UNC100 Axiom Installation Manual
new generation
building security
July 31, 2014 –V1.2

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 2of 25
Copyright Notice
Copyright©1995-2014 by RBH Access Technologies Inc.
All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant to an
agreement containing restrictions on its use. No part of this book may be copied or distributed,
transmitted, stored in a retrieval system, or translated into any human or computer language, in any
form or by any means, electronic, mechanical, magnetic, manual, or otherwise, or disclosed to third
parties without the express written consent of RBH Access Technologies Inc., Mississauga, Ontario,
Canada.
Trademark
AxiomV™is the trademark of RBH Access Technologies Inc. Windows is a trademark of Microsoft
Corporation. All other product names mentioned herein are the property of their respective owners.
Use of a term in this book should not be regarded as affecting the validity of any trademark or service
mark.
Disclaimer
This book is provided as is, without warranty of any kind, either express or implied, including but not
limited to performance, merchantability, or fitness for any particular purpose. Neither RBH Access
Technologies Inc. nor its dealers or distributors shall be liable to any person or entity with respect to any
liability, loss, or damage, caused, or alleged to have been caused directly or indirectly by this
information. Further RBH Access Technologies Inc. reserves the right to revise this publication, and to
make changes to the content hereof from time to time, without the obligation of RBH Access
Technologies Inc. to notify any person or organization of such revision or changes.
RBH ACCESS TECHNOLOGIES INC.
2 Automatic Road, Suite 108
Brampton, Ontario
CANADA
L6S 6K8
www.rbh-access.com

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 3of 25
Revision History
Editor
Revision
Comment
Date mm/dd/yy
DM
1.0
First Release
08/13/13
RB
1.1
Removed reference to fire input
Removed partial firmware upgrade (formats)
Added dip-switch 5
Added Revision History
Updated copyright
Eliminated reference to rack mount type
Clarified the use of the Power Input/ Output
Moved all cable specs to one location.
Moved all input specs to one location.
Moved all output specs to one location.
Reduced the number of pages.
03/19/14
DM
1.1
Minor editing of text.
03/24/14
RB
1.2
Changing output voltage from
12V to 12v –14v
Changing battery charger spec
07/21/14
DM
1.2
Minor editing.
07/31/14
DM
1.2
ULC text added.
08/06/14

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 4of 25
Copyright Notice ............................................................................................................................................ 2
Trademark...................................................................................................................................................... 2
Disclaimer....................................................................................................................................................... 2
Revision History ............................................................................................................................................. 3
Panel Graphics ............................................................................................................................................... 5
Introduction ................................................................................................................................................... 7
ULC-S319-05 III.............................................................................................................................................. 7
Communication.............................................................................................................................................. 7
Networks........................................................................................................................................................ 7
RS485 Applications......................................................................................................................................... 8
DIP Switch Settings ........................................................................................................................................ 8
Controller Addressing .................................................................................................................................... 9
Master Controller......................................................................................................................................... 10
Slave Controller............................................................................................................................................ 10
RS485 (HOST) Port Baud Rate Selection (Master Only)............................................................................... 10
Host Connection........................................................................................................................................... 10
PC to UNC100 Connection –RS485 Wiring.................................................................................................. 11
UNC100 TCP/IP Connection ......................................................................................................................... 12
Telnet ........................................................................................................................................................... 13
Battery Charger............................................................................................................................................ 15
Reverse Battery Protection.......................................................................................................................... 15
Battery Test.................................................................................................................................................. 15
Fuse Monitoring........................................................................................................................................... 15
Diagnostic LED’s ........................................................................................................................................... 15
Tamper Detection ........................................................................................................................................ 15
RAM Memory............................................................................................................................................... 16
Power Input / Output................................................................................................................................... 16
D-NET Device Network................................................................................................................................. 16
Reader Interface .......................................................................................................................................... 19
Reader Connection ...................................................................................................................................... 19
Access Point Operating Modes .................................................................................................................... 20
Two Person .......................................................................................................................................... 20
High Security ........................................................................................................................................ 20

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 5of 25
Unlocked .............................................................................................................................................. 20
Tamper................................................................................................................................................. 20
Lockout Alarm ...................................................................................................................................... 20
Door Held Open Warning..................................................................................................................... 20
Door Held Open Alarm......................................................................................................................... 20
Keypad / Reader Combination............................................................................................................. 20
Access Granted .................................................................................................................................... 20
Access Denied ...................................................................................................................................... 20
Outputs ........................................................................................................................................................ 21
Default Output Operation........................................................................................................................ 21
Lock Output.......................................................................................................................................... 21
Forced / Tamper................................................................................................................................... 21
Door Held Open ................................................................................................................................... 21
Alarm Shunt ......................................................................................................................................... 21
Switching Inductive Devices (Locks, Bells) ............................................................................................... 21
Input Applications ........................................................................................................................................ 22
Request to Exit (RTE)................................................................................................................................ 22
Door Contact (DC) .................................................................................................................................... 22
Supervised Inputs......................................................................................................................................... 23
Input Circuit Types ....................................................................................................................................... 23
UNC100 Specification................................................................................................................................... 25
Cable Specification....................................................................................................................................... 25
Panel Graphics

