USER GUIDE
HLS 44-SER
3 (6)
Produal
Oy
Keltakalliontie 18, 48770 Kotka FINLAND Tel: +358 10 219 9100 / Fax: +358 5 230 9210 [email protected]i www.produal.com Information is subject to change without prior notice.
MODBUS REGISTERS OF THE SET 6…9 PROFILES
SET 6: Heating with radiator and cooling with beam
Register Parameter Description Value Range Default Comments
COILS
1 Cooling PWM overdrive enable (A1) Off=0, On=1 Off - On 0 No modbus overdrives
2 Cooling 0-10V overdrive enable (Y3) Off=0, On=1 Off - On 0 No modbus overdrives
3 Heating PWM overdrive enable (A2) Off=0, On=1 Off - On 0 No modbus overdrives
4 Heating 0-10V overdrive enable (Y4) Off=0, On=1 Off - On 0 No modbus overdrives
5 VAV overdrive enable (Y1) Off=0, On=1 Off - On 0 No modbus overdrives
6 FAN overdrive enable (Y2) Off=0, On=1 Off - On 0 No modbus overdrives
7 On/Off damper overdrive enable (B1) Off=0, On=1 Off - On 0 No modbus overdrives
8 Light control overdrive enable (B2) Off=0, On=1 Off - On 0 No modbus overdrives
9 Overdrive On/off damper by modbus (B1) Off=0, On=1 Off - On 0 No modbus overdrives
10 Overdrive Light control by modbus (B2) Off=0, On=1 Off - On 0 No modbus overdrives
11 SERVICE ALARM RESET Off=0, On=1 Off - On 0
12 Cooling disabled Off=0, On=1 Off - On 0 Cooling working
13 Heating disabled Off=0, On=1 Off - On 0 Heating working
14 NIGHT MODE Off=0, On=1 Off - On 0 The device is allways in day mode
15 Cooling output mode (DIR/REV) Off=0, On=1 Off - On 0 Direct output mode
16 Heating output mode (DIR/REV) Off=0, On=1 Off - On 0 Direct output mode
17 Cooling stages (1st/2st) Off=0, On=1 Off - On 0 1 stage cooling, chilled beam
18 Sequence of cooling stages (A-st/V-st) Off=0, On=1 Off - On 0 No affect on this process
19 Fan ramp with motor ramp Off=0, On=1 Off - On 1 No affect on this process
20 Night operation mode (DZ/FG) Off=0, On=1 Off - On 0 No affect, if the device is allways in day mode, see Coil 14
21 Night to day setpoint transition Off=0, On=1 Off - On 0 No affect, if the device is allways in day mode, see Coil 14
22 Jam function Off=0, On=1 Off - On 0 the jum fuction is not activated
23 Fan type (3coil/CE) Off=0, On=1 Off - On 0 No affect on this process
24 Fan speed 3 disabled Off=0, On=1 Off - On 0 No affect on this process
25 Fan night to day transition Off=0, On=1 Off - On 0 No affect, if the device is allways in day mode, see Coil 14
26 VAV for heating Off=0, On=1 Off - On 0 No affect on this process, the VAV function is not used
27 Display TE/SP Off=0, On=1 Off - On 0 The display shows the room temperature (not the setpoint)
28 DI2 operation direction Off=0, On=1 Off - On 0 DI2 is not used. No affect on this process
29 Cooling on/off thermostat (off = P/PI) Off=0, On=1 Off - On 0 P/PI mode for cooling
30 Heating on/off thermostat (off = P/PI) Off=0, On=1 Off - On 0 P/PI mode for heating
31 Y1 for cooling (off = VAV) Off=0, On=1 Off - On 0 Y1 is not connected ... No influence
32 Y2 for heating (off = FAN) Off=0, On=1 Off - On 0 Y1 is not connected ... No influence
HOLDING REGISTERS
40001FAN Speed by Modbus 0 … 4 0 - 1 - 2 - 3 - 4 0 No affect on this process
40002Setpoint by Modbus 80 … 500 8,0 … 50,0 °C 210 Temperature setpoint from modbus 21°C
40003Overdrive Cooling PWM by modbus (A1) 0 … 1000 0,00 … 100,0% 0 No modbus overdrives chosen... The value has no affect (see coils 1 ... 10)
40004Overdrive Cooling 0...10V by modbus (Y3) 0…1000 0 …10.00 V 0 No modbus overdrives chosen... The value has no affect (see coils 1 ... 10)
