CD30/35 MANUAL
&
START GUIDE
FOR USE ON
PPM ELECTROMAGNETIC EQUIPMENT
VF Advance
VF Premier
Mini VF
VFX
Magnatron

P/N SM1222
Rev 6
Print Date 2/14/2018
PPM Contact information:
AMERICAS EUROPE|MIDDLE EAST|AFRICA
PPM TECHNOLOGIES PPM TECHNOLOGIES EMEA Ltd.
500 E. Illinois St. Axis 40 Oxford Road
Ne berg, OR 97132 | USA Stokenchurch
(503) 538-3141 Buckinghamshire HP14 3SX
(800) 523-8123 toll free in the US +44 1494 682800
(503) 538-8575 fax +44 1494 682801 fax
Webpage: www.ppmtech.com
Printed in the USA
Manual Revision Log
REV # DATE CHANGE DESCRIPTION SECTIONS MODIFIED
BY
0 1/29/09 Original creation of quick start supplement for using the
CD30 on PPM EM equipment (VF, Magnatron, etc.) ALL NJD
1 3/1/09 Updated setup values, added –En note 4, 4.2 NJD
2 4/17/09 Clarified numerous sections, added QS addendum ALL NJD
3 7/28/09 Updated wiring diagram, added sections 1.3, 2.4 & 7x 2, 1.3, 2.4, 7x NJD
4 12/13/10 Added PPM Contact information Intro DER
5 8/8/12 Change section on how to hide service menus (C127) 3.2 (C127) CWJ
6 12/08/17 Revised sections for accelerometer use 2.2; 4.2; 4.3; QSA TNT
PPM Technologies reserves the right to alter at any time, without notice and without liability or other
obligations on its part, materials, equipment specifications, and models. PPM Technologies also reserves
the right to discontinue the manufacture of models, parts, and components thereof.

P/N SM1222
Rev 6
Print Date 2/14/2018
Table of Contents
1. Summary
1.1. Controller Specifications
1.2. Application
1.3. Safety Instructions
2. Wiring
2.1. Power (incoming to controller/outing to coil)
2.2. Feedback Sensor
2.3. System control wiring
2.3.1. Enable Unit
2.3.2. External Set Point (C038~ESP)
2.3.3. Status Relay (C040~r.b.)
2.3.4. 2
nd
Set Point (C038~2.)
2.4. Recommended Method for Installing a Frequency Controller
3. CD30/35 Important Menu Settings
3.1. Basic Display Navigation
3.2. C210, C143, C117, C127 (Save & Hide Settings)
3.3. C038 (Function Settings)
3.4. C040 (Service Settings)
4. Step by Step Setup Procedure
4.1. Wire CD30/35
4.2. Set CD30/35 Menu Settings for PPM equipment
4.3. Set Sensor Position using C051
4.4. Run Automatic Frequency Search (AFS)
4.5. Set Operating Characteristics (A, P)
4.6. Save User Settings & Hide Menus
5. Main Fault Messages
6. Troubleshooting
7. Special Applications
7.1. Master/Slave Control
7.2. Single Controller for Multiple Magnet Coils
CD30/35 Quick Start Addendum

P/N SM1222
Rev 6
Print Date 2/14/2018
1 – SUMMARY
The CD30 with software version “L” or higher is compatible with both Wright LT
conveyors and PPM VF & Magnatron conveyors. The main changes from the DMT include:
•The CD30/35 runs about half as quiet (10dbA less) as the DMT
•All settings are made by using the touch-panel and display (similar to a VFD touch-
panel) that is incorporated into the front panel of the CD30
•The CD30/35 does not come standard with a door potentiometer
•The CD30/35 does come with a local disconnect switch mounted onto the door
•The CD30/35 works as a replacement for both the DMT & MagII controllers, and will be
phased in PPM’s new standard controller for all applications for the above legacy
controllers.
1.1 – CONTROLLER SPECIFICATIONS
•Supply voltage: 115/230 v, +/-15%, 50/60 Hz
•Supply Power Draw: 3 to 4A
•Set Point: display, potentiometer 10kOhm, 0-10vdc, 0(4)-20mA
•Enable Input: contact, 24vdc
•Enable 2
nd
Setpoint: contact, 24vdc
•Status relay: change over contacts (max 250v, 2A)
•Fuse: 10A, Type B
•Operating Temperature: 0°C to 45°C
1.2 – APPLICATIONS
The CD30/35 has been tested & validated to work on the following equipment:
•VF Advance & Mini at 1200cpm (20hz) to 1450cpm (24.2hz)
•VF Premier & VFX at 750cpm (12.5hz) to 1200cpm (20hz)
•Magnatron at 1500cpm (25hz) to 2100cpm (35hz)
NOTE: CD30/35 will virtually work at any speed from 5hz to 60hz on all equipment, with or
without a feedback sensor. The above equipment speed ranges are just guidelines for our
typical equipment.
There are two sizes of CD30/35 Controller, a 10A & a 15A controller. The controller required is
base on the rules below regarding the application & product density:
•Use the CD30 (10A controller) if:
oProduct density is 20lb/ft^3 or less
•Use the CD35 (15A controller) if:
oProduct density is greater than 20lb/ft^3, or
oThe conveyor is being fed by a hopper

