Caution!
There is the danger of tipping when the
doors are opened 180° and the housing
is empty!
If necessary, secure the Micro Data
Centre to a solid surface.
Caution!
Thereisthedanger of tippingwhenmore
than one component is pulled-out from
the 482.6 mm (19") level.
Pull-out only one component from the
482.6 mm (19") level at a time.
Caution!
There is danger caused by falling devic-
es. No devices may be installed on the
internal mounting rails when they are ad-
justed. The failure to adhere to this rule
can lead to severe injuries and/or dam-
age to devices.
Also observe the following safety notes:
–
Any mains power connection or mains power wiring
required as part of the Micro Data Centre Level E
wiring may only be performed by an experienced
electrician.
–
Do not modify the unit!
–
Use only original spare parts!
–
The Micro Data Centre does not provide any protec-
tion against standing or rising water.
–
During normal operation, the Micro Data Centre
must not come in contact with water, aggressive or
inflammable gases and vapours.
–
The Micro Data Centre may only be operated within
the specified environmental conditions (see section
10 "Technical specifications").
–
Observe any national regulations for accident pre-
vention.
–
Observe any company-internal regulations.
–
Observe all special safety notes associated with the
individual tasks in the appropriate sections.
2.2
Safety notes for the prevention of dam-
age to the Micro Data Centre
Note:
The Micro Data Centre may only be in-
stalled vertically on a flat floor with max. 2°
deviation to guarantee the correct function
of the safety doors.
Note:
Do not change the location of the Micro
Data Centre yourself and do not disassem-
ble it yourself.
Contact the manufacturer or a service com-
pany authorised by the manufacturer to
perform this work.
Note:
Prior to the assembly of the Micro Data
Centre, check the requirements placed on
the operational environment.
The Micro Data Centre may be used only
for the approved indoor application.
With this regard, also observe the manufac-
turer's details for the components to be in-
stalled. In particular, the permitted environ-
mental parameters, such as temperature,
air humidity and the requirements placed
on the ambient air, must be observed.
Do not obstruct or adjust the air inlets and
outlets of the cooling system on the inside
and the outside of the Micro Data Centre.
The heat load inside the Micro Data Centre
must not exceed the rated power specified
on the rating plate of the cooling system.
The ambient temperature at the installation
site of the Micro Data Centre must lie within
the temperature limits of +10°C and +35°C.
Ensure adequate ventilation or climate con-
trol of the installation site.
Note:
Use only original spare parts. Should spare
parts be required, contact customer ser-
vice at Rittal.
Note:
Store the keys for opening the safety doors
only at a location that cannot be accessed
by unauthorised persons. Never save the
keys in the Micro Data Centre.
Note:
After completion of the cooling unit installa-
tion, wait at least two hours before placing
the unit into operation. The commissioning
must be performed by authorised person-
nel. The customer is responsible for the
correct operation of the condensate dis-
charge routed through the cable duct.