9 x 25 DIN 7981 – 2 pcs, nylon plug 5x25 – 2
pcs, hammered steel plug 12x30 – 2 pcs);
• 1x Quick Launch Guide.
4. TECHNICAL DATA
PARAMETER UNITS VALUE
Mounting Surface
Voltage V (AC/DC) 24 (max 1,3 W)
Communication line ModBus RS485
Cable length [m] 13
Dimensions (W x H x D) [mm] 123 x 82 x 15
Protection class IP- 30
Ambient temperature [°C] 10 - 40

4 | EN SA-CONTROL v2019.1
Relative humidity [%] 10 - 80 (without condensation)
5. CONNECTING SA-CONTROL REMOTE CONTROLLER
TO AN AIR HANDLING UNIT
Use the following steps to connect a SA-Control remote controller to an air han-
dling unit:
• Unpack the SA-Control remote controller;
•Connect the cable to the connector slot on the control panel pic. 3.1 - 3.3 (page
63):
•Use the cable with an RJ10 connector for the connection to the air handling unit
with PRV control board (further RJ10 cable) pic. 4.1 (page 63);
•Use the cable with an RJ45 connector for the connection to the air handling unit
with a MCB or mini MCB control board (further RJ45 cable) pic. 4.2 (page 63).
•Plug in the RJ45 cable connector to the X18 MCB pic. 5 (page 63) or X18 mi-
niMCB pic. 6 (page 64) connection slot on the control board. Make sure that the
PRV control board, plug the RJ10 cable connector into the RS485_2 slot on the
pic 7 (page 64);
• Plug the ventilation unit into the electric circuit.
6. INSTALLATION ON A WALL
• Turn the panel g. 2.1 (page 63).
• Put it at the desired location on the wall pic. 8 - 11 (page 64). Mark the positions
of the mounting holes.
• Drill two 5 mm holes at the marked positions for the nylon plugs and the hole
throughout the wall to install the cable pic. 9 (page 64). Insert the nylon plugs.
NOTE: You can use special metal plugs (included) instead of the nylon ones.
• Use the included 2.9x16 DIN7981C screws and mount the panel to the wall as
indicated in g. 8 (page 64).
• Put the panel on the mounting bracket g. 9 - 11 (page 64).
IMPORTANT: IT IS FORBIDDEN to leave the remaining remote controller’s
cable in the AHU’s control box pic. 12 (page 64)!
IMPORTANT: Do not forget to connect the cable before attaching the panel.
7. THE MAIN SCREEN PRV BOARD
In pic. 13 (page 65) the main window of the PRV board functions is shown:
l1. Date and time.

EN | 5SA-CONTROL v2019.1
l2. Temperature of the extracted air (room temperature).
B1. Menu button.
B2. Click to open the fans speed setting window.
B3. Click to open the temperature setting window.
B4. Click to open the mode setting window.
B5. Show the next set of indication panels.
8. THE MAIN SCREEN MCB/MINIMCB BOARD
In pic. 14 (page 65) the main window MCB board functions are shown:
l1. Operating mode (comfort, max boost, stand-by, building protection or econ-
omy).
l2. Date and time.
l3. Temperature of the extracted air (room temperature).
l4. Temperature of the outside air.
B1. Menu button.
B2. Click to open the mode setting window.
B3. Show next set of indicators.
9. LANGUAGE SELECTION
Go to the MENU → SETTINGS →LANGUAGE to choose the language. Pic. 15 (page
66).
B1. Buttons to select the language for the user interface.
10. CHANGING OF DATE / TIME
Go to the MENU → DATE & TIME to change the date/time selection. Pic. 16 (page
66).
l1. Set the date & time displayed.
F1. Year.
F2. Month.
F3. Day.
F4. Hour (24h format).
F5. Minute.
B1. Buttons to increase value.
B2. Buttons to decrease value.