P/N SM1222
Rev 6
Print Date 2/14/2018
1.3 – SAFETY CONSIDERATIONS

P/N SM1222
Rev 6
Print Date 2/14/2018
2 – WIRING
Use Diagram as reference for all connections in section 2
(Consult the CD30 manual for more detail)

P/N SM1222
Rev 6
Print Date 2/14/2018
2.1 – POWER (IN/OUT)
•Incoming Plant Power (230v, 1PH, 50/60hz)
oIf local disconnect is used (typically on the door of the CD30):
1
st
hot leg into terminal 35 (L)
2
nd
hot leg into terminal 36 (N)
Ground into terminal 38 (PE)
oIf not local disconnect is present (i.e. chassis mounted)
1
st
hot leg into terminal 31 (L)
2
nd
hot leg into terminal 32 (N)
Ground into terminal 38 (PE)
•Outgoing power to coil (removable connector on bottom of CD30)
o1
st
hot leg into terminal 41 (A1)
o2
nd
hot leg into terminal 42 (A2)
oGround into terminal 43 (PE)

P/N SM1222
Rev 6
Print Date 2/14/2018
2.2 – FEEDBACK SENSOR
The CD30 is setup to operate with the standard DMT & Mag II sensor (Gordon p/n 06A578) as
well as PPM’s own accelerometer. It gets wired into the terminal strip on the CD30/35, so the
existing DMT connector on the end of the sensor wire must be cut off if replacing an existing
DMT or Mag II with a CD30/35.
Wiring connections for DMT/Mag II sensor:
•Black (ground) – terminal 1
•Red (+24v) – terminal 3
•White/grey (sensor) – terminal 12
•Black (large wire) (shield) – terminal 16
2.3 – SYSTEM CONTROL WIRING
2.3.1 – ENABLE UNIT
The Unit is enabled by closing contacts or by applying a 24v signal
•Input terminals for contacts: 5 & 6
•Input terminals for 24vdc: 4(-) & 5(+24v)
2.3.2 – EXTERNAL SET POINT (C038~E.S.P.)
NOTE: to enable external set point, set ESP = 1 (on menu C038)
•Potentiometer (10kOhm) input terminals: 7(-), 8(E), 10(+10v)
•0 to +10vdc input terminals: 7(-), 8(+0 to 10v)
•0(4) to 20mA input terminals: 7(-), 9(+0 to 20mA)
IMPORTANT – A minimum level for the output voltage can be selected when an external set
point is used (to adapt the set point to give a true minimum vibration of the feeder), this is
achieved by setting the internal set point “A” on the display. This must be done before
switching on the external set point source, through the controller. (Should there be no
requirement for a zero correction then “A” must be set to “0” before the external set point
function is selected).
2.3.3 – STATUS RELAY (C040~r.b.)
Internal relay contact on terminals 14 & 15
Wire into either a 100AC or 24DC relay
•When r.b.=0 (relay closes if output power is present)
•When r.b.=1 (relay closes if incoming (main plant power) power to the controller is
present & there are no error messages displayed)
2.3.4 – 2
ND
SET POINT (C038~2.)
2
nd
set point input terminals: 2 & 3

P/N SM1222
Rev 6
Print Date 2/14/2018
2.4 – RECOMMENDED METHOD FOR INSTALLING A FREQUENCY
CONTROLLER

P/N SM1222
Rev 6
Print Date 2/14/2018
3 – CD30 IMPORTANT MENU SETTINGS
(Consult the Wright CD30 manual for more detail)
3.1 – BASIC DISPLAY NAVIGATION