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 6of 25

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 7of 25
Introduction
The UNC100 is a single door In/Out access point controller for the Axiom™ system that includes a built-in
local area network interface.
The network interface also utilizes a POE (power over Ethernet) converter.
ULC-S319-05 III
For ULC-S319-05 III compliance, all wiring into the panel’s cabinet must enter through metal conduit.
Also be sure to mount the panel in a protected area.
Communication
The UNC100 has one RS485 port and an Ethernet 10/100 interface. Communications from the host
computer running Axiom software can be achieved in the following ways; either via the Ethernet
interface or via RS485 through a direct connection to a designated channel. The UNC100’s RS485
channel may be programmed as HOST, DNET, UNC-NET, or LAN. Use the DIP switch to select baud rate
for Host communications as 9600, 38400, 57600, or 115200.
Networks
There are three networks supported by the UNC100 these are:
1) Host Communications through the Ethernet or direct connection.
2) Device Communications for devices such as additional RC-2s starting at address 2, Alarm Keypads,
IOC-16 controllers, and PC100.
3) Controller Communications for controllers such as additional UNC500s or for NC100s via UNC-NET
which is protocol designed for RS485 communications between UNC500s and UNC100s only.

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 8of 25
RS485 Applications
Application name
Description
HOST
The Host port connects the UNC500 to a PC through an RS485
interface.
D-NET
The D-NET (Device Network) connects local device controllers
(RC-2, IOC-16, SafeSuite™ Panels, NRC2000, or NURC2000) to
the UNC100 controller on a high-speed bi-directional RS485
network.
UNC-NET
The UNC-NET (Controller Network) connects the UNC100
controller to other on a high-speed bi-directional RS485
network.
DIP Switch Settings
The UNC100 DIP switch controls the device’s address and serial port baud rate.
Note: To Clear Panel memory –All DIP switches must be off and the unit powered off and
on.
DIP Switch
DIP Switch
Function
1 - 4
Controller Address
5
Ethernet Secure Mode1
6,7
Controller Baud Rate
8
Not used
1DIP switch 5 up will enables Ethernet Secure Mode. This will prevent access to the panel’s programming through
the Ethernet.

UNC100 Axiom Hardware Manual V1.2 RBH Access Technologies Inc.
Page 9of 25
Controller Addressing
Use DIP switches 1, 2, 3, and 4 to select the controller address. The address is binary coded and the
switch settings for all fifteen possible addresses are given below.
Controller Addressing
Switch 1
Switch 2
Switch 3
Switch 4
Address
Off
Off
Off
Off
Clear Memory
On
Off
Off
Off
1 (Master)
Off
On
Off
Off
2 (Slave)
On
On
Off
Off
3 (Slave)
Off
Off
On
Off
4 (Slave)
On
Off
On
Off
5 (Slave)
Off
On
On
Off
6 (Slave)
On
On
On
Off
7 (Slave)
Off
Off
Off
On
8 (Slave)
On
Off
Off
On
9 (Slave)
Off
On
Off
On
10 (Slave)
On
On
Off
On
11 (Slave)
Off
Off
On
On
12 (Slave)
On
Off
On
On
13 (Slave)
Off
On
On
On
14 (Slave)
On
On
On
On
15 (Slave)

UNC100 Axiom Hardware Manual V1.1 RBH Access Technologies Inc.
Page 10 of 25
Master Controller
Each network must have a single unit designated as the master controller. The master controller
connects to the PC. Setting the DIP switch address to 1 will automatically designate a unit as the master
controller.
Slave Controller
All controllers addressed 2 through 15 are referred to as slave controllers.
RS485 (HOST) Port Baud Rate Selection (Master Only)
The controller's serial port baud rate is set with controller DIP switches 6 and 7. This setting determines
the speed used to communicate with the PC; the controller baud rate must be the same as the baud rate
set for the port within the AxiomV™ software. The default baud rate is 9600.
Controller Baud Rate Selection
DIP Switch 6
DIP Switch 7
Baud Rate
OFF
OFF
9600
ON
OFF
38400
OFF
ON
57600
ON
ON
115200
Host Connection
The master controller is connected to either a serial port on the PC or through the local Ethernet via a
static IP address. The means of communication is configured in the AxiomV™software under Network
Properties/Port Type.