40005Overdrive Heating PWM by modbus (A2) 0 … 1000 0,00 … 100,0% 0 No modbus overdrives chosen... The value has no affect (see coils 1 ... 10)
40006Overdrive Heating 0...10V by modbus (Y4) 0…1000 0 …10.00 V 0 No modbus overdrives chosen... The value has no affect (see coils 1 ... 10)
40007Overdrive VAV by modbus (Y1) 0…1000 0 …10.00 V 0 No modbus overdrives chosen... The value has no affect (see coils 1 ... 10)
40008Overdrive FAN by modbus (Y2) 0…1000 0 …10.00 V 0 No modbus overdrives chosen... The value has no affect (see coils 1 ... 10)
40009DI2 Not used, ext T, door/window, condensation 0 … 3 0 … 3 0 DI2 is not used in this process
40010 Temperature sensor adjustment -30 … 30 -3,0 … 3,0 °C 0 Internal sensor has its factory calibration
40011 Center of user setpoint 180 … 260 18,0 … 26,0 °C 210 Center of the user setpoint 21°C
40012 User setpoint limits 0 … 160 0,0 … 16,0 °C 30 End user can change the setpoint +/- 3 °C from the point above
40013 Control mode 0 … 1 P/PI 1 Control mode PI
40014 Dead zone 0 … 30 0,0 … 3,0 °C 2 Dead zone 2,0 °C
40015 Setpoint relation to Dz 0 … 100 0 … 100% 50 Setpoint is in the center of the dead zone
40016 Proportional band 10 … 320 1,0 … 32,0 °C 20 Proportional band 2,0 °C
40017 Integral time 50 … 5000 50 … 5000s 300 Ti = 300 seconds
40018 Fresh air control: 0:CO2 (T), 1:PIR (T), 2: CO2, 3:PIR 0 … 3 0 … 3 0 No influence because VAV is not used in this process
40019 Dead zone night mode 0 … 100 0,0 … 10,0 °C 60 No affect, if the device is allways in day mode, see Coil 14
40020 FG Thermostat setpoint 80 … 500 8,0 … 50,0 °C 170 No affect, if the device is allways in day mode, see Coil 14 and Coil 20
40021 DI1 mode selection: 0= not used, 1= day night by ext
contact 0 … 1 0 … 1 0 DI1 is not used to controll day/night mode
40022 DI1 operation Direction 0 … 1 0 … 1 0 DI1 not used ... No influence
40023 DI1 delay passive to active 0 … 60 0 … 60min 0 DI1 not used ... No influence
40024 DI1 delay active to passive 0 … 60 0 … 60min 5 DI1 not used ... No influence
40025 “man in house”-button, day extension period 1 … 480 1 … 480min 120 No affect, if the device is allways in day mode, see Coil 14
40026 DI1 boost level 0 … 1000 0,0 … 100,0% 0 DI1 not used ... No influence
40027 U1 mode: not used, CO2, T setpoint, T meas 0 … 3 0 … 3 0 U1 not connected
40028 Minimum of cooling actuator 0 … 500 0,0 … 50,0 % 0 Full operation range from 0%
40029 Maximum of cooling actuator 500 … 1000 50,0 … 100,0 % 1000 Full operation range to 100%
40030 Minimum of heating actuator 0 … 500 0,0 … 50,0 % 0 Full operation range from 0%
40031 Maximum of heating actuator 500 … 1000 50,0 … 100,0 % 1000 Full operation range to 100%
40032 Minimum of FAN output 0 … 500 0,0 … 50,0 % 0 Full operation range from 0%
40033 Maximum of FAN output 500 … 1000 50,0 … 100,0 % 1000 Full operation range to 100%
40034 Minimum of VAV output 0 … 500 0,0 … 50,0 % 0 Full operation range from 0%
40035 Maximum of VAV output 500 … 1000 50,0 … 100,0 % 1000 Full operation range to 100%
40036 Output scale FAN output Hi 0 … 1000 0,00 … 100,0% 1000 The process has not FAN... No influence
40037 Output scale FAN output Low 0 … 1000 0,00 … 100,0% 0 The process has not FAN... No influence
40038 Fan Control 0 … 3 0 … 3 0 The process has not FAN... No influence
40039 Low limit SP for the CO2 control 400 … 1000 400 … 1000ppm 700 The process have not CO2 control ... No influence
40040 High limit SP for the CO2 control 500 … 2000 500 … 2000ppm 1250 The process have not CO2 control ... No influence