AN302-0802 1
Remote control with the GCP-MG
Application Note 302
Revision 1.0, December 2008
Preparation ............................................................................................................................................. 1
GCP-30 setup .................................................................................................................................. 1
GCP-MG setup ................................................................................................................................ 1
Testing ................................................................................................................................................... 2
PLC program implementation .................................................................................................................... 5
References .............................................................................................................................................. 5
This Application Note describes how to perform remote control operations like genset start, stop and
alarm reset using Modbus and the GCP-MG gateway.
Preparation
All devices have to be configured first to a allow remote control as it is disabled by default. The
GCP-30 unit also requires some hardwiring.
GCP-30 setup
Before being able to use remote control, please check that the GCP-30 unit has been parameterized
accordingly. Refer to chapter Interface in your GCP-30 Series Genset Control manual.
• GCP-30 parameter 120 Control via COM X1X5 must be turned on
• Discrete input Automatic 2 (terminal 5) must be asserted.
• GCP-30 parameter 122 Ackn. F2,F3 via COM interf must be turned on if remote alarm acknowl-
edgment is required.
• GCP-30 must be in Automatic mode (Automatic LED must be lit)
GCP-MG setup
Remote control needs to be enabled on the GCP-MG gateway for each device.
Use a web browser and point it to the IP address of your GCP-MG gateway. The overview page will
appear.
To configure the Modbus access, enter the Configuration sub-menu and click on either the GCP-30
or LS 4 menu entry. This opens either the GCP-30 settings or the LS 4 settings.
For each device you require remote control, set to either control or monitored control as shown
below. Save the configuration settings.