Price BFC Series Manuel utilisateur

MANUAL – SERVICE + INSTALLATION
BACnet Flow Controller for Fan Filter Units
BFC Series
v300 –Issue Date: 05/16/19
© 2019 Price Industries Limited. All rights reserved.

BACNET FLOW CONTROLLER
TABLE OF CONTENTS
Product Overview
General Information....................................................... 1
Installation & Mounting Instructions
Typical Wiring ................................................................ 2
Input/Output Description ............................................... 2
Display Navigation
Initial Startup ................................................................. 3
Service Menu ................................................................ 4
Service Menu – Fan....................................................... 5
Service Menu – Filter ..................................................... 6
Service Menu – I/O........................................................ 7
Service Menu – BACnet ................................................ 8
Service Menu – Diagnostics .......................................... 8
Networking & Setup
Network Wire Specifications.......................................... 9
Network Layout........................................................... 10
Package/Component Identification.............................. 12
Location...................................................................... 13
Mounting..................................................................... 14
BAS Input Signal ......................................................... 15
Analog RPM Feedback................................................16
Wiring and Cables ....................................................... 17
Maintenance
Troubleshooting........................................................... 18
Specifications.............................................................. 19
BACnet points list for BFC firmware v2.0.0.................. 20

1
priceindustries.com |BACNET FLOW CONTROLLER - Manual
BACNET FLOW CONTROLLER
PRODUCT OVERVIEW
7
8
4
3
11
General Information
The BACnet Flow Controller (BFC) is a BTL listed DDC fan controller designed specifically for controlling flow through Fan Filter
Units (FFU) with EC motor technology. The BFC controls an EC motor through a local setpoint which is adjustable using a push
button interface on the BFC, by an analog BAS input voltage, or over BACnet.
In addition to fan control, the BFC can monitor filter pressure drop, filter loading, signal for filter changes, monitor the motor and
filter lifetime in hours, as well as report airflow and air temperature over the filter. This information can be viewed from the LCD
screen on the front of the BFC controller, or over BACnet on a building management system.
NOTE: This manual only covers the BFC controller. For troubleshooting an ECM motor, please visit http://www.priceindustries.com
and download the ECM Motor Troubleshooting Manual.
BACK OF BFC CONTROLLER
FRONT OF BFC CONTROLLER
1
34
1
2
3
4
Service Port RJ12 Jack
BACnet Connection RJ45
Jacks
Up and Down arrow
buttons for navigation
Menu button for info
menu and entering
Service menus
22
5
6
9
10
1
2
BACnet MS/TP Terminals
Motor #1 Jack
Thermistor Input
Analog Inputs
Contact Closure
24 VAC Binary Outputs
0-10 VDC Analog Outputs
Pressure Transducer
24 VAC Power Connection
BACnet Connection RJ45
Jacks
Service Port RJ12 Jack
55
6
12
2
3
4
10
11
789

2BACNET FLOW CONTROLLER - Manual |priceindustries.com
BACNET FLOW CONTROLLER
INSTALLATION & MOUNTING INSTRUCTIONS
Typical Wiring
Input/Output Description
Analog Outputs
AO1 Configurable for Unit Pressure, CFM (Air Flow),
RPM (Motor Speed), Filter Load and BAS.
AO2 Configurable for Unit Pressure, CFM (Air Flow),
RPM (Motor Speed), Filter Load and BAS.
24 VAC Binary Outputs
BO1 Red LED out
BO3 Green LED out
COM COMMON
Analog Inputs
AI1 Input voltage for remote fan speed control
AI2 Spare
Inputs
Thermistor Input Analog input for monitoring air over filter
temperature, 10k type J thermistor
Contact Closure Binary input
*Factory wired LED (Optional)
*See FFU Manual for LED Status.
RED LED
GREEN LED
COMMON
*Factory wired LED (Optional)
*See FFU-HE Manual for LED Status
Factory Wired
-24V COM
+24V HOT
RED CABLE
WHITE CABLE
BLACK CABLE
For every controller ordered with the
BACnet option, an optional CAT- 5 network
cable can be provided by Price.

3
priceindustries.com |BACNET FLOW CONTROLLER - Manual
BACNET FLOW CONTROLLER
DISPLAY NAVIGATION
Initial Startup
When the BFC controller is powered up with 24VAC it will display the following information.
PRICE
ELECTRONICS Start–up screen
BFC
VX.X.X Displays firmware version
ECM SPEED
X RPM Displays RPM of motor 1
CURRENT CFM
XX CFM Displays current airflow (only appears if constant flow motor program is selected)
CURRENT PRESSURE
XX INH2O Displays static pressure across filter
ECM SETPOINT
X % Displays ECM setpoint in % motor speed
UNIT STATUS
XXX Displays current unit status ( Off, Normal, No RPM Signal, and Overspeed)
CONTROL MODE
XXX Displays current control over the unit (BACnet, BAS, Local)
*LCD display will cycle between ECM SPEED, CURRENT CFM, CURRENT PRESSURE, ECM SETPOINT, UNIT STATUS, and
CONTROL MODE during normal operation.
Change ECM motor setpoint using and arrow keys
LOCAL SETPOINT
58% Setpoint will save after being adjusted with arrow keys
NOTE: Local setpoints are stored to EEPROM and will remain set after power failures.

