preussen automation DALI Touch ME7 Manuel utilisateur

DALI Touch ME7
User guide


DALI Touch ME7
Contents
Description of the DALI Touch ME7 panel 4
Assembly 5
Initialization screen 6
Pre-set dynamic sequences 8
Custom dynamic sequences 9
Static pre-sets 11
The settings 12

preussen automation GmbH © 2016 | Flurweg 11 | 82402 Seeshaupt | Germany
DALI Touch ME7
Description of the DALI Touch ME7 panel
A The connector for connecting the
data network.
B The feeding connector.
C 3 x DALI line (the most upper one is
internally biased).
D Reserved for future use.
Earthing
The opening for connecting
Make the opening by removing one of
the indicated parts.
Fixing on the wall
Bend the indicated parts in the
direction outside from the corpus.
Screw on the reverse side of assembly
corpus.
4
A
B
-
+
D
C

Assembly on the solid wall
228 mm
80 mm
155 mm
3
2
1
Assembly (Plasterboard, OSB plate, etc.)
min.
90 mm
4- 45 mm
228 mm
155 mm
1
2
2
2
3
4
Assembly
5

preussen automation GmbH © 2016 | Flurweg 11 | 82402 Seeshaupt | Germany
DALI Touch ME7
Initialization screen
After the first power-on you have to
choose the mode of DALI Touch ME7
panel. You can choose either Tunable
White mode (TW mode) or RGB mode.
Furthermore you can choose whether
you would like to use the ambient light
sensor (closed loop) or not (open loop).
Select the DALI line you would like to
use. Multiple DALI lines can be selected.
Only DALI line 1 is internally biased. DALI
lines 2 and 3 needs external DALI power
supply.
Screen for addressing the ballast
depends on the mode selection – TW
or RGB. Press SCAN to start searching
process. All DALI devices present on
the DALI bus will appear the column on
the left with their corresponding DALI
addresses. Press the address to select
TW mode
TW control without sensor
TW control with sensor
RGB control
the DALI device. To identify DALI device
you use button IDENTIFY – DALI device
starts to periodically turn the light
on and off. Identification is aborted
by repeated press of the button. To
move DALI device into the groups for
TW or RGB control use corresponding
buttons: ”warm / cold” for TW mode or
”red /green /blue” for RGB mode. The
selected DALI device then appears in the
corresponding column. Use arrows up
and down to scroll the columns. Whole
group of devices can be identified using
corresponding TEST button. To remove
DALI device from a group use trash
button. The deleted device will appear
back in the left column. After finishing
the selection of DALI devices into the
groups press OK.
6
Use trash button to remove
the device from group.
Use OK button to finish and
save the settings.

7
RGB Mode
Identifies selected device.
Column with discovered devices.
Press corresponding button to
move the device into correct group.
Starts scanning the DALI lines. DALI Touch ME7 panel is
scanning the lines.
Home screen offers four basic options. User can choose between ”pre-set”, ”custom
dynamic sequences”, ”static preset” and manual control. Information panel at the
bottom of the screen informs about currently set mode and actual brightness level. In
the bottom-left corner home button is located – pressing home button returns device
to home screen. Use ”settings” button to change settings of DALI Touch ME7.
Manual control mode offers direct control over the DALI luminaires. In TW mode user
can control intensity and colour temperature of luminaires. In RGB mode user can
control hue, saturation and intensity. Control is performed when touching and moving
the scroll button of the corresponding slider. Return to the home screen can be done
using ”x” button or by using home button.
RGB control Information panel Manual
control

preussen automation GmbH © 2016 | Flurweg 11 | 82402 Seeshaupt | Germany
DALI Touch ME7
8
Pre-set dynamic sequences
When selecting ”pre-set dynamic se-
quences” in TW mode user will see three
dynamic white pre-sets:
”daylight”, ”activate” and ”moving”.
By pressing the buttons corresponding
pre-set sequences will be selected and
sequence timing screen will appear.
Parameters of dynamic sequence can
be set after selection of the sequence.
Repetition of the sequence can be
enabled or disabled and number of
repetition can be set. The user can
also define whether the light should be
turned off after the end of sequence
or not. The sequence starts after
confirmation by pressing OK button. The
activated sequence is indicated in the
information bar as well as with the play
sign placed on the corresponding pre-
set button. The sequence will be active
until other sequence or scene is set or
manual control is used. In RGB mode
there are eight pre-set options. Timing
settings looks the same as for TW mode.
Activated sequence.

9
Custom dynamic sequences
When selecting ”custom dynamic
sequences” in any mode a dialog for
setting, editing and creating custom
dynamic sequences will appear. On the
left side of the screen button for loading
existing custom dynamic sequences are
located. If password protection is set
you have to press ”unlock tools” and
type password first in order to add or
modify sequences. Security settings are
located in settings menu. On the right
side of the screen buttons for custom
sequences management are placed. You
can add new sequence by pressing ”add
new” button or edit the existing custom
sequence by pressing ”edit” button.
”duplicate” button serves for creating
a copy of existing sequence. ”modify
preset” button allows for modification
of pre-set sequence and saving it as
custom sequence. Undesired sequences
can be remove using button ”delete”.
Use touch keyboard to enter the label.
When adding new sequence you will
be prompted to enter a label for new
sequence.
Colour definition
Add / remove
point on timeline
Go to defined time
Previews the
sequence
Sequence
overview
Zoom / Un-
zoom overview

preussen automation GmbH © 2016 | Flurweg 11 | 82402 Seeshaupt | Germany
DALI Touch ME7
Colour definition in RGB (on the left) and TW (on the right) mode.
When pressing SAVE button new dynamic sequence is saved and appears on the left
side of the screen. By clicking on the sequence button the sequence is selected and
timing settings screen appears. Selected sequence is indicated also in the Information
panel.
10
Table des matières
Manuels Écran tactile populaires d'autres marques

IBASE Technology
IBASE Technology ASTUT-152-RE1S Manuel utilisateur

YASKAWA
YASKAWA TP 610C Manuel utilisateur

B&R
B&R Power Panel C Series Manuel utilisateur

Beijer Electronics
Beijer Electronics X2 control Manuel utilisateur

AXIOMTEK
AXIOMTEK GOT321W-521 Manuel utilisateur

TRIDONIC.ATCO
TRIDONIC.ATCO x-touchBOX Manuel utilisateur