6 | EN SA-CONTROL v2019.1
11. CHANGING OF SUPPLY AIR TEMPERATURE
Go to the MENU → SET POINT to change the supply air temperature. Pic. 17 (page
67).
l1. Window name.
l2. Time.
l3. Newly-set desired room temperature (the extracted air temperature).
B1. Back. Return to the previous window.
B2. Decrease the set temperature.
B3. Increase the set temperature.
12. CHANGING THE FAN SPEED, BOOST (PRV)
Click on the fan speed button to change the fan speed, boost (PRV). Pic. 18
(page 67).
l1. Displays the active fan speed mode.
B1. Click to activate the “Stand-by” mode (if other settings allow this).
B2. Click to turn on fan speed 1.
B3. Click to turn on fan speed 2.
B4. Click to turn on fan speed 3.
B5
13. CHANGING OF MODE (MCB)
Click on the system mode button to change the mode (MCB). Pic. 19 (page 68):
l1. Current operating mode.
B1. STANDBY – AHU is stopped.
B2. BUILDING PROTECTION – maintain minimal air movement. The temper-
ature can be maintained depending on the settings in the MENU → SET POINTS.
B3. ECONOMY – use a decreased fan speed. The temperature can be main-
tained depending on the settings in the MENU → SET POINTS.
B4. COMFORT – use normal fan speed. The temperature is maintained.
B5
14. THE MAIN SAFETY INSTRUCTIONS
•
•
•
•

EN | 7SA-CONTROL v2019.1
•
•Electric connection must be performed according to electrical schematics and
•
15. UTILIZATION
Electrical and electronic waste.
•
•
• For further information on recycling, please contact the seller or the supplier.
16. SOFTWARE UPGRADE
Go to http://www.salda.lt/en/products/category/download_page/ or scan QR
Code Pic. 20 (page 68).

8 | DE SA-CONTROL v2019.1
1. BESCHREIBUNG
Der Bedienteil SA-Control ist entworfen worden für:
• SALDA - Lüftungsgeräte und andere Geräte, die auf PRV - Controller (RIS EKO
3.0, RIRS EKO 3.0, Smarty 3R VER/VEL 3.0), MCB/MiniMCB Controller
(Smarty, AmberAir, AmberAir Compact) basiert sind;
• Modbus-kontrollierte Geräte.
Achtung!
• Einige der Artikel in dieser Bedienungsanleitung können für Sie nicht
gelten. Es hängt vom Typ der Steuerplatine auf Ihrem Gerät ab.
• Wählen Sie immer Zubehöre, die durch Salda UAB ausgefertigt
worden sind. Sonst entfällt die Garantie.
2. DIMENSIONEN VON SA-CONTROL
Im Foto 1 (Seite 63) werden die Dimensionen geschildert: 123 x 82 x 15 (mm).
3. ZUBEHÖRE ZU SA-CONTROL
• 1x Bedienungsfeld von SA-Control;
• 2x Kabel (RJ45 für MCB/MiniMCB Steuerplatine und RJ10 für PRV Steuerpl-
atine);
-
tecker 5x25 - 2 Stück, gehämmerter Stahldübel 12x30 - 2 Stück);
• 1x Schneller Startführer.
4. TECHNISCHE DATEN
PARAMETER EINHEITEN WERT
Einbau
Stromspannung V (AC/DC) 24 (max 1,3W)
Fernmeldeleitung ModBus RS485
Kabellänge [m] 13
Dimension (W x H x D) [mm] 123 x 82 x 15
IP-30
Umgebungstemperatur [°C] 10 - 40