4BACNET FLOW CONTROLLER - Manual |priceindustries.com
BACNET FLOW CONTROLLER
DISPLAY NAVIGATION
Service Menu
Hold down Menu button for 5 seconds, display will show ‘Passcode’. Use Up and Down arrow buttons to enter this sequence:
Down, Up, Up, Down.
Use Up and Down arrow buttons to navigate through the menu. Use the menu button to enter and exit specific menus.
Sub Menu Accessible Menu Items
SERVICE MENU
FAN
Unit Style Supply
Unit Size
Wheel Type
Motor Voltage
Motor Program
Motor Runtime
Reset Motor Runtime
CFM Offset (only appears if constant flow motor program is selected)
CFM Tweak (only appears if constant flow motor program is selected)
ECM Setback
*Refer to page 5 for additional menu detail
SERVICE MENU
FILTER
Filter Type
Filter Load
Load Trip
Filter Runtime
Reset Filter
*Refer to page 6 for additional menu detail
SERVICE MENU
I/O
BAS (AI1)
AI2
Contact Close
A01 Usage
A01 PresVal
A02 Usage
A02 PresVal
*Refer to page 7 for additional menu detail
SERVICE MENU
BACNET
MAC Address
Device Inst
Baud Rate
RS-485 Termination
*Refer to page 8 for additional menu detail
SERVICE MENU
DIAGNOSTICS
Restore Defaults
*Refer to page 8 for additional menu detail
PRESS MENU
TO EXIT

5
priceindustries.com |BACNET FLOW CONTROLLER - Manual
BACNET FLOW CONTROLLER
DISPLAY NAVIGATION
Service Menu – Fan
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through. Use the menu button to enter and
exit specific menu items.
UNIT STYLE SUPPLY Read Only - Factory set for supply or return airflow
UNIT SIZE
Displays the ECM motor calibration for FFU nominal size (2x2)
Selectable sizes are: 2’ x 2’, 2’ x 3’, 2’ x 4’
NOTE: Must match actual configuration of FFU.
WHEEL TYPE Read Only - Factory set for forward curved (FC) or backward curved (BC)
MOTOR VOLTAGE Adjust unit voltage type from 115/240/277
MOTOR PROGRAM Displays the current ECM motor program.
Selectable for: constant flow (Const Volum) or constant torque (Const Torque)
MOTOR RUNTIME
X HRS Read Only - Displays number of hours on motor since last reset
RESET MOTOR RUNTIME Resets Motor Runtime
ECM SETBACK Set ECM motor night setback (activated upon contact closure)
PRESS MENU
TO EXIT

6BACNET FLOW CONTROLLER - Manual |priceindustries.com
BACNET FLOW CONTROLLER
DISPLAY NAVIGATION
Service Menu – Filter
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through. Use the menu button to enter and
exit specific menu items.
FILTER TYPE
XXX
Adjust filter type, BTR, RSR.
BTR = Bench Top Removable RSR = Room Side Removable
FILTER LOAD
XX % Read Only - Displays % of filter loading based on new, clean filter pressure drop
LOAD TRIP
X.XX
Adjust filer load trip point
Example:
Filter loading trip point at 1.50 inH2O
Filter calibrated pressure: 0.16 inH2O
Filter load will trip at .24 inH2O
FILTER RUNTIME
X HRS Read Only – Displays number of hours on filter since last reset
RESET
FILTER Resets Filter Runtime - For calibrating filter during initial setup or upon filter replacement
PRESS MENU
TO EXIT

7
priceindustries.com |BACNET FLOW CONTROLLER - Manual
BACNET FLOW CONTROLLER
DISPLAY NAVIGATION
Service Menu – I/O
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through. Use the menu button to enter and
exit specific menu items.
BAS (AI1)
0 VDC Read Only – Displays current input BAS voltage for motor speed control
AI2
0 VDC Read Only – Displays input voltage to Analog Input 2
CONTACT CLOSE Read Only - Used to enable night setback when closed
AO1 USAGE
CFM
Configure Analog Output 1 for:
Unit Press - Unit Pressure; Range (0"-2"of H2O)
CFM - Airflow; Range (0 - 5000 CFM)
RPM - Range (0 - 2500 RPM). See page 11 for RPM details.
Filter Life - Range (0 - 100%)
BAS - 0-10VDC signal to BAS
Disabled
AO1 PRESVAL
XX VDC Read Only - Present Value for Analog Output 1
AO2 USAGE
CFM
Configure Analog Output 2 for:
Unit Press - Unit Pressure; Range (0”-2”of H2O)
CFM - Airflow; Range (0 - 5000 CFM)
RPM - Range (0 - 2500 RPM). See page 11 for RPM details.
Filter Life - Range (0 - 100%)
BAS - 0-10VDC signal to BAS
Disabled
AO2 PRESVAL
X VDC Read Only - Present Value for Analog Output 2
PRESS MENU
TO EXIT

8BACNET FLOW CONTROLLER - Manual |priceindustries.com
BACNET FLOW CONTROLLER
DISPLAY NAVIGATION
Service Menu – BACnet
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through. Use the menu button to enter and
exit specific menu items.
MAC ADDRESS
XX
Sets unit’s MAC address
NOTE: the MAC address (range 1-99) is added to the device instance.
Example: MAC address = 1, device instance = 100, total address for this BFC would be 101
DEVICE INST
X,XXX,XXX
This is the ‘software’ BACnet address and must be unique to your building site.
Range: 1 – 4,194,303
BAUD RATE
76800
BAUD RATE
This sets the BACnet MS/TP baud rate
76800 baud (default baud rate for Price products) - fastest
38400 baud
19200 baud
9600 baud (all BACnet devices must at least support this speed) – slowest
RS-485 TERM.
XXXXXXXX Enable and disable RS-485 termination on MS/TP segment.
PRESS MENU
TO EXIT
Service Menu – Diagnostics
Press Menu button to enter this menu. Use Up and Down arrow buttons to navigate through. Use the menu button to enter and
exit specific menu items.
RESTORE
DEFAULTS This allows a full controller reset, and will revert all user changes back to Price defaults
PRESS MENU
TO EXIT