DE | 9SA-CONTROL v2019.1
Relative Feuchtigkeit [%] 10 - 80 (ohne Kondensation)
5. VERBINDUNG EINES SA-CONTROL BEDIENTEILES
ZU EINEM LÜFTUNGSGERÄT
Verwenden Sie die folgenden Schritte, um den Bedienteil SA-Control mit einem
• Packen Sie den Bedienteil SA-Control aus;
•s. Foto 3.1 -
3.3 auf der Seite 63):
•-
tungsgerät mit der PRV Steuerplatine (weiter RJ10 Kabel) (s. Foto 4.1 auf der
Seite 63);
•-
tungsgerät mit einem MCB oder MCB Mini Steuerplatine (weiter RJ45 Kabel) (s.
Foto 4.2 auf der Seite 63).
•s. Foto 5 auf
(s. Foto 6 auf der Seite 64) auf
der Steuerplatine ein. Stellen Sie sicher, dass das Gerät während der Operation
ausgeschaltet wird. Wenn das Lüftungsgerät mit einer PRV Steuerplatine ausges-
dem Gerätsgehäuse (s. Foto 7 auf der Seite 64) ein;
• Schalten Sie das Lüftungsgerät in den elektrischen Stromkreis ein.
6. SA-CONTROL INSTALLATION AN EINER WAND
• Abb. 2
• Stellen Sie es an der gewünschten Position an der Wand (s. Foto 8 - 11 auf der
•
s.
Foto 9 auf der Seite 63) BE-
MERKEN SIE:-
legt) verwenden.
• Verwenden Sie die beigelegten 2.9x16 DIN7981C Schrauben und befestigen
Abb. 8 (Seite 64).
• Stellen Sie die Tafel, indem Sie die Handlungen wie auf dem oberen Foto 9 - 11
(Seite 64) ausrichten.
WICHTIG: ES WIRD VERBOTEN, das restliche Kabel der Fernbedienung im
Kontrollkasten des AHU liegen zu lassen! Foto 12 (seite 64).
WICHTIG: Vergessen Sie nicht, das Kabel vor der Befestigung der Tafel zu

10 | DE SA-CONTROL v2019.1
verbinden.
7. HAUPTBILDSCHIRM DER PRV STEUERPLATINE
Auf dem Foto 13
l1. Datum und Zeit.
l2. Ablufttemperatur (Raumtemperatur).
B1. Menü Taste.
B2. -
B3.
B4.
B5.
8. DER HAUPTSCHIRM DER MCB/MINIMCB STEUER-
PLATINE
Auf dem Foto 14 (Seite 65) werden die MCB - Funktionen auf dem Hauptfenster
l1. Betriebsmodus (comfort, max boost, stand-by, building protection or econo-
my).
l2. Datum und Zeit.
l3. Ablufttemperatur (Raumtemperatur).
l4. Aussenlufttemperatur.
B1. Menü Taste.
B2.
B3.
9. SPRACHAUSWAHL
MENÜ →EINSTELLUNGEN →SPRACHE
Foto 15 (Seite 66).
10. ÄNDERUNG DES DATUMS / DER ZEIT
MENÜ →DATUM UND ZEIT
Foto 16 (Seite 66).
l1.
Autres manuels pour SA-Control
1
Table des matières
Langues :
Autres manuels Salda Télécommande

Salda
Salda SA-CONTROL RIRS 1200 HWR EKO 3.0 RHX Manuel de l'opérateur

Salda
Salda Ptouch Manuel utilisateur

Salda
Salda PRO Manuel utilisateur

Salda
Salda RIS 1200 VEL EKO 3.0 Manuel de l'opérateur

Salda
Salda Ptouch Manuel utilisateur

Salda
Salda RIRS 1900 HER EKO 3.0 RHX Manuel de l'opérateur

Salda
Salda UNI Manuel utilisateur
Manuels Télécommande populaires d'autres marques

Panasonic
Panasonic EUR7622KB0 Manuel utilisateur

Bang & Olufsen
Bang & Olufsen Beo4 Manuel utilisateur

Sunwave Tech.
Sunwave Tech. RemoteComm SRC-7000 Manuel utilisateur

Multiplex
Multiplex PROFI TX 9 Manuel utilisateur

One Remote
One Remote RMB4 Manuel utilisateur

FUTABA
FUTABA 9ZAP - PART2 Manuel utilisateur